background image

© Panasonic HA Air-Conditioning (M) Sdn. Bhd. 2009. 
Unauthorized copying and distribution is a violation of law.

 

Order No: RAC1001001C8 

 

 
 

Indoor Unit 

Outdoor Unit

 

S-22KA1E5 
S-28KA1E5 
S-36KA1E5 
S-45KA1E5 
S-56KA1E5 
S-63KA1E5 
S-71KA1E5 

S-22KA1E5S 
S-28KA1E5S 
S-36KA1E5S 
S-45KA1E5S 

S-22YA1E5 
S-28YA1E5 
S-36YA1E5 
S-45YA1E5 
S-56YA1E5 

S-63UA1E5 
S-71UA1E5 
S-90UA1E5 
S-22NA1E5 
S-28NA1E5 
S-32NA1E5 
S-36NA1E5 
S-45NA1E5 
S-56NA1E5 

S-45MA1E5 
S-56MA1E5 
S-63MA1E5 
S-71MA1E5 
S-90MA1E5 

U-4LA1E5
U-5LA1E5
U-6LA1E5

U-4LA1E5-1
U-5LA1E5-1
U-6LA1E5-1

 

 

 

 

 

PRECAUTION OF LOW TEMPERATURE 

In order to avoid frostbite, be assured of no refrigerant leakage during the installation or repairing of refrigerant circuit.

 

 

WARNING 

This service information is designed for experienced repair technicians only and is not designed for use by the general public. 
It does not contain warnings or cautions to advise non-technical individuals of potential dangers in attempting to service a product. 
Products powered by electricity should be serviced or repaired only by experienced professional technicians. Any attempt to 
service or repair the products dealt with in this service information by anyone else could result in serious injury or death. 

Summary of Contents for S-32NA1E5

Page 1: ...1 U 5LA1E5 1 U 6LA1E5 1 PRECAUTION OF LOW TEMPERATURE In order to avoid frostbite be assured of no refrigerant leakage during the installation or repairing of refrigerant circuit WARNING This service information is designed for experienced repair technicians only and is not designed for use by the general public It does not contain warnings or cautions to advise non technical individuals of potent...

Page 2: ...e Indoor Unit NA1E5 Series 63 8 5 Low Static Pressure Hide Away Type Indoor Unit MA1E5 Series 65 8 6 Outdoor Unit LA1E5 Series 67 9 Printed Circuit Board 69 9 1 Wall Mounted Type Indoor Unit KA1E5 Series 69 9 2 60 x 60 Cassette Type Indoor Unit YA1E5 Series 71 9 3 95 x 95 Cassette Type Indoor Unit YA1E5 Series 72 9 4 Slim Hide Away Type Indoor Unit NA1E5 Series 72 9 5 Low Static Pressure Hide Away...

Page 3: ... Air Temperature Sensor Abnormality F20 01 244 19 4 Wired Remote Controller Thermistor Abnormality F20 02 245 19 5 Indoor Pipe Temperature Sensor Abnormality F21 01 246 19 6 Indoor Gas Temperature Sensor Abnormality F22 01 247 19 7 Indoor Address Double Registration F25 01 248 19 8 Total Quantity Capacity of Connected Indoor Unit Abnormality F30 01 249 19 9 Low Pressure Protection F31 01 250 19 10...

Page 4: ...4 23 6 Heating 430 24 Exploded View and Replacement Parts List451 24 1 Indoor Unit 451 ...

Page 5: ...gle outlet must be used If electrical circuit capacity is not enough or defect found in electrical work it will cause electrical shock or fire 9 This equipment is strongly recommended to install with Earth Leakage Circuit Breaker ELCB or Residual Current Device RCD Otherwise it may cause electrical shock and fire in case equipment breakdown or insulation breakdown 10 Do not use joint cable for ind...

Page 6: ...oint than standard solder typically the melting point is 50 F 70 F 30 C 40 C higher Please use a high temperature solder iron In case of the soldering iron with temperature control please set it to 700 20 F 370 10 C Pb free solder will tend to splash when heated too high about 1100 F 600 C 7 Power supply connection to the air conditioner Connect the power supply cord of the air conditioner to the ...

Page 7: ... Easy installation Refrigerant distributor Easy Servicing with 7 segment Error Code Display at panel 60 x 60 Cassette Type Indoor Unit o YA1E5 Series Light and thin design with thickness of 24cm allowing easy installation Easy Servicing with 7 segment Error Code Display at panel 95 x 95 Cassette Type Indoor Unit o UA1E5 Series Flexible and convenient Drain Up mechanism Light and thin design with t...

Page 8: ...over 2 The build in thermistor allows indoor temperature detection in accordance with indoor conditions by switching with indoor unit thermistor 3 Twin non polar wires make installation work easy 10m cable supplied as accessory Wireless Remote Control CZ RWS1 Heat pump models CZ RWC1 Cooling models 1 New ergonomic design 2 Built in 24 hours OFF ON timer ...

Page 9: ...n DC24V 2mA wire length max 150m COM shorted with Max rated current LV1 70 LV2 40 LV3 0 Forced Stop o With the Forced Stop input it is possible to override the air conditioning operation to force stop if signal is received from a fire alarm system BAS or etc From external device it is required to use a volt free contact relay for integration DC24V 2mA wire length max 150m When contact closed AC wi...

Page 10: ...ted unit will in priority to operate heat mode only o Priority mode is indicated in wired remote If remote setting is not same mode with Priority Mode indoor unit will standby until priority mode canceled power led blinks ON 2 5sec OFF 0 5sec Share External Signals to Next Outdoor Unit o The Cooling Heating Selector and Forced Stop input signals can be share with next outdoor systems o Maximum 30 ...

Page 11: ...ys for two remote controls are identical Last pressed button has priority main or slave is set at remote control Indoor units Remote side remote control Local side remote control Remote side Optional wired remote control Local side Optional wired remote control Common control Common control group Operation is possible using either wired or wireless remote control unit Last pressed button has prior...

Page 12: ...12 ...

Page 13: ...Max Input Power W 35 37 40 Type Cross Flow Fan Cross Flow Fan Cross Flow Fan Material ASG30K1 ASG30K1 ASG30K1 Motor type DC 8 Poles DC 8 Poles DC 8 Poles Input power W Output power W 30 30 30 Cool r p m 810 840 940 Lo Heat r p m 940 980 1020 Cool r p m 920 970 1070 Me Heat r p m 1020 1070 1140 Cool r p m 1030 1100 1200 Indoor Fan Speed Hi Heat r p m 1100 1170 1260 Moisture Removal L h Pt h 1 3 2 7...

Page 14: ...x Diameter mm 2 Thermostat Electronic Control Electronic Control Electronic Control Maximum C 32 32 32 Cool Minimum C 21 21 21 Maximum C 27 27 27 Indoor Operation Range Heat Minimum C 16 16 16 1 Cooling capacities are based on indoor temperature of 27 C Dry Bulb 80 6 F Dry Bulb 19 0 C Wet Bulb 66 2 F Wet Bulb and outdoor air temperature of 35 C Dry Bulb 95 F Dry Bulb 24 C Wet Bulb 75 2 F Wet Bulb ...

Page 15: ... ASG30K1 Motor type DC 8 Poles DC 8 Poles Input power W Output power W 30 30 Cool r p m 960 980 Lo Heat r p m 1040 1130 Cool r p m 1090 1120 Me Heat r p m 1170 1240 Cool r p m 1230 1260 Indoor Fan Speed Hi Heat r p m 1300 1350 Moisture Removal L h Pt h 2 5 5 3 3 2 6 7 Cool m 3 min ft 3 min 8 2 289 11 1 392 Lo Heat m 3 min ft 3 min 9 1 321 13 4 473 Cool m 3 min ft 3 min 9 7 342 13 2 466 Me Heat m 3...

Page 16: ...r Operation Range Heat Minimum C 16 16 1 Cooling capacities are based on indoor temperature of 27 C Dry Bulb 80 6 F Dry Bulb 19 0 C Wet Bulb 66 2 F Wet Bulb and outdoor air temperature of 35 C Dry Bulb 95 F Dry Bulb 24 C Wet Bulb 75 2 F Wet Bulb 2 Heating capacities are based on indoor temperature of 20 C Dry Bulb 68 0 F Dry Bulb and outdoor air temperature of 7 C Dry Bulb 44 6 F Dry Bulb 6 C Wet ...

Page 17: ...Motor type DC 8 Poles DC 8 Poles Input power W Output power W 30 30 Cool r p m 1040 1080 Lo Heat r p m 1160 1200 Cool r p m 1200 1270 Me Heat r p m 1300 1360 Cool r p m 1360 1460 Indoor Fan Speed Hi Heat r p m 1440 1520 Moisture Removal L h Pt h 3 6 7 6 4 2 8 8 Cool m 3 min ft 3 min 11 4 402 12 0 423 Lo Heat m 3 min ft 3 min 13 1 462 13 7 484 Cool m 3 min ft 3 min 13 7 484 14 7 519 Me Heat m 3 min...

Page 18: ...lectronic Control Electronic Control Maximum C 32 32 Cool Minimum C 21 21 Maximum C 27 27 Indoor Operation Range Heat Minimum C 16 16 1 Cooling capacities are based on indoor temperature of 27 C Dry Bulb 80 6 F Dry Bulb 19 0 C Wet Bulb 66 2 F Wet Bulb and outdoor air temperature of 35 C Dry Bulb 95 F Dry Bulb 24 C Wet Bulb 75 2 F Wet Bulb 2 Heating capacities are based on indoor temperature of 20 ...

Page 19: ...45 45 40 Type Turbo Fan Turbo Fan Turbo Fan Material ABS GF 10 ABS GF 10 ABS GF 10 Motor type DC 8 Poles DC 8 Poles DC 8 Poles Input power W Output power W 40 40 40 Cool r p m 430 430 440 Lo Heat r p m 500 520 540 Cool r p m 490 500 520 Me Heat r p m 545 565 585 Cool r p m 560 580 600 Indoor Fan Speed Hi Heat r p m 590 610 630 Moisture Removal L h Pt h 1 3 2 7 1 6 3 4 2 1 4 4 Cool m 3 min ft 3 min...

Page 20: ...tronic Control Electronic Control Electronic Control Maximum C 32 32 32 Cool Minimum C 21 21 21 Maximum C 27 27 27 Indoor Operation Range Heat Minimum C 16 16 16 1 Cooling capacities are based on indoor temperature of 27 C Dry Bulb 80 6 F Dry Bulb 19 0 C Wet Bulb 66 2 F Wet Bulb and outdoor air temperature of 35 C Dry Bulb 95 F Dry Bulb 24 C Wet Bulb 75 2 F Wet Bulb 2 Heating capacities are based ...

Page 21: ... ABS GF 10 Motor type DC 8 Poles DC 8 Poles Input power W Output power W 40 40 Cool r p m 450 490 Lo Heat r p m 560 580 Cool r p m 540 580 Me Heat r p m 605 625 Cool r p m 620 660 Indoor Fan Speed Hi Heat r p m 650 670 Moisture Removal L h Pt h 2 5 5 3 3 2 6 7 Cool m 3 min ft 3 min 6 5 229 7 2 254 Lo Heat m 3 min ft 3 min 8 3 293 8 6 303 Cool m 3 min ft 3 min 7 9 279 8 6 303 Me Heat m 3 min ft 3 m...

Page 22: ...Heat Minimum C 16 16 1 Cooling capacities are based on indoor temperature of 27 C Dry Bulb 80 6 F Dry Bulb 19 0 C Wet Bulb 66 2 F Wet Bulb and outdoor air temperature of 35 C Dry Bulb 95 F Dry Bulb 24 C Wet Bulb 75 2 F Wet Bulb 2 Heating capacities are based on indoor temperature of 20 C Dry Bulb 68 0 F Dry Bulb and outdoor air temperature of 7 C Dry Bulb 44 6 F Dry Bulb 6 C Wet Bulb 42 8 F Wet Bu...

Page 23: ... 71 Max Input Power W 110 120 130 121 131 141 121 131 141 Type Turbo Fan Turbo Fan Turbo Fan Material ABS GF 10 ABS GF 10 ABS GF 10 Motor type AC 3 Speeds 6 Poles AC 3 Speeds 6 Poles AC 3 Speeds 6 Poles Input power W Output power W 35 35 35 Cool r p m 370 390 410 400 420 430 400 420 430 Lo Heat r p m 370 390 410 400 420 430 400 420 430 Cool r p m 430 450 470 460 480 490 460 480 490 Me Heat r p m 4...

Page 24: ...r mm 2 Thermostat Electronic Control Electronic Control Electronic Control Maximum C 32 32 32 Cool Minimum C 21 21 21 Maximum C 27 27 27 Indoor Operation Range Heat Minimum C 16 16 16 1 Cooling capacities are based on indoor temperature of 27 C Dry Bulb 80 6 F Dry Bulb 19 0 C Wet Bulb 66 2 F Wet Bulb and outdoor air temperature of 35 C Dry Bulb 95 F Dry Bulb 24 C Wet Bulb 75 2 F Wet Bulb 2 Heating...

Page 25: ...a mmAq 0 0 29 3 0 0 29 3 Max Current A 0 39 0 44 0 49 0 44 0 49 0 54 Max Input Power W 77 82 87 83 88 93 Type Sirocco Sirocco Material PP PP Motor type AC 4 Speeds 4 Poles AC 4 Speeds 4 Poles Input power W Output power W 25 25 Cool r p m 640 660 690 700 730 750 Lo Heat r p m 640 660 690 700 730 750 Cool r p m 720 740 780 780 810 840 Me Heat r p m 720 740 780 780 810 840 Cool r p m 800 830 860 880 ...

Page 26: ...inimum C 21 21 Maximum C 27 27 Indoor Operation Range Heat Minimum C 16 16 1 Cooling capacities are based on indoor temperature of 27 C Dry Bulb 80 6 F Dry Bulb 19 0 C Wet Bulb 66 2 F Wet Bulb and outdoor air temperature of 35 C Dry Bulb 95 F Dry Bulb 24 C Wet Bulb 75 2 F Wet Bulb 2 Heating capacities are based on indoor temperature of 20 C Dry Bulb 68 0 F Dry Bulb and outdoor air temperature of 7...

Page 27: ...0 29 3 0 0 29 3 Max Current A 0 44 0 49 0 54 0 44 0 49 0 54 Max Input Power W 88 93 98 88 93 98 Type Sirocco Sirocco Material PP PP Motor type AC 4 Speeds 4 Poles AC 4 Speeds 4 Poles Input power W Output power W 40 40 Cool r p m 730 760 790 730 760 790 Lo Heat r p m 730 760 790 730 760 790 Cool r p m 840 870 900 840 870 900 Me Heat r p m 840 870 900 840 870 900 Cool r p m 940 970 1000 940 970 1000...

Page 28: ...inimum C 21 21 Maximum C 27 27 Indoor Operation Range Heat Minimum C 16 16 1 Cooling capacities are based on indoor temperature of 27 C Dry Bulb 80 6 F Dry Bulb 19 0 C Wet Bulb 66 2 F Wet Bulb and outdoor air temperature of 35 C Dry Bulb 95 F Dry Bulb 24 C Wet Bulb 75 2 F Wet Bulb 2 Heating capacities are based on indoor temperature of 20 C Dry Bulb 68 0 F Dry Bulb and outdoor air temperature of 7...

Page 29: ...29 3 0 0 29 3 Max Current A 0 55 0 60 0 65 0 50 0 55 0 60 Max Input Power W 99 104 109 110 115 120 Type Sirocco Sirocco Material PP PP Motor type AC 4 Speeds 4 Poles AC 4 Speeds 4 Poles Input power W Output power W 40 50 Cool r p m 770 800 830 730 770 800 Lo Heat r p m 770 800 830 730 770 800 Cool r p m 880 910 940 850 890 920 Me Heat r p m 880 910 940 850 890 920 Cool r p m 970 1000 1040 970 1010...

