Function Urban Multi “MX1, ME1 Series” Using R-22
27
1.5
Safety for Restart
1.5.1
Restart Safety Timer
The compressor will not run for five minutes by making forced thermostat OFF condition in order to prevent
it from being turned on and off in rapid succession, and to equalize pressure in the refrigerant circuit. It
however restarts automatically after five minutes passes if it is in thermostat ON condition. The pressure
equalizing solenoid valve is actuated for 10 minutes (15 minutes for 8 and 10HP heating only) after the
compressor stops in order to equalize pressure.
If 10 minutes or more has elapsed since the compressor was turned off (15 minutes for 8 and 10HP heating
only) , turn the solenoid valve for equalizing pressure on for about 1 minute and equalize the pressure.
When heating, to prevent noise produced by the passing of indoor unit’s refrigerant to equalize pressure
after the compressor stops, fully close the indoor unit’s electronic expansion valve for 5 minutes (10
minutes for 8 and 10HP).
1.5.2
Soft Start
The following control is carried out to protect the compressor and inverter.
1. Operates at low frequency (fixed) for 1 minute after compressor starts. (Prevents liquid refrigerant
backflow)
2. Pressure equalizing and hot gas bypass solenoid valves open and start low load.
Soft Start of
Compressor
Thermostat
Thermostat ON
Thermostat
OFF
Thermostat OFF
Thermostat ON
Thermostat ON
Compressor
ON
ON
ON
OFF
OFF
5 minutes
Pressure equalizing
solenoid valve
1 minute
(Soft start)
10 minutes
(15 minutes for
8.10 HP heating only)
1 minute
(Pressure
equalizing)
1 minute
(Soft start)
Indoor unit
electronic expansion
valve (when heating)
Linear control
Fully closed
0 pulses
Linear control
Fully closed
0 pulses
1000 pulses
5 minutes
(10 minutes
for 8 and 10 HP)
240 pulses
1000 pulses
Linear control
OFF
OFF
ON
ON
OFF
ON
OFF
(VL005)
Compressor frequency
1 minute when started
Time
42Hz
(VG001)
Frequency during soft start
CU-5
42Hz
CU-8·10
42Hz+OFF
Summary of Contents for Urban Multi MX1R Series
Page 13: ...PACD011001C2 xii Table of Contents ...
Page 23: ...PACD011001C2 2 Urban Multi MX1 ME1 Series Using R 22 ...
Page 125: ...Test Operation PACD011001C2 104 Test Operation Urban Multi MX1 ME1 Series Using R 22 ...
Page 155: ...Test Operation PACD011001C2 134 Test Operation Urban Multi MX1 ME1 Series Using R 22 ...
Page 239: ...PACD011001C2 218 Urban Multi MX1R ME1R Series Using R 407C ...
Page 245: ...Outline PACD011001C2 224 General Information Urban Multi MX1R ME1R Series Using R 407C ...
Page 293: ...Function PACD011001C2 272 Function Urban Multi MX1R ME1R Series Using R 407C ...
Page 343: ...Test Operation PACD011001C2 322 Test Operation Urban Multi MX1R ME1R Series Using R 407C ...
Page 427: ...PACD011001C2 406 UM Combination MA1R Series Using R 407C ...
Page 433: ...Product Outline PACD011001C2 412 General Information UM Combination MA1R Series Using R 407C ...
Page 501: ...Test Operation PACD011001C2 480 Test Operation UM Combination MA1R Series Using R 407C ...
Page 586: ...PACD011001C2 Wiring Diagrams Outdoor Unit Appendix 565 CZ 100 160HR1HE ...
Page 590: ...PACD011001C2 Wiring Diagrams Outdoor Unit Appendix 569 CZ 100 160HR1HP ...
Page 592: ...PACD011001C2 Wiring Diagrams Outdoor Unit Appendix 571 PA 24 26 28 30MA1XPK ...
Page 594: ...PACD011001C2 Wiring Diagrams Indoor Unit Appendix 573 CS 40 50 80 125LMHPP ...
Page 596: ...PACD011001C2 Wiring Diagrams Indoor Unit Appendix 575 2 3 Corner Type CS 25 32 40 63DM1HPK ...
Page 598: ...PACD011001C2 Wiring Diagrams Indoor Unit Appendix 577 CS 80 100 125FMHPP ...
Page 600: ...PACD011001C2 Wiring Diagrams Indoor Unit Appendix 579 CS 200 250EMHPK ...
Page 601: ...Wiring Diagrams Indoor Unit PACD011001C2 580 Appendix 2 6 Ceiling Type CS 32 63 100TMJPL ...
Page 604: ...PACD011001C2 Wiring Diagrams Indoor Unit Appendix 583 2 9 Small Duct Type CS 20 25NM1HPP ...