PACD011001C2
Outline of Control
Function UM Combination “MA1R Series” Using R-407C
427
[Defrosting operation]
The defrosting operation provides the following control functions.
[Defrosting operation ending conditions]
When the following conditions are met, the defrosting operation ends.
However, when the compressor stops during a defrosting operation, if condition (Tb > 12.5°C) is not met at
the next compressor startup, the defrosting operation starts and a 10-minute counter is activated when the
software startup is completed.
Defrost out
20 sec delay
20 sec delay
∗
1
∗
7
PI control
PI control
PI control
∗
3
SH control
PI control
52Hz+OFF
67Hz+OFF
30 sec
50 sec
LP protection control after
this point
2000pls
500(
∗
4)
Normal control
Normal control
According to
∗
6
OFF
Hot start
2 min
Defrost
Defrost IN
Exhaust from accumulator
INV
SVP
Outdoor EV
Outdoor fan
Indoor fan
4-way valve
Indoor EV
(unit with
thermostat ON)
OR
OR
&
DSHi>30
Th6 – Te>10
LP<0.1MPa
1 minute or more after
completion of defrosting
operation
Elapsed time of 10 minutes
Step at which
preparation mode
is activated is set
as upper limit.
SH control
according to
∗
2
Operate all indoor unit EV as follows : 1000 pls (50 sec)
→
0 pls (10 sec)
→
4-way
valve switching
→
0 pls (15 sec
∗
5)
Signal output during oil
return/defrosting operation
preparation
Defrost
preparation
flag
∗
1
Accumulator discharge operation ending
conditions
∗
2
SH control by outdoor unit EV
PI control activated when SHS = 10
(initial opening degree: 200 pls
In the case of an LP retry, the next PI
control is provided at SHS = 5.
When condition
∗
1 is met, the next startup
condition is reset to SHS = 10.)
∗
3
When returning to normal outdoor EV control,
the PI control is provided at that opening
degree.
∗
4
Opening degree of indoor unit EV during
defrosting operation
• Initial value: 500
• Next indoor unit EV opening degree (200-
2000) is determined based on (Th6 – Te < 15)
appearing time in previous defrosting operation
0 minute
→
+100
Less than 3 minutes
→
+0
3 minutes or more
→
–100
∗
5
0 pls maintained after elapsed time of 15
seconds until LP < 0.2 MPa
∗
6
Opens receiver solenoid valve for 60 seconds at
1 minute after the preparation mode is
activated.
However, the valve is closed when Th6 – Te < 0.
∗
7
CU-8MA1XPK
52Hz + ON
CU-10MA1XPK
71Hz + ON
CU-16, 20MA1XPK
52Hz + ON + ON
(V0807)
OR
When distribution pipe temperatures at all heat exchanger
outlets (during cooling operation) are as follows: Tb > 12.5°C
When defrosting operation is conducted for 10 minutes
Summary of Contents for Urban Multi MX1R Series
Page 13: ...PACD011001C2 xii Table of Contents ...
Page 23: ...PACD011001C2 2 Urban Multi MX1 ME1 Series Using R 22 ...
Page 125: ...Test Operation PACD011001C2 104 Test Operation Urban Multi MX1 ME1 Series Using R 22 ...
Page 155: ...Test Operation PACD011001C2 134 Test Operation Urban Multi MX1 ME1 Series Using R 22 ...
Page 239: ...PACD011001C2 218 Urban Multi MX1R ME1R Series Using R 407C ...
Page 245: ...Outline PACD011001C2 224 General Information Urban Multi MX1R ME1R Series Using R 407C ...
Page 293: ...Function PACD011001C2 272 Function Urban Multi MX1R ME1R Series Using R 407C ...
Page 343: ...Test Operation PACD011001C2 322 Test Operation Urban Multi MX1R ME1R Series Using R 407C ...
Page 427: ...PACD011001C2 406 UM Combination MA1R Series Using R 407C ...
Page 433: ...Product Outline PACD011001C2 412 General Information UM Combination MA1R Series Using R 407C ...
Page 501: ...Test Operation PACD011001C2 480 Test Operation UM Combination MA1R Series Using R 407C ...
Page 586: ...PACD011001C2 Wiring Diagrams Outdoor Unit Appendix 565 CZ 100 160HR1HE ...
Page 590: ...PACD011001C2 Wiring Diagrams Outdoor Unit Appendix 569 CZ 100 160HR1HP ...
Page 592: ...PACD011001C2 Wiring Diagrams Outdoor Unit Appendix 571 PA 24 26 28 30MA1XPK ...
Page 594: ...PACD011001C2 Wiring Diagrams Indoor Unit Appendix 573 CS 40 50 80 125LMHPP ...
Page 596: ...PACD011001C2 Wiring Diagrams Indoor Unit Appendix 575 2 3 Corner Type CS 25 32 40 63DM1HPK ...
Page 598: ...PACD011001C2 Wiring Diagrams Indoor Unit Appendix 577 CS 80 100 125FMHPP ...
Page 600: ...PACD011001C2 Wiring Diagrams Indoor Unit Appendix 579 CS 200 250EMHPK ...
Page 601: ...Wiring Diagrams Indoor Unit PACD011001C2 580 Appendix 2 6 Ceiling Type CS 32 63 100TMJPL ...
Page 604: ...PACD011001C2 Wiring Diagrams Indoor Unit Appendix 583 2 9 Small Duct Type CS 20 25NM1HPP ...