Page 30: ...inimum C 21 21 Maximum C 27 27 Indoor Operation Range Heat Minimum C 16 16 1 Cooling capacities are based on indoor temperature of 27 C Dry Bulb 80 6 F Dry Bulb 19 0 C Wet Bulb 66 2 F Wet Bulb and outdoor air temperature of 35 C Dry Bulb 95 F Dry Bulb 24 C Wet Bulb 75 2 F Wet Bulb 2 Heating capacities are based on indoor temperature of 20 C Dry Bulb 68 0 F Dry Bulb and outdoor air temperature of 7...

Page 31: ...essure Pa mmAq 49 5 69 7 49 5 69 7 Max Current A 0 80 0 85 0 90 0 80 0 85 0 90 Max Input Power W 180 190 200 180 190 200 Type Sirocco Sirocco Material ABS ABS Motor type AC 4 Speeds 4 Poles AC 4 Speeds 4 Poles Input power W Output power W 94 94 Cool r p m 690 715 740 690 715 740 Lo Heat r p m 690 715 740 690 715 740 Cool r p m 790 825 855 790 825 855 Me Heat r p m 790 825 855 790 825 855 Cool r p ...

Page 32: ... Cool Minimum C 21 21 Maximum C 27 27 Indoor Operation Range Heat Minimum C 16 16 1 Cooling capacities are based on indoor temperature of 27 C Dry Bulb 80 6 F Dry Bulb 19 0 C Wet Bulb 66 2 F Wet Bulb and outdoor air temperature of 35 C Dry Bulb 95 F Dry Bulb 24 C Wet Bulb 75 2 F Wet Bulb 2 Heating capacities are based on indoor temperature of 20 C Dry Bulb 68 0 F Dry Bulb and outdoor air temperatu...

Page 33: ...ernal Static Pressure Pa mmAq 49 5 69 7 49 5 69 7 Max Current A 0 80 0 85 0 90 0 80 0 85 0 90 Max Input Power W 180 190 200 180 190 200 Type Sirocco Sirocco Material ABS ABS Motor type AC 4 Speeds 4 Poles AC 4 Speeds 4 Poles Input power W Output power W 94 94 Cool r p m 600 625 Lo Heat r p m 600 625 Cool r p m 700 725 Me Heat r p m 700 725 Cool r p m 815 840 Indoor Fan Speed Hi Heat r p m 815 840 ...

Page 34: ... Cool Minimum C 21 21 Maximum C 27 27 Indoor Operation Range Heat Minimum C 16 16 1 Cooling capacities are based on indoor temperature of 27 C Dry Bulb 80 6 F Dry Bulb 19 0 C Wet Bulb 66 2 F Wet Bulb and outdoor air temperature of 35 C Dry Bulb 95 F Dry Bulb 24 C Wet Bulb 75 2 F Wet Bulb 2 Heating capacities are based on indoor temperature of 20 C Dry Bulb 68 0 F Dry Bulb and outdoor air temperatu...

Page 35: ...atic Pressure Pa mmAq 49 5 69 7 Max Current A 1 10 1 15 1 20 Max Input Power W 245 260 275 Type Sirocco Material ABS Motor type AC 4 Speeds 4 Poles Input power W Output power W 154 Cool r p m 700 730 770 Lo Heat r p m 700 730 770 Cool r p m 820 850 890 Me Heat r p m 820 850 890 Cool r p m 980 1010 1050 Indoor Fan Speed Hi Heat r p m 980 1010 1050 Moisture Removal L h Pt h 5 4 11 3 Cool m 3 min ft ...

Page 36: ...um C 16 1 Cooling capacities are based on indoor temperature of 27 C Dry Bulb 80 6 F Dry Bulb 19 0 C Wet Bulb 66 2 F Wet Bulb and outdoor air temperature of 35 C Dry Bulb 95 F Dry Bulb 24 C Wet Bulb 75 2 F Wet Bulb 2 Heating capacities are based on indoor temperature of 20 C Dry Bulb 68 0 F Dry Bulb and outdoor air temperature of 7 C Dry Bulb 44 6 F Dry Bulb 6 C Wet Bulb 42 8 F Wet Bulb 3 Heating ...

Page 37: ...0 26 0 26 0 21 0 21 0 21 0 Max Current Heat A 29 0 29 0 29 0 26 0 26 0 26 0 22 5 22 5 22 5 Cool W 6 20k 6 20k 6 20k 5 70k 5 70k 5 70k 4 40k 4 40k 4 40k Max Input Power Heat W 6 20k 6 20k 6 20k 5 70k 5 70k 5 70k 4 70k 4 70k 4 70k Starting Current A 25 24 23 21 20 19 15 14 14 Type Hermetic Motor Hermetic Motor Hermetic Motor Motor Type Brushless 4 Poles Brushless 4 Poles Brushless 4 Poles Compressor...

Page 38: ...tronic Control Electronic Control Protection Device Electronic Control Electronic Control Electronic Control Maximum C 43 43 43 Cool Minimum C 5 5 5 Maximum C 24 24 24 Outdoor Operation Range Heat Minimum C 15 15 15 1 Cooling capacities are based on indoor temperature of 27 C Dry Bulb 80 6 F Dry Bulb 19 0 C Wet Bulb 66 2 F Wet Bulb and outdoor air temperature of 35 C Dry Bulb 95 F Dry Bulb 24 C We...

Page 39: ...39 4 Dimensions 4 1 Wall Mounted Type Indoor Unit 4 1 1 S 22KA1E5 S 28KA1E5 S 36KA1E5 S 45KA1E5 S 22KA1E5S S 28KA1E5S S 36KA1E5S S 45KA1E5S ...

Page 40: ...40 4 1 2 S 56KA1E5 S 63KA1E5 S 71KA1E5 ...

Page 41: ...41 4 2 60 x 60 Cassette Type Indoor Unit 4 2 1 S 22YA1E5 S 28YA1E5 S 36YA1E5 S 45YA1E5 S 56YA1E5 ...

Page 42: ...42 4 3 95 x 95 Cassette Type Indoor Unit 4 3 1 S 63UA1E5 S 71UA1E5 S 90UA1E5 ...

Page 43: ...43 4 4 Slim Hide Away Type Indoor Unit 4 4 1 S 22NA1E5 S 28NA1E5 S 32NA1E5 S 36NA1E5 S 45NA1E5 S 56NA1E5 ...

Page 44: ...44 4 5 Low Static Pressure Hide Away Type Indoor Unit 4 5 1 S 45MA1E5 S 56MA1E5 ...

Page 45: ...45 4 5 2 S 63MA1E5 S 71MA1E5 S 90MA1E5 ...

Page 46: ...4LA1E5 U 5LA1E5 U 6LE1E5 U 4LA1E5 1 U 5LA1E5 1 U 6LE1E5 1 300 385 Air intake side 100 or more 200 or more 620 900 295 125 40 350 1340 24 515 140 140 Space for piping wiring and maintenance 500 or more Air outlet side Gravity point ...

Page 47: ...EMP SENSOR GAS SIDE TEMP SENSOR LOW PRESSURE SWITCH GAS BYPASS VALVE 4 WAY VALVE HIGH PRESSURE SWITCH OIL SEPARATOR 3 WAY 3 WAY LIQUID SIDE GAS SIDE HEAT EXCHANGER EVAPORATOR HEAT EXCHANGER TEMP SENSOR SUCTION TEMP SENSOR HEAT EXCHANGER SENSOR MUFFLER STRAINER EXPANSION VALVE CHECKVALVE EXPANSION VALVE LIQUID BYPASS VALVE STRAINER RECEIVER STRAINER ...

Page 48: ...nted Type Indoor Unit KA1E5 Series ZNR100 FUSE100 L N U1 U2 AC220V 240V 50Hz SC M URBAN NET ZNR101 ZNR102 6 2 60 x 60 Cassette Type Indoor Unit YA1E5 Series ZNR1 SSR1 L N U1 U2 AC220 230 240V 50Hz SC M M 1 URBAN NET ZNR2 ZNR3 FUSE100 ...

Page 49: ...s SSR1 RY H RY M RY L L N U1 U2 SC M 1 M 1 ZNR1 CR1 CR2 CR3 ZNR2 ZNR3 FUSE101 AC220 230 240V 50Hz URBAN NET 6 4 Slim Hide Away Type Indoor Unit NA1E5 Series RY H RY M RY L L N U1 U2 SC M 1 ZNR1 CR1 CR2 CR3 ZNR2 ZNR3 FUSE101 AC220 230 240V 50Hz URBAN NET ...

Page 50: ...50 6 5 Low Static Pressure Hide Away Type Indoor Unit MA1E5 Series RY H RY M RY L L N U1 U2 SC M 1 ZR1 CR1 CR2 CR3 ZR2 ZR3 FUSE101 AC220 230 240V 50Hz URBAN NET 6 6 Outdoor Unit LA1E5 Series ...

Page 51: ...51 7 Wiring Connection Diagram 7 1 Wall Mounted Type Indoor Unit KA1E5 Series ...

Page 52: ...52 7 2 60 x 60 Cassette Type Indoor Unit YA1E5 Series ...

Page 53: ...53 7 3 95 x 95 Cassette Type Indoor Unit UA1E5 Series ...

Page 54: ...54 7 4 Slim Hide Away Type Indoor Unit NA1E5 Series ...

Page 55: ...55 7 5 Low Static Pressure Hide Away Type Indoor Unit MA1E5 Series ...

Page 56: ...56 7 6 Outdoor Unit LA1E5 Series ...

Page 57: ...57 8 Electronic Circuit Diagram 8 1 Wall Mounted Type Indoor Unit KA1E5 Series ...

Page 58: ...58 ...

Page 59: ...59 8 2 60 x 60 Cassette Type Indoor Unit YA1E5 Series ...

Page 60: ...60 ...

Page 61: ...61 8 3 95 x 95 Cassette Type Indoor Unit UA1E5 Series ...

Page 62: ...62 ...

Page 63: ...63 8 4 Slim Hide Away Type Indoor Unit NA1E5 Series ...

Page 64: ...64 ...

Page 65: ...65 8 5 Low Static Pressure Hide Away Type Indoor Unit MA1E5 Series ...

Page 66: ...66 ...

Page 67: ...67 8 6 Outdoor Unit LA1E5 Series ...

Page 68: ...68 ...

Page 69: ...69 9 Printed Circuit Board 9 1 Wall Mounted Type Indoor Unit KA1E5 Series 9 1 1 Main PCB 9 1 2 Power PCB CN FM CN DCV ...

Page 70: ...70 9 1 3 Receiver PCB CN DISP 9 1 4 Error Code Display PCB CN CODE ...

Page 71: ...71 9 2 60 x 60 Cassette Type Indoor Unit YA1E5 Series 9 2 1 Main PCB CN FM CN STM2 CN EV LED CN DISP CN OPT3 CN UN CN TIMER CN REM CN TH2 CN TH1 OUTDOOR ADDRESS INDOOR ADDRESS JEM A CN STM1 ...

Page 72: ...N STM1 CN STM2 CN EV CN DISP CN OPT3 CN UN CN REM CN TH2 CN TH1 OUTDOOR ADDRESS INDOOR ADDRESS CN TIMER 9 4 Slim Hide Away Type Indoor Unit NA1E5 Series 9 4 1 Main PCB CN STM1 CN STM2 CN EV CN DISP CN OPT3 CN UN CN REM CN TH2 CN TH1 OUTDOOR ADDRESS INDOOR ADDRESS CN TIMER ...

Page 73: ...73 9 5 Low Static Pressure Hide Away Type Indoor Unit MA1E5 Series 9 5 1 Main PCB CN STM1 CN STM2 CN EV CN DISP CN OPT3 CN UN CN REM CN TH2 CN TH1 OUTDOOR ADDRESS INDOOR ADDRESS CN TIMER ...

Page 74: ...74 9 6 Outdoor Unit LA1E5 Series 9 6 1 Main PCB ...

Page 75: ...75 9 6 2 Noise Filter PCB CN TH1 CN OPT4 CN OPT3 CN V1 CN V2 CN OPT1 CN PWR CN OPT2 CN RY1 CN HOT ...

Page 76: ...76 9 6 3 Capacitor PCB DCN IN DCN OUT DCP IN DCP OUT ...

Page 77: ...ation mode of AUTO HEAT FAN COOL or DRY TEMP UP DOWN button Use to select the desired temperature AIR SWING AUTO MANUAL button Not applicable for Hide Away models FILTER RESET button Press to reset the FILTER RESET display after washing the filter TEST RUN button VENTILATION button ECONOMY button Function not available for this model ODOUR WASH button Function not available for this model CHECK bu...

Page 78: ...tton System reset SET button Local setting function ADDRESS button Use to change the address setting of indoor unit RC RESET button Use to clear the remote control setting from memory TIMER CLOCK SET buttons Use to set timer operation and current time AIR SWING AUTO MANUAL buttons Not applicable for Hide Away models MODE button Use to select operation mode of AUTO HEAT FAN COOL or DRY HEAT mode is...

Page 79: ...0m or less Sub1 Sub2 Sub3 Sub4 Sub5 Sub piping length 15m or less From outdoor unit to innermost indoor unit difference 55m or less Allowable piping length From 1 st branch to innermost indoor unit difference 30m or less Example of piping connection Indoor outdoor height difference Max 30m Indoor outdoor height difference Max 15m Main1 Main2 Main3 Main4 Sub1 Sub3 Sub5 Sub4 1st branch Outdoor unit ...

Page 80: ...9 52 mm 3 8 15 88 mm 5 8 Branch to Outdoor 4 5 6HP 9 52 mm 3 8 15 88 mm 5 8 Branch to Branch 9 52 mm 3 8 15 88 mm 5 8 Horizontally Vertically Branch pipe is required to installed at straight horizontal or vertical position This is to have even refrigerant distribution Min 30cm Bending point of connecting pipe is required minimum 30cm from branch pipe This is to avoid back pressure ...

Page 81: ... and horizontal installation 0 10 20 30 15 5 25 30 25 20 15 10 5 capacity ratio capacity ratio 20 30 50 70 80 10 90 40 0 95 0 90 0 85 1 00 1 00 0 95 0 90 0 85 60 pipe length m Cooling I D O D height difference m heating 0 10 20 30 15 5 25 30 25 20 15 10 5 capacity ratio capacity ratio 20 30 50 70 80 10 90 40 0 99 0 98 0 97 1 00 1 00 60 pipe length m 0 99 0 98 0 97 I D O D height difference m ...

Page 82: ...ry out the installation work with reliability on the place that can bears the weight of this unit sufficiently Insufficient strength leads to injury due to falling of the unit Carry out predetermined installation work in preparation for strong wind such as typhoon earthquake Imperfection in installation work may lead to accidents arisen from overturn etc The unit must be installed in accordance wi...

Page 83: ...e may still occur even if the separation distance is more than 1 meter 11 4 1 ACCESSORIES PACKED IN THE INDOOR UNIT CONTAINER Name Q ty Appearance Purpose Plate 1 Screw 5 Installation plate fixing screw Installation Instruction 1 This manual 11 4 2 SELECTING THE LOCATION FOR THE INDOOR UNIT Install the indoor unit once the following conditions are satisfied and after receiving the customer approva...

Page 84: ...generated 5 Avoid places near high frequency generators 11 4 3 INSTALLATION OF INDOOR UNIT HOW TO FIX INSTALLATION PLATE The mounting wall shall be strong and solid enough to prevent it from the vibration 128 Wall Wall Wall Installation plate 1 2 screw More than Measuring Tape Indoor unit 241 5mm 128mm 234 5mm 128 mm More than 1 5 6 A B C 4 3 More than 1 2 Dimension Model 1 2 3 4 5 6 S 22KA S 28KA...

