Mini VRF SYSTEM
Self-Diagnostics Function Table
5
1. Self-Diagnostics Function Table
5-2
Self-Diagnostics Function Table
Causes and corrections in instances when automatic address setting cannot be started.
Trouble
Cause and correction
The power LED on the outdoor unit control PCB does
not turn ON.
Check for any errors in the power wiring to the outdoor
unit, and check for a missing phase.
LED 1 and 2 on the outdoor unit control PCB do not
turn OFF when the outdoor unit power is turned ON,
and automatic address setting cannot be started.
Check the “Alarm Displays” table and correct the
problem.
An alarm appears immediately when automatic
address setting is started from the remote controller.
Nothing happens when the operator attempts to start
automatic address setting from the remote controller.
Check that the remote controller wiring and the inter-
unit control wiring are connected correctly.
Check that the indoor unit power is ON.
Causes and corrections in instances when automatic address setting starts, but cannot be completed successfully.
Trouble
Cause and correction
An alarm appears on the remote controller sometime
from several seconds to several minutes after
automatic address setting is started.
Check the “Alarm Displays” table and correct the
problem.
LED 1 and 2 on the outdoor unit control PCB indicate
that automatic address setting is in progress (the LEDs
blink alternately) for several minutes after automatic
address setting is started (the compressors may also
start and stop several times), however LED 1 and
2 never indicate that automatic address setting is
completed (turn OFF).
Check the alarm details on the “Outdoor Unit Control
PCB LED 1 and 2 Alarms” table, then check the “Alarm
Displays” table and correct the problem.
If alarm E15, E16, or E20 appears after automatic address setting is started, check the following items.
Alarm display
Alarm description
E15
The number of indoor units detected during automatic address setting was smaller than the
number of indoor units which was set with switch S004 on the outdoor unit PCB.
E16
The number of indoor units detected during automatic address setting was larger than the
number of indoor units which was set with switch S004 on the outdoor unit PCB.
E20
The outdoor unit received no serial signals from indoor units within 90 seconds after
automatic address setting was started.
•
•
•