![Panasonic U-4LE1R8 Service Manual Download Page 67](http://html1.mh-extra.com/html/panasonic/u-4le1r8/u-4le1r8_service-manual_4153774067.webp)
Mini VRF SYSTEM
Trouble Diagnosis
3
3-27
3. Mini VRF System Alarm Codes
F08 Outdoor Air Temperature Sensor (TO
)
Error
Error Detection Method
1.
It is judged an error when open circuit or short circuit.
Error Diagnosis
2.
Sensor connector is connected to PC board properly.
1-1
1-2
Reconnect and check
Yes
No
1 Sensor
2 PC board
Replace PC board because of outdoor control PC board failure.
2-1
Resistance between sockets is infinity or
0 ohm.
1-2
Replace sensor
2-1
Yes
No
SM830209-00̲Mini̲VRF SYS.indb 27
SM830209-00̲Mini̲VRF SYS.indb 27
2012/01/11 18:25:11
2012/01/11 18:25:11