Page 85: ...sert the piping sleeve to the hole 2 Fix the bushing to the sleeve 3 Cut the sleeve until it extrudes about 15 mm from the wall When the wall is hollow please be sure to use the sleeve for tube assembly to prevent dangers caused by mice biting the connecting cable CAUTION 4 Finish by sealing the sleeve with putty or caulking compound at the final stage 15 mm Putty or caulking compound ø70 through ...

Page 86: ...r unit Right and Right Bottom piping Cover for the bottom piping Tape it with piping in a position as mentioned in Fig below Cover for the right piping Piping Drain hose Right Rear piping Cover for the bottom piping Cover for the bottom piping Tape it with piping in a position a s mentioned in Fig below Cover for the right piping Piping Drain hose Cover for the left piping Cover for piping In case...

Page 87: ...ed scale in copper pipe 2 When there is a lot of brazings for long piping install a strainer midway of the piping The strainer is locally supplied 3 Use clean copper pipe with inner wall surface free from mist and dust Blow nitrogen gas or air to blow off dust in the pipe before connection 4 Form the piping according to its routing Avoid bending and bending back the same piping point more than thr...

Page 88: ...oard designed for this purpose the switch should disconnected all poles with a contact separation of at least 3 mm 3 Always ground the air conditioner with a grounding wire and screw to meet the LOCAL REGULATIONS 4 Be sure to connect the wires correctly to terminal board with connecting the crimp type ring terminal to the wires 5 Be sure to turn off the main power before installing and connecting ...

Page 89: ...to 1 minute once power is supplied do not operate the remote controller during this time Once the wires are connected to 1 remote controller group control and power is supplied to the indoor unit the A C No is automatically set To stop group control use follow the directions below and clear the A C No that was automatically set after disconnecting the wires for group control If it is not cleared t...

Page 90: ... receiving sound can be change over by the following steps a Press AUTO switch continuously for more than 26 sec to below 31 sec A pep pep pep pep pep pep sound will occur at the twenty sixth sec b Press the AC RESET button once Remote controller signal will activate the Remote controller sound setting mode c Press the AUTO switch once to select Remote controller receiving sound ON OFF A pep sound...

Page 91: ...ller will change to normal operation after 30 minutes NOTE 5 Use the outdoor unit to cancel the outdoor unit test run and the wired controller to cancel the wired controller test run For the test run method using the AUTO switch refer to the AUTO operation section in the installation instruction manual for the infrared receiver 11 4 9 CHECK THE FOLLOWING ITEMS WHEN INSTALLATION IS COMPLETE After c...

Page 92: ...hat can bears the weight of this unit sufficiently Insufficient strength leads to injury due to falling of the unit Carry out predetermined installation work in preparation for strong wind such as typhoon earthquake Imperfection in installation work may lead to accidents arisen from overturn etc The unit must be installed in accordance with applicable national and local regulations Any electrical ...

Page 93: ...ening the heat insulator Flat washer for M10 8 For fixing the hanging bolts Screw M5 4 Set screw for paper model and panel fixing Installation Instruction 1 This manual 11 5 2 SELECTING THE LOCATION FOR THE INDOOR UNIT Provide a check port on the piping side ceiling for repair and maintenance Install the indoor unit once the following conditions are satisfied and after receiving the customer appro...

Page 94: ...pecially in factories etc 3 Avoid places where inflammable gas is generated flows in contaminated or leaked 4 Avoid places where sulphurous acid gas or corrosive gas can be generated 5 Avoid places near high frequency generators Model name Height from the ceiling S 22YA1E5 S 28YA1E5 S 36YA1E5 S 45YA1E5 S 56YA1E5 280mm or more 11 5 3 INSTALLATION OF INDOOR UNIT CEILING OPENING DIMENSIONS AND HANGIN...

Page 95: ...midway of the piping The strainer is locally supplied 3 Use clean copper pipe with inner wall surface free from mist and dust Blow nitrogen gas or air to blow off dust in the pipe before connection 4 Form the piping according to its routing Avoid bending and bending back the same piping point more than three times This will result in hardening of the pipe 5 After deforming the pipe align centers o...

Page 96: ...leave it provisionally until the test comes to an end Feed water to the flexible drain hose and check the piping for leakage Be sure to check the drain up motor for normal operating and noise when electric wiring is complete When the test is complete connect the flexible drain hose to the drain port Feed water Drain hose Drain up motor Glue the joint Drain hose connection Use the clip accessory Ma...

Page 97: ...m a dedicated electrical circuit All electric work must be carried out by a qualified technician according to proper technical standards for electrical work and according to installation manual for installation work If circuits with insufficient capacity are used or if electrical work is not carried out properly electric shocks or fire may result Caution Be sure to install a current leakage breake...

Page 98: ...pply cables 1 Length m Leakage current breaker A Switch A Fuse A 2 Control Cable Remote Controller Cable Indoor unit 220V 240V 2 mm 2 100 15A 15A 15A 0 75 mm 2 0 5 2 mm 2 1 The maximum length shows a 2 voltage drop 2 Use an unshielded bus transmission line CONNECTING THE WIRES TO THE CONTROL BOX Remove the mounting screw remove the control box cover and then connect the wires by following the proc...

Page 99: ...method However if the wall type indoor unit is connected then manual setting is not possible Automatic setting By switching ON the indoor unit s power supply with the DIP switch where the A C No is set to 01 factory setting the A C No will be automatically set After activating the power for all indoor units the automatic setting takes approximately one minute Once the A C No is automatically set e...

Page 100: ...se damage to the drain pan and other components 3 Fit the decorative panel and ceiling wall together and confirm no gap in between Readjust indoor unit height if there is a gap between ceiling wall and decorative panel e l p m a x e d o o G Air conditioner unit Decorative panel Fit the insulator this part and be careful for cool air leakage Ceiling Air e l p m a x e d a B Cool air leakage no good ...

Page 101: ...ower supply and wait for at least 5 minutes before performing this operation NOTE 2 Do not short the remote control wires There is no protective circuit operation Normal operation will commence once the short is solved NOTE 3 During the test run ensure to operate the units in cooling mode prior to operating the units in heating mode Caution Operating the units in heating mode first may cause compr...

Page 102: ...cleaning temperature control etc As to parts to be sold separately With regards to installation of the parts sold separately follow the installation manual which is provided with the parts sold separately As for work specifications of the outdoor unit read the OUTDOOR UNIT INSTALLATION MANUAL attached to the outdoor unit ...

Page 103: ...sufficiently Insufficient strength leads to injury due to falling of the unit Carry out predetermined installation work in preparation for strong wind such as typhoon earthquake Imperfection in installation work may lead to accidents arisen from overturn etc The unit must be installed in accordance with applicable national and local regulations Any electrical work should only be carried out by qua...

Page 104: ... insulating refrigerant pipe joint Band 4 For fastening the heat insulator Flat washer for M10 8 For fixing the hanging bolts Screw M5 4 Set screw for paper model and panel fixing Installation Instruction 1 This manual 11 6 2 SELECTING THE LOCATION FOR THE INDOOR UNIT Provide a check port on the piping side ceiling for repair and maintenance Install the indoor unit once the following conditions ar...

Page 105: ...exist especially in factories etc 3 Avoid places where inflammable gas is generated flows in contaminated or leaked 4 Avoid places where sulphurous acid gas or corrosive gas can be generated 5 Avoid places near high frequency generators Model name Height from the ceiling S 63UA1E5 S 71UA1E5 S 90UA1E5 246mm or more 11 6 3 INSTALLATION OF INDOOR UNIT CEILING OPENING DIMENSIONS AND HANGING BOLT LOCAT...

Page 106: ...ing install a strainer midway of the piping The strainer is locally supplied 3 Use clean copper pipe with inner wall surface free from mist and dust Blow nitrogen gas or air to blow off dust in the pipe before connection 4 Form the piping according to its routing Avoid bending and bending back the same piping point more than three times This will result in hardening of the pipe 5 After deforming t...

Page 107: ...leave it provisionally until the test comes to an end Feed water to the flexible drain hose and check the piping for leakage Be sure to check the drain up motor for normal operating and noise when electric wiring is complete When the test is complete connect the flexible drain hose to the drain port Feed water Drain hose Drain up motor Glue the joint Drain hose connection Use the clip accessory Ma...

Page 108: ...om a dedicated electrical circuit All electric work must be carried out by a qualified technician according to proper technical standards for electrical work and according to installation manual for installation work If circuits with insufficient capacity are used or if electrical work is not carried out properly electric shocks or fire may result Caution Be sure to install a current leakage break...

Page 109: ...s Power supply cable Circuit breaker Minimum capacity Model name Power supply Minimum power cable supply cables 1 Length m Leakage current breaker A Switch A Fuse A 2 Control Cable Remote Controller Cable Indoor unit 220V 240V 2 mm 2 100 15A 15A 15A 0 75 mm 2 0 5 2 mm 2 1 The maximum length shows a 2 voltage drop 2 Use an unshielded bus transmission line CONNECTING THE WIRES TO THE CONTROL BOX Rem...

Page 110: ... method However if the wall type indoor unit is connected then manual setting is not possible Automatic setting By switching ON the indoor unit s power supply with the DIP switch where the A C No is set to 01 factory setting the A C No will be automatically set After activating the power for all indoor units the automatic setting takes approximately one minute Once the A C No is automatically set ...

Page 111: ... pieces of the decorative panel to the indoor unit There is direction information at decorative panel PIPING SIDE indication meaning the direction of piping side 4 Adjust between decorative panel fixing hole and indoor unit screw hole 5 Fix decorative panel with 4 screws with already fix at paper model for installation Before installing the decorative panel always remove the paper template Hinge A...

Page 112: ...en control board and control board cover 9 After complete install back removed part follow opposite procedure Warning Be sure to hook the air inlet grill string to prevent grill from falling and causing injury from it When using the infrared remote controller refer to the instruction manual supplied with the infrared remote controller option and the infrared receiver option CN STM1 CN STM2 Clamp t...

Page 113: ...ller will change to normal operation after 30 minutes NOTE 5 Use the outdoor unit to cancel the outdoor unit test run and the wired controller to cancel the wired controller test run For the test run method using the AUTO button on the infrared receiver refer to the Emergency operation section in the installation instruction manual for the infrared receiver 11 6 12 CHECK THE FOLLOWING ITEMS WHEN I...

Page 114: ... fluorescent lights Refer to the illustration below If using an inverter type fluorescent light keep the receiver at least 1 meter away from the light otherwise the remote control operation may not work properly Fluorescent light 300 mm or more Infrared Receiver Indoor unit Turn on the fluorescent lights and check to that the receiver properly receives the remote control signal while the fluoresce...

Page 115: ...t does not stick out 2 Remove the control box cover by removing the two screws and connect joint cord for wiring to the P C B connector CN DISP in the control box Note When securing the decorative panel to the unit be sure that the receiver s joint cord remains inside the decorative panel and is not caught on the ceiling Joint cord for receiver remains inside the decorative panel Ceiling Decorativ...

Page 116: ... cooling operation Again press the AUTO switch for 5 seconds or more it will beep twice to start the heating operation The setting of the fan speed and louver control will be fixed as shown by the table below While the indoor unit is running the POWER indicator on the infrared receiver will illuminate and it will light off when the indoor unit stops Heating operation is not available for indoor un...

Page 117: ...rs the weight of this unit sufficiently Insufficient strength leads to injury due to falling of the unit Carry out predetermined installation work in preparation for strong wind such as typhoon earthquake Imperfection in installation work may lead to accidents arisen from overturn etc The unit must be installed in accordance with applicable national and local regulations Any electrical work should...

Page 118: ...eat insulator 2 For insulating refrigerant pipe joint Band 4 For fastening the heat insulator Flat washer for M10 8 For fixing the hanging bolts Installation Instruction 1 This manual 11 8 2 SELECTING THE LOCATION FOR THE INDOOR UNIT Provide a check port on the piping side ceiling for repair and maintenance Install the indoor unit once the following conditions are satisfied and after receiving the...

Page 119: ...ollection hood with suf cient capacity Unit mm 2 Avoid installing the air conditioner in such circumstances where cutting oil mist or iron powder exist especially in factories etc 3 Avoid places where inflammable gas is generated flows in contaminated or leaked 4 Avoid places where sulphurous acid gas or corrosive gas can be generated 5 Avoid places near high frequency generators H 11 8 3 INSTALLA...

Page 120: ...ng Avoid bending and bending back the same piping point more than three times This will result in hardening of the pipe 5 After deforming the pipe align centers of the union fitting of the indoor unit and the piping and tighten them firmly with wrenches 6 Connect pipe to the service valve or ball valve which is located below the outdoor unit 7 After completed the piping connection be sure to check...

Page 121: ... may be required to take off this part for checking or servicing the drain up motor Please do not glue Make sure that there is no clearance here 2 Precautions in high humidity circumstance This air conditioner has been tested according to the JIS Standard Conditions with Mist and have been confirmed that there are no faults However if it is operated for a long time in high humid atmosphere dew poi...

Page 122: ... the terminal connection section Imperfect connection and fixing leads to fire etc 1 Select a power source that is capable of supplying the current required by the air conditioner 2 Feed the power source to the unit via a distribution switch board designed for this purpose the switch should disconnected all poles with a contact separation of at least 3 mm 3 Always ground the air conditioner with a...

Page 123: ... C No are set to a value other than 01 Once the wires are connected to 1 remote controller group control and power is supplied to the indoor unit the A C No is automatically set To stop group control use follow the directions below and clear the A C No that was automatically set after disconnecting the wires for group control If it is not cleared then the wired controller will not show any display...

Page 124: ...itched OFF When the power supply is turned ON the stored A C No is recalled To change the setting of the A C No turn OFF the power supply before resetting the DIP switch Ensure that there is no redundancy in the A C No Any redundancy can cause faulty control Ensure to set the A C No to 01 for 1 indoor unit A C No 01 02 03 04 05 06 07 08 Indoor unit printed circuit board DIP switch SW2 Unnecessary ...

Page 125: ...ller will change to normal operation after 30 minutes NOTE 5 Use the outdoor unit to cancel the outdoor unit test run and the wired controller to cancel the wired controller test run For the test run method using the AUTO button on the infrared receiver refer to the Emergency operation section in the installation instruction manual for the infrared receiver 11 8 11 CHECK THE FOLLOWING ITEMS WHEN I...

Page 126: ...weight of this unit sufficiently Insufficient strength leads to injury due to falling of the unit Carry out predetermined installation work in preparation for strong wind such as typhoon earthquake Imperfection in installation work may lead to accidents arisen from overturn etc The unit must be installed in accordance with applicable national and local regulations Any electrical work should only b...

Page 127: ...gerant pipe 2 2 Hose clip for thermal insulator 5 3 M10 Flat waher 8 4 Thermal insulator for drainage hole 1 5 Duct flange R 1 6 Duct flange L 1 7 Screws 4 8 Flexible pipe 1 5 and 6 should be installed when the duct will be installed at the return hole 11 9 2 SELECTING THE LOCATION FOR THE INDOOR UNIT Provide a check port on the piping side ceiling for repair and maintenance Install the indoor uni...

Page 128: ... to install the air conditioner in such place where it may not suck in oily steam Air conditioner Cooking table Ensure ample distance 2 Avoid installing the air conditioner in such circumstances where cutting oil mist or iron powder exist especially in factories etc 3 Avoid places where inflammable gas is generated flows in contaminated or leaked 4 Avoid places where sulphurous acid gas or corrosi...

Page 129: ...l charging etc 1 Brazing for piping a Execute brazing before tightening the flare nut b Brazing must be executed while blowing nitrogen gas This prevents generation of oxidized scale in copper pipe 2 When there is a lot of brazings for long piping install a strainer midway of the piping The strainer is locally supplied 3 Use clean copper pipe with inner wall surface free from mist and dust Blow ni...

