![Panasonic U-4LE1R8 Service Manual Download Page 99](http://html1.mh-extra.com/html/panasonic/u-4le1r8/u-4le1r8_service-manual_4153774099.webp)
Mini VRF SYSTEM
PCB Settings
4
1. Outdoor Unit Control PCB
4-7
LED1, 2
(D302, D303)
LED (red × 2)
LED 1 and 2 blink alternately while automatic address setting is in progress.
Display the alarm contents for alarms that are detected by the outdoor unit.
•
•
Power LED
(D514)
LED (green): Power indicator
Indicates the DC 5V power on the outdoor unit control PCB.
RUN
2P plug : Start pin
Short-circuit this pin and apply a pulse signal to start all indoor units in that refrigerant
system.
STOP
2P plug : Stop pin
Short-circuit this pin and apply a pulse signal to stop all indoor units in that refrigerant
system.
CHK
2P plug (black)
Short-circuit during the test run operation.
Open the circuit after the test run.
SILENT
(CN-SILENT)
2P plug (White) : Socket for silent mode
CN-OPTION 1, 2
Plug for Demand Terminal (optional CZ-CAPDC3)
Used for installing the external timer for the silent mode.
(Refer to the section 1-14. Servicing and Maintenance Functions in service manual.)
AP
2P plug : Vacuuming pin
To perform vacuuming of the outdoor unit, short-circuit this pin and then turn the
power ON. All solenoid valves turn ON and vacuuming begins smoothly. (Do not
perform automatic address setting at this time.)
Release the short-circuit to return the unit to normal status.
•
•
MODE
2P plug : Indoor unit Heating/Cooling mode change pin
When operating the compressors to perform automatic address setting, operation
in Heating mode can be normally used. However, short-circuiting this pin performs
operation in Cooling mode. (Static signal)
Short-circuiting this pin during ordinary operation changes the mode from Cooling
to Heating (if the current mode is Cooling) or from Heating to Cooling (if the
current mode is Heating).
•
•
TEST
2P plug
This pin is used to test the PCB at the factory.
When the power is turned ON after this pin has been short-circuited, all output
signals will be output in sequence. (Sequential output does not occur if this pin is
short-circuited when the power is already ON.) Releasing this pin returns the unit
to normal control.
•
•
SM830209-00̲Mini̲VRF SYS.indb 7
SM830209-00̲Mini̲VRF SYS.indb 7
2012/01/11 18:26:37