3. Mini VRF System Alarm Codes
E09 More Than One Remote Controller Set to Main Error
Error Detection Method
Error Diagnosis
It is judged an error when more than one remote controller in a remote control group is set as the main remote controller.
Forgot to set one remote controller to sub in a 2-remote control group.
When using one wireless and one wired remote controller in a control group, forgot to set one of them to sub.
•
•
Method for setting a remote controller to sub (CZ-RTC2)
•
1.
2.
Set one of the 2 remote controllers to sub.
1-1
1 Remote
controller
Press and hold both + buttons for 4 seconds or longer.
Press button (Once the display changes from flashing to steady, the setting is complete).
Once you press button, the remote controller returns to its normal display.
This will display , the item “01” and the setting data “0001” or the like on the remote controller’s display.
Press Timer
1.
4.
5.
2.
3.
/ buttons to switch the setting data to “0000”. (0000:SUB 0001:Main)
Wireless remote controller
S003 (#3)
Sub: I
Main: O
S003 (#3)
Sub: ON
Main: OFF
S003 (#3)
Sub: ON
Main: OFF
CZ-RWSL2
CZ-RWSU2
Cable clamp
PCB cover
Adjustable
Corner Cap
Receiver PCB
ON
1
2
3
4
Screw
CZ-RWST2
S003
DIP Switch 3
CZ-RWSC2
Main/Sub Switch