Page 130: ...door unit Band Accessory Heat insulator for piping Local supply Heat insulator Accessory Hose clip Accessory Heat insulator Local supply The thickness must be at least 8 mm Flexible hose with heat insulator Accessory PVC pipe O D ø32 Local supply To be glued It may be required to take off this part for checking or servicing the drain up motor Please do not glue Make sure that there is no clearance...

Page 131: ...y result Warning Wiring shall be connected securely using specified cables and fix them securely so that external force of the cables may not transfer to the terminal connection section Imperfect connection and fixing leads to fire etc 1 Select a power source that is capable of supplying the current required by the air conditioner 2 Feed the power source to the unit via a distribution switch board...

Page 132: ...roup control and power is supplied to the indoor unit the A C No is automatically set To stop group control use follow the directions below and clear the A C No that was automatically set after disconnecting the wires for group control If it is not cleared then the wired controller will not show any display Instructions on clearing the A C No after automatic setup Turn OFF the indoor unit power su...

Page 133: ...ed To change the setting of the A C No turn OFF the power supply before resetting the DIP switch Ensure that there is no redundancy in the A C No Any redundancy can cause faulty control Ensure to set the A C No to 01 for 1 indoor unit A C No 01 02 03 04 05 06 07 08 Indoor unit printed circuit board DIP switch SW2 Unnecessary operation 1 ON 2 ON 1 2 ON 3 ON 1 3 ON 2 3 ON 1 2 3 ON A C No 09 10 11 12...

Page 134: ...eration after 30 minutes NOTE 5 Use the outdoor unit to cancel the outdoor unit test run and the wired controller to cancel the wired controller test run For the test run method using the AUTO button on the infrared receiver refer to the Emergency operation section in the installation instruction manual for the infrared receiver 11 9 11 CHECK THE FOLLOWING ITEMS WHEN INSTALLATION IS COMPLETE After...

Page 135: ...ration below If using an inverter type fluorescent light keep the receiver at least 1 meter away from the light otherwise the remote control operation may not work properly Fluorescent light 300 mm or more Infrared Receiver Indoor unit Turn on the fluorescent lights and check to that the infrared receiver properly receives the remote control signal while the fluorescent lights are lit If the earth...

Page 136: ...l box cover Control cable Control box Screw Remove the control box cover by removing the screws and connect the joint cord for wiring to the P C B connector CN DISP in the control box Connect joint cord for wiring to the P C B connector CN DISP in the control box of the indoor unit Secure and clamp the joint cord together with the other cable Core ...

Page 137: ...e cooling operation Again press the AUTO switch for 5 seconds or more it will beep twice to start the heating operation The setting of the fan speed and louver control will be fixed as shown by the table below While the indoor unit is running the POWER indicator on the infrared receiver will illuminate and it will light off when the indoor unit stops Heating operation is not available for indoor u...

Page 138: ...ndoor units at a maximum range of 8 meters from directly in front of the indoor unit If the remote controller is at an angle to the receptor unit the operating range may become shortened If using a single remote controller to operate several air conditioners address setting will be required To be discussed later INFRARED REMOTE CONTROLLER INSTALLATION PROCEDURE Use the holder to store the remote c...

Page 139: ...ress setting switch with a ballpoint pen or similar object to change the address setting as shown in the illustration to the right The address number displayed on the LCD changes in the order ADDRESS 1 ADDRESS 2 ADDRESS 3 GROUP ADDRESS 1 each time this switch is pressed LCD Only the air conditioner unit which address numbers match the address number on the LCD can be operated Note If the batteries...

Page 140: ...ck Terminal block Terminal block Infrared receiver LOCAL SETTING Press the SET switch 2 to operate the Local setting mode Use the switches TEMP to choose the Mode No Use the switches TIMER to choose the Setting value Press the SET switch 1 to check the setting details The setting details are displayed for approximately 4 seconds and then it exits the local setting mode If no operation is performed...

Page 141: ...r 003 for the Setting value Press the SELECT switch and use the switches TIMER to set the night time low noise end time Press the SET switch 1 to confirm After the end time is set the display proceeds to the start time setting Use the switches TIMER to adjust the time and the SET switch 1 to fix the start time setting After the start time is displayed for approximately 2 seconds it exits from loca...

Page 142: ...ONTROLLER SET UP LOCATION Select a place where the remote controller can be operated easily after obtaining approval from the customer Install in a place which is away from direct sunlight and as free from humidity as possible Install in a place which is as flat as possible to avoid the remote controller from warping If installed to a wall with an uneven surface damage to the LCD case or operation...

Page 143: ... indoor unit and the remote controller as shown in the illustration below The remote control cable is non polar At the time of shipment from the factory the connector cable used to connect the terminal block and connector CN1 is disconnected When connecting the remote controller wiring and installing the remote controller be sure to connect the cord to the connector CN1 The remote control cable su...

Page 144: ...emote control cable exposed use nippers to cut a notch into the upper case The feeding out direction can be either up or to the left or right Strip the end of the remote control cable which is to be connected to the remote controller Refer to the illustration on the right Route the remote control cable inside the lower case in accordance with the intended feeding out direction Refer to the illustr...

Page 145: ...ush the upper case until it snaps shut onto the lower case tab while being careful not to clamp the remote control cable and the connector cord Upper case Lower case If remote control cable is embedded 1 Embed an outlet box into the wall and then secure the remote controller base plate to the outlet box with the two accessory M4 screws Make sure that the base plate is flat against the wall at this...

Page 146: ...roller thermistor Connect the remote controllers Connect both remote controllers to terminals and on the indoor unit terminal block non polar Indoor unit Terminal block GROUP CONTROL Up to a maximum of 16 indoor units can be connected at the time of group control Do not connect the heat pump unit with the cooling unit only All in the group will be set by the remote controller thermistor setting wh...

Page 147: ...nit address 5 Once the indoor unit address is fixed with the SET switch and it will return to the check display screen for the indoor unit address It is possible to choose a different air conditioner No with the UP DOWN TEMP A C No switches under group control After selecting a different air conditioner No return to step 3 of the procedure 6 After checking the indoor unit address press the TEST RU...

Page 148: ...indoor units can be connected at the time of group control Do not connect the heat pump unit with the cooling only unit There are 2 methods for setting the group control address A C No an automatic and a manual setting method The A C No setting cannot be confirmed when using the automatic method To set each indoor unit s A C No use the manual setting method However if the wall type indoor unit is ...

Page 149: ...me the CHECK switch is pressed Further details of the problem can be displayed by pressing the SET switch while the general problem details are being displayed Example of current problem display Press the CHECK switch Further details of the problem can be displayed by pressing the SET switch Problem details Problem display REVIEWING THE PROBLEM HISTORY If the CHECK display on the wired controller ...

Page 150: ...ails of the problem can be displayed by pressing the SET switch Problem details Problem display The display can be switched between the previous problem and the one before that by pressing the UP DOWN TIMER switches After eliminating the cause of the problem press the CHECK switch once more to return to the normal display ...

Page 151: ...W 14 6kW 2 unit 6 unit U 5LA1E5 14 0kW 7 0kW 18 2kW 2 unit 8 unit U 6LA1E5 15 5kW 7 8kW 20 2kW 2 unit 8 unit 1 Use the above table to combine the number of indoor units with the appropriate capacity which matches the outdoor unit s cooling capacity rate Set the combined number of units to comply with the appropriate capacity 2 Assuming a system where all indoor units are operating at the same time...

Page 152: ...t use other parts except original optional parts described in catalog and manual Once installation work is completed check that there are no refrigerant gas in the room that can come into contact with sparks or flames from a fan heater stove or kitchen range which will cause toxic gases to be generated When performing piping work do not mix air except for specified refrigerant R410A in refrigerati...

Page 153: ... the area directly in front of the outtake the outdoor unit s air flow is reduced and the outflow may re enter short circuit causing the following outcome Reduced capacity Increased frost formation during heating or Operation stopped due to increased pressure Should an exceptionally strong wind blow to the area directly in front of the outtake of the outdoor unit there is the risk of damage due to...

Page 154: ...ore than 200 M ore than 500 M ore than 100 M o r e t h a n 2 0 0 2 For multiple units more than 2 units If there are obstacles on both sides If there are obstacles above the unit 1 For separate installation location Only if there are obstacles at the intake 2 For multiple units more than 2 units If there are obstacles on both sides If there are obstacles on the intake and the other side Less than ...

Page 155: ...rate installation location M ore than 300 M ore than 100 M ore than 200 M ore than 500 If there are obstacles above the unit 2 For multiple units up to 2 units Pattern 2 If there is an obstacle that is higher than the unit on the discharge side There is no limit to the height of the obstacle above the discharge If the upper part is open M ore than 100 M ore than 300 M o r e t h a n 2 0 0 M o r e t...

Page 156: ...tion 400 More than 200 If there are obstacles at the discharge If there are obstacles at the intake 1 2 E For multiple row installation on the roof etc M ore than 2000 M ore than 400 M ore than 500 M ore than 200 M ore than 100 M ore than 300 M ore than 1000 For one row installation setup For multiple units more than 2 units The dimensions for H A and L are shown in the following table A L H 200 H...

Page 157: ...depending on the installation set up there is risk of drain water running overhead If installation of a drain pipe is required install a drain elbow connected to the mounting hole at the bottom of the unit and connect it to a hose with an inner diameter of Ø 16 mm The hose is not supplied If drain holes of the outdoor unit are covered by a mounting base or by floor surface raise the unit in order ...

Page 158: ...ich are specially designed for use with R410A When connecting with flaring tools coat the flare section with ether based oil Ensure to use the flare nuts supplied with the unit when connecting this unit Only for storing or for open pipes 2 The local pipes can protrude from any four directions Make holes in the pipe panel for the pipes to penetrate it and lay the pipes accordingly It is recommended...

Page 159: ...h rod with a charge hose Once adjustments to the valve are completed ensure to tighten the valve cap according to the prescribed torque Tightening torque 10 7N m 14 7N m 1 1kgf m 1 5kgf m Precautions for connecting the pipes Ensure that the pipes do not come into contact with the compressor s bolts or exterior panel There is a risk of condensation from the 3 way valve coming out between the insula...

Page 160: ...n has completed ensure there is no gas leakage When tightening the flare nut coat the flares inner surface only with refrigerant oil on the flares Firstly screw in 3 4 turns by hand Ensure not to get oil on the screw part Refrigerant oil used is ether based Once the piping connections are completed perform leakage inspection using nitrogen gas Brazing work Always blow nitrogen gas through the pipe...

Page 161: ...ended to use the manifold with the side glass Cylinder Cylinder Gas refrigerant Possible Not possible Liquid refrigerant Use tools that are designed specifically for R410A for pressure resistance and to prevent mixing impurities Fill the refrigerant from the 3 way valve s service port on the liquid side For filling and replacing all refrigerant For refilling due to a leak For refilling refrigerant...

Page 162: ...occurs seal it accordingly Tie the cables with the provided binding strap so that they do not touch the compressor and the pipes When setting up the cables inside of unit install properly so that the front panel will not lift up Make sure that front panel mount correctly Use a round type terminal with an insulation sleeve for connecting to the terminal block Use the appropriate screwdriver for tig...

Page 163: ...ker A Switch A Fuse A Control Cable U 4LA1E5 220V 240V 4 mm 2 8 5 33A 40A 40A 0 75 mm 2 U 5LA1E5 220V 240V 6 mm 2 13 33A 40A 40A 0 75 mm 2 U 6LA1E5 220V 240V 6 mm 2 12 33A 40A 40A 0 75 mm 2 1 The maximum length shows a 2 voltage drop NOTE Use the standard power supply cables for Europe such as H05RN F or H07RN F which conforms to CENELEC HAR rating specifications or use the cables based on IEC sta...

Page 164: ... 50Hz Loop wire not possible Circuit Breaker Earth Circuit Breaker Circuit Breaker Earth Earth Earth Unit No 2 Unit No 1 Switch Circuit Breaker Remote controller Remote controller Outdoor unit Bus lines power supply switch OFF Central control device Bus line transmission wire Signal wire Remote controller cord Signal wire Greater than 0 5 mm2 Less than 2 0 mm2 2 wire overall extension less than 20...

Page 165: ... the indoor and outdoor unit to 000 erases At the time of shipment from the factory the setting is 000 2 Firstly switch the power supply ON for all indoor units and then switch the power supply ON for the outdoor units It is possible to perform simultaneously After switching ON the outdoor unit s power supply the address is automatically set After switching ON the power it takes approximately 1 mi...

Page 166: ...mber 000 cannot be used Set the order for the unit address starting from 001 without skipping as this facilitates the procedural tasks maintenance and inspection checks Before switching on the power supply of the outdoor unit s ensure that the bus lines power supply is switched on by setting switch SW5 to ON Position 10 Position 1 Position 100 Position 10 Position 1 Position 100 Position 10 Positi...

Page 167: ...perly insulated tool to operate the switch on the circuit board Do not use your finger or a metallic object Never switch the power supply ON until the installation has completed Supply electrical current through all indoor units and check the voltage Supply electrical current through all the outdoor units and check each inter phase voltage ...

Page 168: ...a wired remote controller attached check that the temperature values displayed during test run for the heat exchanger are as follows The heat exchanger temperature is displayed on the wired remote controller timer display screen The heat exchanger temperature during the cooling test run is 6 to 20 C and during the heating test run it is 25 to 55 C If the connected indoor unit s capacity exceeds 10...

Page 169: ...it s power supply back to ON By setting it to cooling operation the heating operation cannot be used Once the unit is in cooling operation and in order to return to heating cooling mode turn off the power supply Disconnect JP1 and switch ON the power supply Note Ensure to turn OFF the power supply before disconnecting JP1 There is a risk of damaging the P board by disconnecting JP1 while the power...

Page 170: ...6kW 14 6kW 2 unit 6 unit U 5LA1E5 1 14 0kW 7 0kW 18 2kW 2 unit 8 unit U 6LA1E5 1 15 5kW 7 8kW 20 2kW 2 unit 8 unit 3 Use the above table to combine the number of indoor units with the appropriate capacity which matches the outdoor unit s cooling capacity rate Set the combined number of units to comply with the appropriate capacity 4 Assuming a system where all indoor units are operating at the sam...

Page 171: ...t use other parts except original optional parts described in catalog and manual Once installation work is completed check that there are no refrigerant gas in the room that can come into contact with sparks or flames from a fan heater stove or kitchen range which will cause toxic gases to be generated When performing piping work do not mix air except for specified refrigerant R410A in refrigerati...

Page 172: ...tcome Reduced capacity Increased frost formation during heating or Operation stopped due to increased pressure Should an exceptionally strong wind blow to the area directly in front of the outtake of the outdoor unit there is the risk of damage due to the fan s high speed reverse rotation If the direction of the prevailing wind is known when operating the unit place the unit at an appropriate angl...

Page 173: ...es If there are obstacles above the unit 1 For separate installation location Only if there are obstacles at the intake 2 For multiple units more than 2 units If there are obstacles on both sides If there are obstacles on the intake and the other side Less than 500 More than 1000 M ore than 200 M ore than 200 Less than 500 More than 1000 M o r e t h a n 2 0 0 M ore than 500 M ore than 100 More tha...

Page 174: ...rate installation location M ore than 300 M ore than 100 M ore than 200 M ore than 500 If there are obstacles above the unit 2 For multiple units up to 2 units Pattern 2 If there is an obstacle that is higher than the unit on the discharge side There is no limit to the height of the obstacle above the discharge If the upper part is open M ore than 100 M ore than 300 M o r e t h a n 2 0 0 M o r e t...

Page 175: ...tion 400 More than 200 If there are obstacles at the discharge If there are obstacles at the intake 1 2 E For multiple row installation on the roof etc M ore than 2000 M ore than 400 M ore than 500 M ore than 200 M ore than 100 M ore than 300 M ore than 1000 For one row installation setup For multiple units more than 2 units The dimensions for H A and L are shown in the following table A L H 200 H...

