![Panasonic U-4LE1R8 Service Manual Download Page 113](http://html1.mh-extra.com/html/panasonic/u-4le1r8/u-4le1r8_service-manual_4153774113.webp)
Mini VRF SYSTEM
Service Checker
6
1. Outdoor Unit Maintenance Remote Controller
6-9
1-4. Monitoring Operations
Displays the indoor unit and outdoor unit sensor
temperatures.
<Operating procedure>
➀
Press and hold the
(CHECK) and
(CANCEL) buttons simultaneously for 4 seconds or
longer to engage temperature monitor mode.
During temperature monitoring,
(CHECK) illuminates.
(The display and operations are the same as for monitor
mode using the indoor unit remote controller.)
➁
Press the
(UNIT) button and select the indoor
unit to monitor.
➂
Press the temperature setting
buttons
and select the item code of the temperature to monitor.
The unit No. of the selected indoor unit, and the
temperature data, are displayed.
➃
To end monitoring, press the
(CHECK) button. The display returns to normal display mode.
NOTE
The display does not blink.