3. Mini VRF System Alarm Codes
L04 Duplicated Setting of Outdoor System Address Error
Error Detection Method
Error Diagnosis
It is judged an error when the identical self-address communication on the indoor and outdoor wirings is received over 5 times
within 3 minutes.
1.
2.
Are other outdoor units using a duplicate setting?
1-1
2-1
2-2
Yes
No
2
When units are networked, first set the system address for each outdoor unit in the order
1-2-3 and then run auto address setting.
2-1
Run the auto address setting.