Page 176: ...depending on the installation set up there is risk of drain water running overhead If installation of a drain pipe is required install a drain elbow connected to the mounting hole at the bottom of the unit and connect it to a hose with an inner diameter of Ø 16 mm The hose is not supplied If drain holes of the outdoor unit are covered by a mounting base or by floor surface raise the unit in order ...

Page 177: ...ased oil Ensure to use the flare nuts supplied with the unit when connecting this unit Only for storing or for open pipes 2 The local pipes can protrude from any four directions Make holes in the pipe panel for the pipes to penetrate it and lay the pipes accordingly It is recommended to apply additional substance to the cut area for anti rust protection Ensure to install pipe panels to prevent rai...

Page 178: ...e prescribed torque Tightening torque 10 7N m 14 7N m 1 1kgf m 1 5kgf m Precautions for connecting the pipes Ensure that the pipes do not come into contact with the compressor s bolts or exterior panel There is a risk of condensation from the 3 way valve coming out between the insulation material and the indoor unit s piping when you install the outdoor unit above then the indoor unit Ensure to ca...

Page 179: ...n has completed ensure there is no gas leakage When tightening the flare nut coat the flares inner surface only with refrigerant oil on the flares Firstly screw in 3 4 turns by hand Ensure not to get oil on the screw part Refrigerant oil used is ether based Once the piping connections are completed perform leakage inspection using nitrogen gas Brazing work Always blow nitrogen gas through the pipe...

Page 180: ...ended to use the manifold with the side glass Cylinder Cylinder Gas refrigerant Possible Not possible Liquid refrigerant Use tools that are designed specifically for R410A for pressure resistance and to prevent mixing impurities Fill the refrigerant from the 3 way valve s service port on the liquid side For filling and replacing all refrigerant For refilling due to a leak For refilling refrigerant...

Page 181: ...occurs seal it accordingly Tie the cables with the provided binding strap so that they do not touch the compressor and the pipes When setting up the cables inside of unit install properly so that the front panel will not lift up Make sure that front panel mount correctly Use a round type terminal with an insulation sleeve for connecting to the terminal block Use the appropriate screwdriver for tig...

Page 182: ... A Switch A Fuse A Control Cable U 4LA1E5 1 220V 240V 4 mm 2 8 5 33A 40A 40A 0 75 mm 2 U 5LA1E5 1 220V 240V 6 mm 2 13 33A 40A 40A 0 75 mm 2 U 6LA1E5 1 220V 240V 6 mm 2 12 33A 40A 40A 0 75 mm 2 1 The maximum length shows a 2 voltage drop NOTE Use the standard power supply cables for Europe such as H05RN F or H07RN F which conforms to CENELEC HAR rating specifications or use the cables based on IEC ...

Page 183: ... 50Hz Loop wire not possible Circuit Breaker Earth Circuit Breaker Circuit Breaker Earth Earth Earth Unit No 2 Unit No 1 Switch Circuit Breaker Remote controller Remote controller Outdoor unit Bus lines power supply switch OFF Central control device Bus line transmission wire Signal wire Remote controller cord Signal wire Greater than 0 5 mm2 Less than 2 0 mm2 2 wire overall extension less than 20...

Page 184: ... the indoor and outdoor unit to 000 erases At the time of shipment from the factory the setting is 000 2 Firstly switch the power supply ON for all indoor units and then switch the power supply ON for the outdoor units It is possible to perform simultaneously After switching ON the outdoor unit s power supply the address is automatically set After switching ON the power it takes approximately 1 mi...

Page 185: ...mber 000 cannot be used Set the order for the unit address starting from 001 without skipping as this facilitates the procedural tasks maintenance and inspection checks Before switching on the power supply of the outdoor unit s ensure that the bus lines power supply is switched on by setting switch SW5 to ON Position 10 Position 1 Position 100 Position 10 Position 1 Position 100 Position 10 Positi...

Page 186: ...perly insulated tool to operate the switch on the circuit board Do not use your finger or a metallic object Never switch the power supply ON until the installation has completed Supply electrical current through all indoor units and check the voltage Supply electrical current through all the outdoor units and check each inter phase voltage ...

Page 187: ...a wired remote controller attached check that the temperature values displayed during test run for the heat exchanger are as follows The heat exchanger temperature is displayed on the wired remote controller timer display screen The heat exchanger temperature during the cooling test run is 6 to 20 C and during the heating test run it is 25 to 55 C If the connected indoor unit s capacity exceeds 10...

Page 188: ...it s power supply back to ON By setting it to cooling operation the heating operation cannot be used Once the unit is in cooling operation and in order to return to heating cooling mode turn off the power supply Disconnect JP1 and switch ON the power supply Note Ensure to turn OFF the power supply before disconnecting JP1 There is a risk of damaging the P board by disconnecting JP1 while the power...

Page 189: ...at injury or damage to property may result This symbol indicates something that is REQUIRED Warning Ask the vendor or a qualified technician to perform the installation A faulty installation carried out by the customer may lead to electric shock or fire Be sure to carry out proper installation according to the installation manual A faulty installation may lead to electric shock or fire The unit mu...

Page 190: ...tput Cord for connecting the control board 1 For connecting on the control board Cord clamp 1 For securing the cord Tie 4 For securing the cord connection Screw 2 For installing the terminal module 11 15 1 OUTSIDE DIMENSIONS 87 12 153 120 12 11 15 2 TERMINAL MODULE INSTALLATION PROCEDURE 1 Install the terminal module with the screws provided 2 pcs so it matches the holes on the outdoor unit s cont...

Page 191: ... filter P C B Connect 10P to CN OPT1 2P to CN OPT2 and 4P to CN OPT3 3 Use the cord provided for P C B to connect to CN OPT4 on the main P C B and to CN OPT4 on the noise filter P C B Cord for connecting theP C B CN OPT4 Main P C B CN OPT4 4 Secure the cord clamp provided to the holes located on the right side of control panel ...

Page 192: ...he wire and cable connections Failure to do so may lead to electric shock or unit failure Connecting cable to H05RN F or H07RN F which conforms to CENELEC HAR rating specifications or use the cables based on IEC standard 245IEC57 245IEC66 Diameter 0 5 mm2 The maximum wire cable length is 150 m ...

Page 193: ...g to the Cooling Heating Selector on the terminal block The Cooling Heating Selector is sold separately as an option Model No CZ RD1 Refer to the installation manual provided with the Cooling Heating Selector for further details on the installation WHEN CONNECTING TO THE FORCED STOP INPUT With the Forced Stop input it is possible to override the air conditioning operation to force a stop if a sign...

Page 194: ... 4 wire to the terminal points 1 through 4 on the lower part of the terminal block and when transferring the Forced Stop input to the next system connect the wiring 2 wire to the terminal points 5 and 6 on the lower part of the terminal block When transferring to the next system for either case connect the wiring to the terminal points 1 through 6 on the lower part of the terminal block Secure the...

Page 195: ...195 ...

Page 196: ... with the cord clamp located on the right side of the control panel 3 Set the wiring and cables for the power and signal lines to the outdoor unit together and secure each wire and cable with the tie 4 Secure and clamp the power and signal lines with the tie set up close to the 3 way valve 5 Set up the wiring and cable for the outdoor unit piping and secure with a tie ...

Page 197: ...197 11 15 5 CHECK AFTER COMPLETING INSTALLATION Check the signals to make sure the unit operates properly using an external input device ...

Page 198: ...when setting up the wire and cable connections Failure to do so may lead to electric shock or unit failure Connecting cable to H05RN F or H07RN F which conforms to CENELEC HAR rating specifications or use the cables based on IEC standard 245IEC57 245IEC66 Diameter 0 5 mm2 The maximum wire cable length is 150 m ...

Page 199: ...g to the Cooling Heating Selector on the terminal block The Cooling Heating Selector is sold separately as an option Model No CZ RD1 Refer to the installation manual provided with the Cooling Heating Selector for further details on the installation WHEN CONNECTING TO THE FORCED STOP INPUT With the Forced Stop input it is possible to override the air conditioning operation to force a stop if a sign...

Page 200: ... 4 wire to the terminal points 1 through 4 on the lower part of the terminal block and when transferring the Forced Stop input to the next system connect the wiring 2 wire to the terminal points 5 and 6 on the lower part of the terminal block When transferring to the next system for either case connect the wiring to the terminal points 1 through 6 on the lower part of the terminal block Secure the...

Page 201: ...201 ...

Page 202: ... with the cord clamp located on the right side of the control panel 3 Set the wiring and cables for the power and signal lines to the outdoor unit together and secure each wire and cable with the tie 4 Secure and clamp the power and signal lines with the tie set up close to the 3 way valve 5 Set up the wiring and cable for the outdoor unit piping and secure with a tie ...

Page 203: ...203 11 16 3 CHECK AFTER COMPLETING INSTALLATION Check the signals to make sure the unit operates properly using an external input device ...

Page 204: ...ing to the instruction manual Furthermore ask the customer to keep this installation manual and the instruction manual in a safe place for later reference Warning Ask the vendor or a qualified technician to perform the installation A faulty installation carried out by the customer may lead to electric shock or fire Be sure to carry out proper installation according to the installation manual A fau...

Page 205: ...ble to H05RN F or H07RN F which conforms to CENELEC HAR rating specifications or use the cables based on IEC standard 245IEC57 245IEC66 Diameter 0 5 mm2 The maximum wire cable length is 150 meters Also avoid installing near power cable due to possible malfunction 1 Removing the decorative panel The decorative panel is embedded in the unit Remove the decorative panel from the mount You can separate...

Page 206: ...lock 3 Orange cord Connect to terminal point 3 on terminal block 4 Yellow cord Connect to terminal point 4 on terminal block When connecting to the short wire follow the diagram below and strip 8 to 10 mm of the wire s end exposing the base wire After inserting it into the connector securely crimp the connection so it does not disconnect Connector Short wire 8 10 mm Stripped segment 4 Connect the ...

Page 207: ...se Earth screw Please note the installation direction 11 17 3 OPERATING PROCEDURE 1 Enable or disable cooling heating selector Choose SW 1 or 2 By choosing 1 the set operations are turned OFF and by choosing 2 the set operations are turned ON 2 Choose either the fan operation or the cooling heating operation Choose SW 3 or 4 Choose 3 for the fan operation and choose 4 for the cooling heating opera...

Page 208: ...ng operation By choosing 5 the wired controller indicates priority to the cooling operation By choosing 6 the wired controller indicates priority to the heating operation 11 17 4 CHECK AFTER COMPLETING INSTALLATION Check the signals to make sure the each setting switch operates properly Be sure that choosing 2 to enable cooling heating selector ...

Page 209: ...heet 11 18 2 Indoor Outdoor unit piping installation For details on the allowable amount of refrigerant allowable pipe lengths and allowable elevation difference refer to the installation instructions provided with the indoor unit The diameter of the piping for the indoor and outdoor units differs depending on the model of the unit Refer to respective diameter of the piping for the indoor and the ...

Page 210: ...at connecting points After removing any impurities at the mouth of the pipe or the connecting points be sure to clean the inside of the pipe with nitrogen gas nitrogen displacement to prevent oxide scale forming on the inner surface of the pipe This step is extremely important when making the connections in the refrigerant piping Do not use an antioxidant If the size of the selected refrigerant pi...

Page 211: ...d side of the branch pipe 2 Wrap tape all around the areas where the insulating materials are joined in order to seal it Tape Local supply Thermal insulator Accessory Insulating material for refrigerant piping Note Do not use any adhesive agents on the connections between thermal insulator 3 Wrap a wide PVC tape all around the surfaces where the ends of the branch pipe and insulating materials are...

Page 212: ...r outdoor units connected as described in the instructions Are there any looped wires Refrigerant pipe Is the piping installed as described in the instructions Are the pipes sizes appropriate Does the pipe s length adhere to the specifications Is the branch pipe slant being appropriately done as described in the instructions Was vacuum removal sufficiently carried out Was the leak tightness test c...

Page 213: ...sor which could cause knocking noise current increase and undesirable vibration 1 Test operation from outdoor unit 2 Test run from indoor unit 1 Check that COOL or HEAT is displayed on the LCD 2 Press OFF ON to start the test operation 3 Within one minute after pressing the OFF ON button press TEST RUN button 4 Then the pipe temperature gas pipe will display on the LCD 5 Press TEMP A C No UP or DO...

Page 214: ...s operation Heat mode and operation mode stops after completion of deice control 13 2 Compressor Startup control During cool start condition where the compressor discharge temperature is less than 15 C compressor frequency perform a shift up after indoor heat exchanger temperature increase 1 C 15 seconds interval sampling If not in cool start condition compressor startup will skipped step 2 3 4 Ga...

Page 215: ... Liquid Bypass Valve Normal 480 pulse full open Indoor Fan Stop 1k 3k Deice Temperature sensor 30 sec z Deice control will end if below condition is fulfilled whichever comes first o Outdoor Heat Exchanger Discharge temperature achieved Outdoor Ambient Temperature C Deice Temperature sensor C 3 above 11 or more 3 to 10 5 or more Below 10 3 or more o 10 minutes has elapsed 13 4 Crank Case Heater Co...

Page 216: ...ow conditions happened o During Cool Mode Outdoor heat exchanger temp 58 C for 10 seconds o During Heat Mode Outdoor heat exchanger temp 30 C when outdoor ambient 5 C Outdoor heat exchanger temp 35 C when outdoor ambient 5 C Every interval of 30sec compressor frequency will reduce 10 if the outdoor heat exchanger temperature still at down zone The compressor frequency will only reduce max 3 times ...

Page 217: ...erload o Compressor Discharge Temperature Control o Total Current Protection o Night Time Low Noise Control 14 7 Compressor Restart Delay Control Compressor only can be startup after at least 3 minutes of compressor OFF During this control compressor cannot restart and gas bypass valve is ON 14 8 Outdoor Residual Heat Removal Control When compressor OFF outdoor fan operate for 1 minute to remove t...

Page 218: ...utes compressor will stop When outdoor ambient temperature is less than 10 C the system will restart 14 11 Heating High Outdoor Ambient Temperature Protection Control When outdoor is operating in Heat mode if outdoor ambient temperature is more than 35 C and compressor is operating for 15 minutes compressor will stop When outdoor ambient temperature is less than 27 C the system will restart ...

Page 219: ...OFF point ΔD is determined using Indoor Intake Temperature Remote Control Setting Temperature Default thermostat off point is shown in table below Low Static Hide away MA1 series Model Wall Mounted KA1 series 60 x 60 Cassette YA1 series 95 x 95 Cassette UA1 series Slim Hide away NA1 series 4 5 5 6 kW 6 3 7 1 9 0 kW Indoor fan speed Me 2 0 2 0 1 5 2 0 1 0 2 0 Thermostat OFF Point ΔD Indoor fan spee...

Page 220: ...ries Slim Hide away NA1 series 4 5 5 6 kW 6 3 7 1 9 0 kW Thermostat OFF Point ΔD 3 0 3 0 2 5 3 0 2 0 3 0 Thermostat OFF Cooling thermostat OFF point 1 0 Cooling thermostat OFF point 2 0 Cooling Intake air temperature remote controller temperature setting Softdry Softdry thermostat OFF point Thermostat OFF continues for 3 minutes if the Intake Air Temperature Internal Setting Temperature Thermostat...

Page 221: ...ve Control During Thermostat OFF the indoor unit expansion valve operation is controlled by the system 15 5 Auto Operation Operation mode is determined by indoor intake temperature and remote control setting temperature o Indoor intake temperature remote control setting temperature Heat mode is selected o Indoor intake temperature remote control setting temperature Cool mode is selected Indoor int...

