Mini VRF SYSTEM
Trouble Diagnosis
3
3-15
3. Mini VRF System Alarm Codes
E06 Error in the Outdoor Unit Receiving Signal from the Indoor Unit
Error Detection Method
(When indoor unit(s) are connected)
Error Diagnosis
It is judged an error when there is no transmission (reply) from the indoor unit to the outdoor unit for a period of three minutes.
The ‘/’ in the table indicates the DC motor’s indoor unit board/AC motor’s indoor unit board.
•
There is no TEST pin on the AC motor’s indoor unit board.
•
For information on the procedures for replacing the indoor unit’s control board, refer to the manual that is packaged with
the indoor unit control PCB.
•
1.
2.
3
Remove the short
3-2
Are the DISP pin and/or CHK pin on the indoor unit control PC board
short-circuited?
Is the indoor unit powered off?
1-1
Is the indoor/outdoor operation line shorted, opened,
grounded or has a wrong contact?
2-1
3-1
Is the wireless remote controller and/or optional control PC board
connected to on the indoor unit’s control PC board?
3-2
Power on
2-1
Correct the wiring
3-1
3-3
3-5
Yes
Yes
Yes
No
No
No
Disconnect the connector mentioned above on the control PC board
of the indoor unit control PC board, and see whether the E06 goes off
after several minutes. (When doing so, if two remote controllers are
being used and the wireless remote controller is the main remote
controller, set the other remote controller as the main.)
3-3
Replace all optional control PC board and/or wireless remote control parts including wiring.
3-4
3-5
3-4
3-5
Yes
No
Indoor
units
control
PC board
1 Indoor unit
power
2 Indoor/
outdoor
operation
line
Yes
No
The indoor unit is not turned on.
The DISP pin of the indoor unit is shorted.
The signal output control PC board (optional control PC board) inside the indoor unit has failed.
•
•
•
There is a short, open, wrong contact or grounding of the indoor/outdoor operation line.
•
The thermistor inside the indoor unit is grounded.
•
Indoor unit control PC board failure
Replace board.
RC
OPTION
OPTION
CHK Pin
CHK Pin
DC Motor Model Indoor unit Control PC Board
AC Motor Model Indoor unit Control PC Board
DISP Pin
RC
DISP Pin