Page 222: ...um Low Indoor fan tap SHi Hi Me Me Me Lo Lo SLo SSLo o DC fan motor Auto fan speed is specified to repetition of 8 patterns 1 pattern 10 seconds and follows odor cut control o AC fan motor Manual fan speed is based on remote control setting Mode Hi Me Lo Cool Fan o AC fan motor Auto fan speed is determined in table below and follows odor cut control Mode Hi Me Lo Stop Cool Fan During Soft Dry Mode...

Page 223: ...ol setting Stop Min Me 39oC 29oC 26oC 33oC 53oC Remote control setting Indoor heat exchanger temperature Indoor heat exchanger temperature Reduced 57oC 55oC for cassette o DC fan motor Auto fan speed depends on indoor heat exchanger temperature and air swing setting Automatic air swing Manual air swing Indoor heat exchanger temperature Stop Hi 39oC 29oC 35oC 26oC Reduced o DC fan motor control dur...

Page 224: ...ing during thermostat OFF compressor ON and temperature between indoor intake temperature and setting temperature is below 30 C Thermostat ON Sampling signal from outdoor unit Indoor fan Compressor ON OFF OFF ON Remote controller fan speed setting DC fan motor SLo AC fan motor Lo DC fan motor SLo AC fan motor Lo 20s Sampling time 120s 240s 240s 120s 240s 120s 60 Ducted D4 60 Ducted D3 75 95x95 Cas...

Page 225: ...ween indoor intake temperature and setting temperature is above 30 C Thermostat ON Sampling signal from outdoor unit Indoor fan Compressor ON OFF OFF ON Remote controller fan speed setting DC fan motor SLo AC fan motor Lo 20s Sampling time 120s 240s 240s 120s 240s 120s Skip sampling ...

Page 226: ...Heat removal control 144 Heat Thermostat OFF 20 32 50 68 20 Normal 20 26 32 45 20 45 Dew control 26 26 32 45 26 45 Cool Fan Thermostat OFF 20 26 32 45 20 45 Normal 20 26 32 45 20 45 Dew control 26 26 32 45 26 45 Dry Thermostat OFF 20 26 32 45 20 45 Automatic mode judgment 20 26 32 45 20 Operation stop 145 Heating automatic air swing control according indoor heat exchanger temperature 60oC 57oC Zon...

Page 227: ...op 0 Air swing direction setting Automatic Mode Condition Zone A 70 70 70 Zone B 20 70 20 53 42 70 Indoor heat exchanger temperature Zone C 20 20 20 Deice 10 Hot start 10 Heat removal control 20 Heat Thermostat OFF 20 Normal 20 70 20 53 42 70 Dew control 34 45 37 45 42 45 Cool Fan Thermostat OFF 20 70 20 53 42 70 Normal 37 Dew control 37 45 37 45 42 45 Dry Thermostat OFF 20 70 20 53 42 70 Automati...

Page 228: ...ion stop 0 Air swing direction setting Automatic Mode Condition Zone A 70 70 70 Zone B 20 70 20 50 40 70 Indoor heat exchanger temperature Zone C 20 20 20 Deice 10 Hot start 10 Heat removal control 20 Heat Thermostat OFF 20 Normal 20 70 20 50 40 70 Dew control 35 Cool Fan Thermostat OFF 20 70 20 50 40 70 Normal 30 Dew control 35 Dry Thermostat OFF 20 70 20 50 40 70 Automatic mode judgment 20 20 20...

Page 229: ... SLo SSLo OFF SSLo OFF SSLo SLo SSLo OFF Softdry Auto SSLo OFF SSLo OFF SSLo Auto SSLo OFF Cool Thermostat Compressor Indoor fan ON OFF 40 sec 50 sec 20 sec 120 sec 20 sec 40 sec 50 sec Thermostat Compressor Indoor fan ON OFF 40 sec 50 sec 20 sec 120 sec 20 sec 40 sec 50 sec During freeze prevention control this control is not triggered 15 9 Drain Pump Control This control applicable for 95 x 95 C...

Page 230: ...me will be multiplied by a correction factor Fan Number Group Correction factor Below Lo 50 Below Me 75 Except above 100 To inform user to clean the filter FILTER RESET display on the wired remote control LCD and FILTER LED on indoor unit remote control receiver indicator will blink for 10 seconds each time operation ON and operation OFF Indoor operation Filter LED Filter RESET LCD ON OFF Blink Bl...

Page 231: ...C o Indoor fan speed is Lo or AUTO Indoor fan speed changed from SLo to Lo and air swing angle follows dew prevention angle When received dew prevention signal from indoor unit compressor frequency reduces according to indoor heat exchanger temperature This control stops when any conditions below is satisfied o Thermostat OFF or compressor OFF o Remote control fan speed temperature setting changed...

Page 232: ...t Dry or OFF o Indoor Thermostat ON before Heat mode changes During this control o DC motor fan speed is fixed at Lo and airflow direction is fixed o AC motor fan speed is fixed at Lo and airflow direction is fixed o Indoor unit POWER LED is OFF This control stops when any conditions below is satisfied o 30 seconds has passed after the start of residual heat removal control o Compressor OFF Protec...

Page 233: ...tor s AUTO switch for more than 5s till one beep is heard Force Heating Mode 1 Press and hold the receptor s AUTO switch for more than 8s till two beeps is heard 2 Press AC RESET button on the wireless remote controller to enter heating mode Individual Response Mode Receiving Sound ON OFF Setting Mode 1 Press and hold the receptor s AUTO switch for more than 26s till six beeps is heard 2 Press AC ...

Page 234: ...N ON ON ON LED2 OFF ON ON ON ON ON ON ON OFF LED3 OFF ON ON ON ON ON ON OFF OFF LED4 OFF ON ON ON ON ON OFF OFF OFF LED5 OFF ON ON ON ON OFF OFF OFF OFF LED6 OFF ON ON ON OFF OFF OFF OFF OFF LED7 OFF ON ON OFF OFF OFF OFF OFF OFF LED8 OFF ON OFF OFF OFF OFF OFF OFF OFF LED9 OFF Outdoor Expansion COMP Outdoor Fan 4 Way Valve Indoor Fan Indoor Expansion Stop Stop Stop Normal Control Normal Control F...

Page 235: ...tch setting to all connected indoor units Indoor Units that having Outdoor Address setting same with the Outdoor Unit will memorized the signal to EEPROM 17 4 Power Save Control Power Save Setting Switch is located at outdoor main PCB With Power Save ON the maximum electrical current pulling from the power source is limited to 85 Usually it used when a 25A breaker is installed at power source line...

Page 236: ...fault control 001 10 seconds fan sampling operation 03 Thermostat OFF indoor fan control 002 Fixed fan speed operation I 000 default Thermostat OFF point ΔD 001 Cool ΔD 2 C Heat ΔD 2 C 002 Cool ΔD 4 C Heat ΔD 4 C 003 Cool ΔD 2 C Heat ΔD 2 C 04 Thermostat OFF point adjustment 004 Cool ΔD 4 C Heat ΔD 4 C I 000 Clear address 06 Outdoor unit address 001 199 Address 1 Address 199 I 10 Group address res...

Page 237: ... Night Time Low Noise ON and OFF timer by pressing Timer SET button o Press TEST RUN button to exit LOCAL SETTING MODE 17 5 3 Thermostat OFF Indoor Fan Control During thermostat OFF and compressor OFF indoor fan control can be alter to suit different application requirement Setting Value Description Operation details 000 Default control Fan control by EEPROM 001 10 seconds fan sampling Fan OFF for...

Page 238: ...at ΔD 4 C 000 Clear address 06 Outdoor unit address 001 199 Address 1 Address 199 Note 1 Mark in the column of the Individual setting shows a setting item individually made for each connected indoor unit Note 2 R represents remote control and I indoor unit Note 3 Start the setting from the setting value 000 17 6 1 Night Time Low Noise This control turns down outdoor unit operation noise by limitin...

Page 239: ... Motor Speed Lo DC Fan Motor Speed Lo 17 6 3 Thermostat OFF Point Adjustment The default thermostat OFF point might not be accurate depends on indoor unit installation condition thermostat OFF point adjustment is could be done 17 7 AC Reset Control When AC Reset at remote control is pressed all indoors outdoor in the system same Outdoor Address will perform micron reset All processing memory count...

Page 240: ...r unit main PCB F32 10 Compressor rotation error IPM abnormal compressor locked compressor lead wire connection outdoor unit main PCB F35 02 Outdoor DC fan motor error Outdoor DC fan motor outdoor unit main PCB connector CN FM1 CN FM2 F40 01 Outdoor temperature sensor error Outdoor temperature sensor lead wire outdoor unit main PCB connector CN TH1 F40 11 Compressor suction temperature sensor erro...

Page 241: ... indoor unit main PCB connector CN TH1 F22 01 Indoor gas pipe temperature sensor error Indoor gas pipe temperature sensor lead wire indoor unit main PCB connector CN TH1 F25 01 Indoor address double registration error Indoor unit address F26 01 Remote control communication line disconnection error Remote control lead wire terminal indoor unit main PCB connector CN REM F27 01 Indoor outdoor unit co...

Page 242: ...ion Conditions During operation of cooling and heating the signal received from drain level float switch in indoor unit is checked whether it is normal Malfunction Caused Faulty connector connection Faulty indoor unit drain pump motor Clogged drain hose Faulty indoor unit PCB main Troubleshooting ...

Page 243: ...50rpm or 50rpm Malfunction Caused Operation stop due to short circuit inside the fan motor winding Operation stop due to breaking of wire inside the fan motor Operation stop due to breaking of fan motor lead wires Operation stop due to fan motor Hall IC malfunction Operation error due to faulty indoor unit PCB main Abnormality Judgment Fan motor runs for 5 seconds and stops for 25 seconds and repe...

Page 244: ...ooling and heating the temperatures detected by the indoor intake air temperature sensor are used to determine sensor errors Malfunction Caused Faulty connector connection Faulty sensor Faulty indoor unit PCB main Abnormality Judgment After 20 minutes operation start and indoor fan running Continue for 120 seconds Troubleshooting ...

Page 245: ...ing and heating the temperatures detected by the wired remote controller thermistor are used to determine sensor errors Malfunction Caused Faulty wired remote controller Faulty indoor unit PCB main Abnormality Judgment Abnormality occur only when wired remote controller thermistor selection is made via Local Setting Troubleshooting ...

Page 246: ...g startup and operation of cooling and heating the temperatures detected by the indoor pipe temperature sensor are used to determine sensor errors Malfunction Caused Faulty connector connection Faulty sensor Faulty indoor unit PCB main Abnormality Judgment Continue for 120 seconds Troubleshooting ...

Page 247: ...g startup and operation of cooling and heating the temperatures detected by the indoor gas temperature sensor are used to determine sensor errors Malfunction Caused Faulty connector connection Faulty sensor Faulty indoor unit PCB main Abnormality Judgment Continue for 120 seconds Troubleshooting ...

Page 248: ...1 Malfunction Decision Conditions During standby startup and operation of cooling and heating the indoor unit detects the same address as that of its own Malfunction Caused Wrong indoor unit address setting Faulty indoor unit PCB main Troubleshooting ...

Page 249: ...e used to determine abnormal system connectivity Malfunction Caused No power supply to indoor unit Wrong total number max min of connected indoor unit Wrong total capacity max min of connected indoor unit Wrong indoor unit and outdoor unit address settings Indoor outdoor signal transmission error due to breaking of U1 U2 Faulty outdoor unit PCB main Troubleshooting ...

Page 250: ...d Clogged air filter of indoor unit Dust accumulation on the indoor outdoor unit heat exchanger Air short circuit at indoor outdoor unit 3 way valve closed Faulty outdoor unit fan motor Refrigerant shortage refrigerant leakage Clogged expansion valve or strainer Faulty outdoor unit low pressure switch Faulty outdoor unit PCB main Abnormality Judgment Continue 3 times in 60 minutes Troubleshooting ...

Page 251: ...nction Caused Clogged air filter of indoor unit Dust accumulation on the indoor outdoor unit heat exchanger Air short circuit at indoor outdoor unit 3 way valve closed Faulty outdoor unit fan motor Excess refrigerant Clogged expansion valve or strainer Faulty outdoor unit high pressure switch Faulty outdoor unit PCB main Abnormality Judgment Continue 8 times in 60 minutes Troubleshooting ...

Page 252: ...perature of thermostat ON indoor unit 5 C During cooling operation when the indoor pipe temperature of thermostat ON indoor unit 45 C Malfunction Caused Faulty sensor Faulty connector connection Faulty outdoor unit PCB main noise filter Faulty four way valve Abnormality Judgment Continue 3 times in 45 minutes Troubleshooting ...

Page 253: ...ooling and when outdoor unit receive indoor unit freezing abnormal signal indoor pipe temperature 0 C from thermostat OFF standby indoor unit Malfunction Caused Faulty sensor Faulty indoor unit expansion valve Faulty indoor unit PCB main Abnormality Judgment Continue 3 times in 45 minutes Troubleshooting ...

Page 254: ...operation of cooling and heating when IPM temperature data 95 C is detected by the IPM temperature sensor Malfunction Caused Air short circuit at outdoor unit Faulty outdoor unit fan motor Faulty outdoor unit PCB main Abnormality Judgment Continue 4 times in 30 minutes Troubleshooting ...

Page 255: ...ons During operation of cooling and heating when an input over current is detected by the current transformer CT in the outdoor unit PCB Malfunction Caused Excess refrigerant Faulty outdoor unit PCB main Abnormality Judgment Continue 6 times in 60 minutes Troubleshooting ...

Page 256: ... temperature data 110 C is detected by the compressor discharge temperature sensor Malfunction Caused Faulty compressor discharge temperature sensor 3 way valve closed Refrigerant shortage refrigerant leakage Clogged expansion valve or strainer Faulty outdoor unit PCB main Faulty compressor Abnormality Judgment Continue 6 times in 120 minutes Troubleshooting ...

Page 257: ...p and operation of cooling and heating when the PFC protection circuitry in the outdoor unit PCB main senses abnormal high DC voltage level Malfunction Caused Power supply surge Compressor windings not uniform Faulty outdoor unit PCB main Abnormality Judgment Continue 2 times in 1 minute Troubleshooting ...

Page 258: ...e inverter DC Peak sensing circuitry in the outdoor unit PCB main Malfunction Caused Faulty outdoor unit PCB main Faulty compressor Abnormality Judgment Continue for 7 times within 30 minutes DC peak occur within 30 seconds compressor startup Continue for 3 times within 30 minutes DC peak occur after 30 seconds compressor startup Troubleshooting ...

Page 259: ... failure is detected by checking the compressor running condition through the position detection circuitry in the outdoor unit PCB main Malfunction Caused Compressor terminal disconnect Faulty outdoor unit PCB main Faulty compressor Abnormality Judgment Continue 4 times in 20 minutes Troubleshooting ...

Page 260: ... motor feedback of rotation 2550rpm or 50rpm Malfunction Caused Operation stop due to short circuit inside the fan motor winding Operation stop due to breaking of wire inside the fan motor Operation stop due to breaking of fan motor lead wires Operation stop due to fan motor Hall IC malfunction Operation error due to faulty outdoor unit PCB main Abnormality Judgment Continue 2 times in 30 minutes ...

Page 261: ...ng startup and operation of cooling and heating the temperatures detected by the outdoor intake air temperature sensor are used to determine sensor errors Malfunction Caused Faulty connector connection Faulty sensor Faulty outdoor unit PCB main Abnormality Judgment Continue for 5 seconds Troubleshooting ...

Page 262: ...ng startup and operation of cooling and heating the temperatures detected by the compressor suction temperature sensor are used to determine sensor errors Malfunction Caused Faulty connector connection Faulty sensor Faulty outdoor unit PCB main Abnormality Judgment Continue for 5 seconds Troubleshooting ...

Page 263: ...ng startup and operation of cooling and heating the temperatures detected by the outdoor pipe temperature sensor are used to determine sensor errors Malfunction Caused Faulty connector connection Faulty sensor Faulty outdoor unit PCB main Abnormality Judgment Continue for 5 seconds Troubleshooting ...

Page 264: ...ng startup and operation of cooling and heating the temperatures detected by the outdoor defrost temperature sensor are used to determine sensor errors Malfunction Caused Faulty connector connection Faulty sensor Faulty outdoor unit PCB main Abnormality Judgment Continue for 5 seconds Troubleshooting ...

Page 265: ...ng startup and operation of cooling and heating the temperatures detected by the compressor discharge temperature sensor are used to determine sensor errors Malfunction Caused Faulty connector connection Faulty sensor Faulty outdoor unit PCB main Abnormality Judgment Continue for 5 seconds Troubleshooting ...

Page 266: ...ty F41 02 Malfunction Decision Conditions During compressor stop when the outdoor unit high pressure switch is open for 1 minute Malfunction Caused Faulty connector connection Faulty outdoor unit high pressure switch Faulty outdoor unit PCB main Troubleshooting ...

Page 267: ...ty F41 12 Malfunction Decision Conditions During compressor stop when the outdoor unit low pressure switch is open for 1 minute Malfunction Caused Faulty connector connection Faulty outdoor unit high pressure switch Faulty outdoor unit PCB main Troubleshooting ...

Page 268: ...ditions A current transformer CT open circuit is detected by checking the compressor running frequency 50Hz and CT detected input current 1 6A for continuously 60 seconds Malfunction Caused CT defective Faulty outdoor unit PCB main Compressor defective low compression Troubleshooting ...

Page 269: ...cision Conditions During startup and operation of cooling and heating the temperatures detected by the IPM temperature sensor are used to determine sensor errors Malfunction Caused Faulty indoor unit PCB main Abnormality Judgment Continue for 5 seconds Troubleshooting ...

Page 270: ...onditions During standby startup and operation of cooling and heating the outdoor unit detects the same address as that of its own on any other outdoor unit of same urban network Malfunction Caused Wrong outdoor unit address setting Faulty outdoor unit PCB main Troubleshooting ...

Page 271: ...on must be 50 to 130 of outdoor unit cooling capacity 4HP MAX 14 6 Rated 11 2 Total indoor capacity kW MIN 5 6 MAX 6 Total indoor capacity kW MIN 2 Combination 50 130 5HP MAX 18 2 Rated 14 0 Total indoor capacity kW MIN 7 0 MAX 8 Total indoor capacity kW MIN 2 Combination 50 130 6HP MAX 20 2 Rated 15 5 Total indoor capacity kW MIN 7 8 MAX 8 Total indoor capacity kW MIN 2 Combination 50 130 ...

Page 272: ... 1 2 1 3 1 4 1 5 1 6 15 10 5 0 5 10 15 20 outdoor air temperature WB heating capacity ratio 16 20 27 indoor air temperature DB cooling power input curve U 4LA1E5 0 0 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 0 9 1 0 1 1 1 2 1 3 1 4 10 0 10 20 30 40 50 outdoor air temperature DB cooling power input ratio 23 15 indoor air temperature WB 19 cooling capacity curve U 4LA1E5 0 0 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 0 ...

Page 273: ...5 1 6 15 10 5 0 5 10 15 20 outdoor air temperature WB heating capacity ratio 16 20 27 indoor air temperature DB cooling power input curve U 5LA1E5 0 0 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 0 9 1 0 1 1 1 2 1 3 1 4 10 0 10 20 30 40 50 outdoor air temperature DB cooling power input ratio 23 15 indoor air temperature WB 19 cooling capacity curve U 5LA1E5 0 0 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 0 9 1 0 1 1 1 2 1...

Page 274: ...5 1 6 15 10 5 0 5 10 15 20 outdoor air temperature WB heating capacity ratio 16 20 27 indoor air temperature DB cooling power input curve U 6LA1E5 0 0 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 0 9 1 0 1 1 1 2 1 3 1 4 10 0 10 20 30 40 50 outdoor air temperature DB cooling power input ratio 15 indoor air temperature WB 19 23 cooling capacity curve U 6LA1E5 0 0 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 0 9 1 0 1 1 1 2 1...

Page 275: ...2 2 10 10 5 2 72 11 2 3 05 11 9 3 41 13 4 3 88 14 8 3 91 39 7 56 1 68 9 02 2 26 10 5 2 92 11 2 3 28 11 9 3 66 13 4 4 03 14 8 4 06 Combination 50 TC Total Capacity kW PI Power Input kW Outdoor Indoor Air Temperature CWB Air Temp 14 0 16 0 18 0 19 0 20 0 22 0 24 0 CDB TC PI TC PI TC PI TC PI TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW kW kW 10 3 78 0 42 4 51 0 51 5 24 0 60 5 60 0 66 5 96 0...

Page 276: ...14 0 4 17 14 9 4 53 16 7 5 00 18 6 5 03 39 9 45 2 80 11 3 3 38 13 1 4 04 14 0 4 40 14 9 4 78 16 7 5 15 18 6 5 18 Combination 50 TC Total Capacity kW PI Power Input kW Outdoor Indoor Air Temperature CWB Air Temp 14 0 16 0 18 0 19 0 20 0 22 0 24 0 CDB TC PI TC PI TC PI TC PI TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW kW kW 10 4 72 0 85 5 63 0 94 6 54 1 03 7 00 1 09 7 46 1 14 8 37 1 25 9 2...

Page 277: ...14 5 4 67 15 5 5 00 16 5 5 36 18 5 5 83 20 2 5 86 39 10 5 3 63 12 5 4 21 14 5 4 87 15 5 5 23 16 5 5 61 18 5 5 98 20 2 6 01 Combination 50 TC Total Capacity kW PI Power Input kW Outdoor Indoor Air Temperature CWB Air Temp 14 0 16 0 18 0 19 0 20 0 22 0 24 0 CDB TC PI TC PI TC PI TC PI TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW kW kW 10 5 23 1 18 6 24 1 27 7 25 1 36 7 75 1 42 8 25 1 47 9 2...

Page 278: ...80 13 0 3 42 13 2 3 75 13 3 4 01 13 7 4 28 14 1 4 31 39 9 83 2 28 11 7 2 86 12 8 3 52 13 0 3 88 13 1 4 16 13 5 4 33 13 8 4 36 Combination 120 Capacity index kW 13 44 TC Total Capacity kW PI Power Input kW Outdoor Indoor Air Temperature CDB Air Temp 14 0 16 0 18 0 19 0 20 0 22 0 24 0 CWB TC PI TC PI TC PI TC PI TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW kW kW 10 9 07 1 49 10 8 1 73 12 6 ...

Page 279: ...12 9 3 75 13 2 4 02 13 5 4 05 39 8 31 1 92 9 92 2 50 11 5 3 16 12 3 3 52 12 7 3 80 13 0 4 07 13 3 4 10 Combination 100 Capacity index kW 11 20 TC Total Capacity kW PI Power Input kW Outdoor Indoor Air Temperature CDB Air Temp 14 0 16 0 18 0 19 0 20 0 22 0 24 0 CWB TC PI TC PI TC PI TC PI TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW kW kW 10 7 56 0 71 9 02 0 95 10 5 1 20 11 2 1 33 11 9 1 4...

Page 280: ... 10 7 2 78 12 0 3 00 12 9 3 25 39 6 80 1 64 8 11 2 13 9 42 2 64 10 1 2 75 10 7 2 86 12 0 3 10 12 7 3 37 Combination 80 Capacity index kW 8 96 TC Total Capacity kW PI Power Input kW Outdoor Indoor Air Temperature CDB Air Temp 14 0 16 0 18 0 19 0 20 0 22 0 24 0 CWB TC PI TC PI TC PI TC PI TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW kW kW 10 6 05 0 60 7 21 0 69 8 38 0 78 8 96 0 84 9 54 0 89...

Page 281: ...8 35 1 90 9 37 2 12 10 4 2 37 39 5 29 1 36 6 31 1 55 7 33 1 76 7 84 1 87 8 35 1 98 9 37 2 22 10 4 2 49 Combination 60 Capacity index kW 6 72 TC Total Capacity kW PI Power Input kW Outdoor Indoor Air Temperature CDB Air Temp 14 0 16 0 18 0 19 0 20 0 22 0 24 0 CWB TC PI TC PI TC PI TC PI TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW kW kW 10 4 54 0 47 5 41 0 56 6 28 0 65 6 72 0 71 7 16 0 76 ...

Page 282: ...57 5 24 0 68 5 60 0 74 5 96 0 79 6 69 0 92 7 42 1 04 21 3 78 0 47 4 51 0 57 5 24 0 69 5 60 0 74 5 96 0 80 6 69 0 93 7 42 1 05 23 3 78 0 48 4 51 0 59 5 24 0 70 5 60 0 76 5 96 0 82 6 69 0 95 7 42 1 08 25 3 78 0 49 4 51 0 60 5 24 0 72 5 60 0 78 5 96 0 85 6 69 1 00 7 42 1 16 27 3 78 0 50 4 51 0 63 5 24 0 76 5 60 0 84 5 96 0 91 6 69 1 08 7 42 1 26 29 3 78 0 54 4 51 0 67 5 24 0 82 5 60 0 90 5 96 0 98 6 ...

Page 283: ... 6 4 65 15 8 5 01 16 2 5 48 16 7 5 51 39 12 3 3 19 14 7 3 77 15 1 4 43 15 3 4 79 15 5 5 17 16 0 5 54 16 4 5 57 Combination 120 Capacity index kW 16 80 TC Total Capacity kW PI Power Input kW Outdoor Indoor Air Temperature CDB Air Temp 14 0 16 0 18 0 19 0 20 0 22 0 24 0 CWB TC PI TC PI TC PI TC PI TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW kW kW 10 11 3 2 15 13 5 2 39 15 7 2 64 16 8 2 77 ...

Page 284: ...15 2 4 96 15 6 5 43 16 0 5 46 39 10 4 3 14 12 4 3 72 14 4 4 38 14 8 4 74 15 0 5 12 15 4 5 49 15 7 5 52 Combination 100 Capacity index kW 14 00 TC Total Capacity kW PI Power Input kW Outdoor Indoor Air Temperature CDB Air Temp 14 0 16 0 18 0 19 0 20 0 22 0 24 0 CWB TC PI TC PI TC PI TC PI TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW kW kW 10 9 45 1 83 11 3 2 07 13 1 2 32 14 0 2 45 14 9 2 5...

Page 285: ...13 4 3 75 15 0 3 97 15 3 4 22 39 8 50 2 73 10 1 3 23 11 8 3 74 12 6 3 85 13 4 3 96 14 7 4 20 15 0 4 47 Combination 80 Capacity index kW 11 20 TC Total Capacity kW PI Power Input kW Outdoor Indoor Air Temperature CDB Air Temp 14 0 16 0 18 0 19 0 20 0 22 0 24 0 CWB TC PI TC PI TC PI TC PI TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW kW kW 10 7 56 1 43 9 02 1 76 10 5 1 85 11 2 1 91 11 9 1 96...

Page 286: ...10 4 2 79 11 7 3 01 13 0 3 26 39 6 61 2 11 7 89 2 50 9 16 2 71 9 80 2 82 10 4 2 93 11 7 3 17 13 0 3 44 Combination 60 Capacity index kW 8 40 TC Total Capacity kW PI Power Input kW Outdoor Indoor Air Temperature CDB Air Temp 14 0 16 0 18 0 19 0 20 0 22 0 24 0 CWB TC PI TC PI TC PI TC PI TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW kW kW 10 5 67 1 03 6 76 1 37 7 85 1 46 8 40 1 52 8 95 1 57 ...

Page 287: ...00 6 54 1 11 7 00 1 17 7 46 1 22 8 37 1 35 9 28 1 47 21 4 72 0 90 5 63 1 00 6 54 1 12 7 00 1 17 7 46 1 23 8 37 1 36 9 28 1 48 23 4 72 0 91 5 63 1 02 6 54 1 13 7 00 1 19 7 46 1 25 8 37 1 38 9 28 1 51 25 4 72 0 92 5 63 1 03 6 54 1 15 7 00 1 21 7 46 1 28 8 37 1 43 9 28 1 59 27 4 72 0 93 5 63 1 06 6 54 1 19 7 00 1 27 7 46 1 34 8 37 1 51 9 28 1 69 29 4 72 0 97 5 63 1 10 6 54 1 25 7 00 1 33 7 46 1 41 8 ...

Page 288: ... 6 5 32 16 9 5 63 17 3 6 10 17 8 6 13 39 13 6 3 90 15 6 4 48 16 1 5 14 16 4 5 50 16 6 5 78 17 1 6 15 17 6 6 18 Combination 120 Capacity index kW 18 60 TC Total Capacity kW PI Power Input kW Outdoor Indoor Air Temperature CDB Air Temp 14 0 16 0 18 0 19 0 20 0 22 0 24 0 CWB TC PI TC PI TC PI TC PI TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW kW kW 10 12 6 2 99 15 0 3 23 17 4 3 48 18 6 3 61 ...

Page 289: ...16 2 5 55 16 7 6 02 17 1 6 05 39 11 5 3 69 13 7 4 27 15 6 4 93 15 8 5 29 16 0 5 67 16 4 6 04 16 8 6 07 Combination 100 Capacity index kW 15 50 TC Total Capacity kW PI Power Input kW Outdoor Indoor Air Temperature CDB Air Temp 14 0 16 0 18 0 19 0 20 0 22 0 24 0 CWB TC PI TC PI TC PI TC PI TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW kW kW 10 10 5 2 66 12 5 2 90 14 5 3 15 15 5 3 28 16 5 3 4...

Page 290: ...14 9 4 74 16 0 5 21 16 3 5 24 39 9 41 3 54 11 2 4 13 13 0 4 54 14 0 4 65 14 9 5 03 15 7 5 40 16 0 5 43 Combination 80 Capacity index kW 12 40 TC Total Capacity kW PI Power Input kW Outdoor Indoor Air Temperature CDB Air Temp 14 0 16 0 18 0 19 0 20 0 22 0 24 0 CWB TC PI TC PI TC PI TC PI TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW kW kW 10 8 37 2 06 10 0 2 15 11 6 2 24 12 4 2 30 13 2 2 43...

Page 291: ... 11 6 3 50 13 0 3 97 14 4 4 00 39 7 32 2 81 8 73 3 00 10 1 3 21 10 9 3 32 11 6 3 70 13 0 4 07 14 4 4 10 Combination 60 Capacity index kW 9 30 TC Total Capacity kW PI Power Input kW Outdoor Indoor Air Temperature CDB Air Temp 14 0 16 0 18 0 19 0 20 0 22 0 24 0 CWB TC PI TC PI TC PI TC PI TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW kW kW 10 6 28 1 46 7 49 1 55 8 70 1 64 9 30 1 70 9 90 1 83...

Page 292: ...33 7 25 1 44 7 75 1 50 8 25 1 55 9 26 1 68 10 3 1 80 21 5 23 1 23 6 24 1 33 7 25 1 45 7 75 1 50 8 25 1 56 9 26 1 69 10 3 1 81 23 5 23 1 24 6 24 1 35 7 25 1 46 7 75 1 52 8 25 1 58 9 26 1 71 10 3 1 84 25 5 23 1 25 6 24 1 36 7 25 1 48 7 75 1 54 8 25 1 61 9 26 1 76 10 3 1 92 27 5 23 1 26 6 24 1 39 7 25 1 52 7 75 1 60 8 25 1 67 9 26 1 84 10 3 2 02 29 5 23 1 30 6 24 1 43 7 25 1 58 7 75 1 66 8 25 1 74 9 ...

Page 293: ...7 1 5 1 4 1 8 1 6 2 1 1 7 2 2 1 8 2 3 1 8 2 3 1 7 2 4 1 7 39 1 5 1 4 1 8 1 6 2 1 1 7 2 2 1 8 2 2 1 8 2 3 1 7 2 3 1 7 Indoor Unit S 28KA1E5 S 28KA1E5S Nominal Capacity kW 2 8 TC Total Capacity kW SHC Sensible Heat Capacity kW Outdoor Indoor Air Temperature Air Temp 14 0WB 16 0WB 18 0WB 19 0WB 20 0WB 22 0WB 24 0WB CDB 20 0DB 23 0DB 26 0DB 27 0DB 28 0DB 30 0DB 32 0DB TC SHC TC SHC TC SHC TC SHC TC SH...

Page 294: ...2 6 3 4 2 8 3 6 2 8 3 7 2 8 3 8 2 7 3 9 2 7 39 2 4 2 3 2 9 2 6 3 4 2 8 3 6 2 8 3 7 2 8 3 8 2 7 3 8 2 6 Indoor Unit S 45KA1E5 S 45KA1E5S Nominal Capacity kW 4 5 TC Total Capacity kW SHC Sensible Heat Capacity kW Outdoor Indoor Air Temperature Air Temp 14 0WB 16 0WB 18 0WB 19 0WB 20 0WB 22 0WB 24 0WB CDB 20 0DB 23 0DB 26 0DB 27 0DB 28 0DB 30 0DB 32 0DB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SH...

Page 295: ...3 6 5 2 4 0 5 6 4 3 5 8 4 4 5 9 4 1 6 1 4 0 39 3 8 3 2 4 5 3 6 5 2 4 0 5 6 4 3 5 7 4 3 5 8 4 1 6 0 3 9 Indoor Unit S 63KA1E5 Nominal Capacity kW 6 3 TC Total Capacity kW SHC Sensible Heat Capacity kW Outdoor Indoor Air Temperature Air Temp 14 0WB 16 0WB 18 0WB 19 0WB 20 0WB 22 0WB 24 0WB CDB 20 0DB 23 0DB 26 0DB 27 0DB 28 0DB 30 0DB 32 0DB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC 10 4 0 3 ...

Page 296: ... 4 9 0 5 3 18 4 8 4 1 5 7 4 6 6 6 5 0 7 1 5 2 7 6 5 3 8 5 5 4 8 8 5 2 20 4 8 4 1 5 7 4 6 6 6 5 0 7 1 5 2 7 6 5 3 8 5 5 4 8 7 5 1 21 4 8 4 1 5 7 4 6 6 6 5 0 7 1 5 2 7 6 5 3 8 5 5 4 8 7 5 1 23 4 8 4 1 5 7 4 6 6 6 5 0 7 1 5 2 7 6 5 3 8 4 5 4 8 5 5 0 25 4 8 4 1 5 7 4 6 6 6 5 0 7 1 5 2 7 6 5 3 8 3 5 3 8 4 5 0 27 4 8 4 1 5 7 4 6 6 6 5 0 7 1 5 2 7 6 5 3 8 1 5 2 8 3 5 0 29 4 8 4 1 5 7 4 6 6 6 5 0 7 1 5 2 ...

Page 297: ...5 1 4 1 8 1 6 2 1 1 7 2 2 1 7 2 3 1 8 2 3 1 7 2 4 1 7 39 1 5 1 4 1 8 1 6 2 1 1 7 2 2 1 7 2 2 1 8 2 3 1 7 2 3 1 7 Indoor Unit S 28YA1E5 Nominal Capacity kW 2 8 TC Total Capacity kW SHC Sensible Heat Capacity kW Outdoor Indoor Air Temperature Air Temp 14 0WB 16 0WB 18 0WB 19 0WB 20 0WB 22 0WB 24 0WB CDB 20 0DB 23 0DB 26 0DB 27 0DB 28 0DB 30 0DB 32 0DB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC...

Page 298: ...2 5 3 4 2 7 3 6 2 7 3 7 2 7 3 8 2 6 3 9 2 6 39 2 4 2 2 2 9 2 5 3 4 2 7 3 6 2 7 3 7 2 7 3 8 2 6 3 8 2 6 Indoor Unit S 45YA1E5 Nominal Capacity kW 4 5 TC Total Capacity kW SHC Sensible Heat Capacity kW Outdoor Indoor Air Temperature Air Temp 14 0WB 16 0WB 18 0WB 19 0WB 20 0WB 22 0WB 24 0WB CDB 20 0DB 23 0DB 26 0DB 27 0DB 28 0DB 30 0DB 32 0DB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC 10 3 0 2 ...

Page 299: ... 1 7 1 4 1 18 3 8 3 1 4 5 3 5 5 2 3 9 5 6 4 0 6 0 4 1 6 7 4 1 7 0 4 1 20 3 8 3 1 4 5 3 5 5 2 3 9 5 6 4 0 6 0 4 1 6 7 4 1 6 9 4 0 21 3 8 3 1 4 5 3 5 5 2 3 9 5 6 4 0 6 0 4 1 6 7 4 1 6 8 4 0 23 3 8 3 1 4 5 3 5 5 2 3 9 5 6 4 0 6 0 4 1 6 7 4 1 6 7 4 0 25 3 8 3 1 4 5 3 5 5 2 3 9 5 6 4 0 6 0 4 1 6 5 4 1 6 6 3 9 27 3 8 3 1 4 5 3 5 5 2 3 9 5 6 4 0 6 0 4 1 6 4 4 0 6 6 3 9 29 3 8 3 1 4 5 3 5 5 2 3 9 5 6 4 0 ...

Page 300: ...0 3 4 5 1 4 1 5 9 4 5 6 3 4 6 6 8 4 8 6 8 4 5 7 0 4 4 39 4 0 3 4 5 1 4 1 5 9 4 5 6 3 4 6 6 8 4 8 6 7 4 5 6 9 4 3 Indoor Unit S 71UA1E5 Nominal Capacity kW 7 1 TC Total Capacity kW SHC Sensible Heat Capacity kW Outdoor Indoor Air Temperature Air Temp 14 0WB 16 0WB 18 0WB 19 0WB 20 0WB 22 0WB 24 0WB CDB 20 0DB 23 0DB 26 0DB 27 0DB 28 0DB 30 0DB 32 0DB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC...

Page 301: ... 4 6 8 18 6 1 5 2 7 2 5 8 8 4 6 4 9 0 6 5 9 6 6 7 10 8 6 9 11 2 6 7 20 6 1 5 2 7 2 5 8 8 4 6 4 9 0 6 5 9 6 6 7 10 8 6 9 11 1 6 6 21 6 1 5 2 7 2 5 8 8 4 6 4 9 0 6 5 9 6 6 7 10 8 6 9 11 0 6 6 23 6 1 5 2 7 2 5 8 8 4 6 4 9 0 6 5 9 6 6 7 10 6 6 8 10 8 6 4 25 6 1 5 2 7 2 5 8 8 4 6 4 9 0 6 5 9 6 6 7 10 5 6 7 10 7 6 4 27 6 1 5 2 7 2 5 8 8 4 6 4 9 0 6 5 9 6 6 7 10 3 6 6 10 5 6 3 29 6 1 5 2 7 2 5 8 8 4 6 4 ...

Page 302: ...5 1 4 1 8 1 6 2 1 1 7 2 2 1 7 2 3 1 8 2 3 1 7 2 4 1 7 39 1 5 1 4 1 8 1 6 2 1 1 7 2 2 1 7 2 2 1 8 2 3 1 7 2 3 1 7 Indoor Unit S 28NA1E5 Nominal Capacity kW 2 8 TC Total Capacity kW SHC Sensible Heat Capacity kW Outdoor Indoor Air Temperature Air Temp 14 0WB 16 0WB 18 0WB 19 0WB 20 0WB 22 0WB 24 0WB CDB 20 0DB 23 0DB 26 0DB 27 0DB 28 0DB 30 0DB 32 0DB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC...

Page 303: ...2 3 3 0 2 4 3 2 2 5 3 3 2 5 3 4 2 5 3 5 2 3 39 2 2 2 0 2 6 2 3 3 0 2 4 3 2 2 5 3 3 2 5 3 3 2 4 3 5 2 3 Indoor Unit S 36NA1E5 Nominal Capacity kW 3 6 TC Total Capacity kW SHC Sensible Heat Capacity kW Outdoor Indoor Air Temperature Air Temp 14 0WB 16 0WB 18 0WB 19 0WB 20 0WB 22 0WB 24 0WB CDB 20 0DB 23 0DB 26 0DB 27 0DB 28 0DB 30 0DB 32 0DB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC 10 2 4 2 ...

Page 304: ...3 0 4 2 3 3 4 5 3 4 4 7 3 5 4 8 3 0 4 9 3 1 39 3 0 2 7 3 6 3 0 4 2 3 3 4 5 3 4 4 6 3 4 4 7 3 0 4 8 3 1 Indoor Unit S 56NA1E5 Nominal Capacity kW 5 6 TC Total Capacity kW SHC Sensible Heat Capacity kW Outdoor Indoor Air Temperature Air Temp 14 0WB 16 0WB 18 0WB 19 0WB 20 0WB 22 0WB 24 0WB CDB 20 0DB 23 0DB 26 0DB 27 0DB 28 0DB 30 0DB 32 0DB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC 10 3 8 3 ...

Page 305: ...0 2 7 3 6 3 0 4 2 3 3 4 5 3 4 4 7 3 5 4 8 3 0 4 9 3 1 39 3 0 2 7 3 6 3 0 4 2 3 3 4 5 3 4 4 6 3 4 4 7 3 0 4 8 3 1 Indoor Unit S 56MA1E5 Nominal Capacity kW 5 6 TC Total Capacity kW SHC Sensible Heat Capacity kW Outdoor Indoor Air Temperature Air Temp 14 0WB 16 0WB 18 0WB 19 0WB 20 0WB 22 0WB 24 0WB CDB 20 0DB 23 0DB 26 0DB 27 0DB 28 0DB 30 0DB 32 0DB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC...

Page 306: ...4 1 5 9 4 5 6 3 4 6 6 8 4 8 6 8 4 5 7 0 4 4 39 4 0 3 4 5 1 4 1 5 9 4 5 6 3 4 6 6 8 4 8 6 7 4 5 6 9 4 3 Indoor Unit S 71MA1E5 Nominal Capacity kW 7 1 TC Total Capacity kW SHC Sensible Heat Capacity kW Outdoor Indoor Air Temperature Air Temp 14 0WB 16 0WB 18 0WB 19 0WB 20 0WB 22 0WB 24 0WB CDB 20 0DB 23 0DB 26 0DB 27 0DB 28 0DB 30 0DB 32 0DB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC 10 4 8 4 ...

Page 307: ... 4 6 8 18 6 1 5 2 7 2 5 8 8 4 6 4 9 0 6 5 9 6 6 7 10 8 6 9 11 2 6 7 20 6 1 5 2 7 2 5 8 8 4 6 4 9 0 6 5 9 6 6 7 10 8 6 9 11 1 6 6 21 6 1 5 2 7 2 5 8 8 4 6 4 9 0 6 5 9 6 6 7 10 8 6 9 11 0 6 6 23 6 1 5 2 7 2 5 8 8 4 6 4 9 0 6 5 9 6 6 7 10 6 6 8 10 8 6 4 25 6 1 5 2 7 2 5 8 8 4 6 4 9 0 6 5 9 6 6 7 10 5 6 7 10 7 6 4 27 6 1 5 2 7 2 5 8 8 4 6 4 9 0 6 5 9 6 6 7 10 3 6 6 10 5 6 3 29 6 1 5 2 7 2 5 8 8 4 6 4 ...

Page 308: ... 18 3 3 78 17 3 3 59 16 3 3 40 15 7 3 31 15 2 3 22 14 2 3 04 13 7 18 3 3 65 17 3 3 47 16 3 3 29 15 7 3 20 15 2 3 12 14 2 2 95 Combination 120 Capacity index kW 15 00 TC Total Capacity kW PI Power Input kW Outdoor Indoor Air Temperature CDB Air Temp 16 0 18 0 20 0 21 0 22 0 24 0 CWB TC PI TC PI TC PI TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW 15 11 7 3 80 11 6 3 89 11 6 3 98 11 6 4 02 11...

Page 309: ... 8 2 78 13 3 2 69 12 9 2 60 12 0 2 42 13 7 15 5 3 05 14 6 2 87 13 8 2 69 13 3 2 60 12 9 2 52 12 0 2 35 Combination 100 Capacity index kW 12 50 TC Total Capacity kW PI Power Input kW Outdoor Indoor Air Temperature CDB Air Temp 16 0 18 0 20 0 21 0 22 0 24 0 CWB TC PI TC PI TC PI TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW 15 11 6 4 08 11 6 4 17 11 6 4 26 11 5 4 30 11 5 4 35 10 9 4 06 13 12...

Page 310: ... 3 2 21 10 9 2 18 10 5 2 14 9 80 2 07 13 7 12 7 2 39 12 0 2 32 11 3 2 14 10 9 2 10 10 5 2 07 9 80 2 00 Combination 80 Capacity index kW 10 00 TC Total Capacity kW PI Power Input kW Outdoor Indoor Air Temperature CDB Air Temp 16 0 18 0 20 0 21 0 22 0 24 0 CWB TC PI TC PI TC PI TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW 15 11 3 3 94 10 6 3 79 10 0 3 64 9 68 3 56 9 36 3 49 8 71 3 35 13 11 ...

Page 311: ...75 1 69 8 47 1 66 8 19 1 62 7 63 1 55 13 7 9 87 1 78 9 31 1 71 8 75 1 64 8 47 1 60 8 19 1 57 7 63 1 50 Combination 60 Capacity index kW 7 50 TC Total Capacity kW PI Power Input kW Outdoor Indoor Air Temperature CDB Air Temp 16 0 18 0 20 0 21 0 22 0 24 0 CWB TC PI TC PI TC PI TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW 15 8 46 2 88 7 98 2 73 7 50 2 58 7 26 2 50 7 02 2 43 6 54 2 29 13 8 46...

Page 312: ...7 05 1 94 6 65 1 82 6 25 1 71 6 05 1 65 5 85 1 59 5 45 1 48 5 6 7 05 1 84 6 65 1 74 6 25 1 63 6 05 1 57 5 85 1 52 5 45 1 41 3 7 7 05 1 78 6 65 1 67 6 25 1 56 6 05 1 51 5 85 1 46 5 45 1 36 0 7 7 05 1 66 6 65 1 57 6 25 1 47 6 05 1 42 5 85 1 38 5 45 1 28 2 2 7 05 1 58 6 65 1 48 6 25 1 39 6 05 1 35 5 85 1 30 5 45 1 22 4 1 7 05 1 52 6 65 1 43 6 25 1 35 6 05 1 30 5 85 1 26 5 45 1 18 6 7 05 1 48 6 65 1 3...

Page 313: ... 4 49 20 8 4 30 20 1 4 21 19 5 4 12 18 1 3 94 13 7 22 2 4 58 22 1 4 40 20 8 4 22 20 1 4 13 19 5 4 05 18 1 3 88 Combination 120 Capacity index kW 19 20 TC Total Capacity kW PI Power Input kW Outdoor Indoor Air Temperature CDB Air Temp 16 0 18 0 20 0 21 0 22 0 24 0 CWB TC PI TC PI TC PI TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW 15 12 7 5 37 12 6 5 46 12 6 5 55 12 6 5 59 12 6 5 64 12 5 5 ...

Page 314: ... 6 3 80 17 0 3 71 16 5 3 62 15 3 3 44 13 7 19 9 4 08 18 7 3 90 17 6 3 72 17 0 3 63 16 5 3 55 15 3 3 38 Combination 100 Capacity index kW 16 00 TC Total Capacity kW PI Power Input kW Outdoor Indoor Air Temperature CDB Air Temp 16 0 18 0 20 0 21 0 22 0 24 0 CWB TC PI TC PI TC PI TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW 15 12 6 4 92 12 5 5 01 12 5 5 10 12 5 5 14 12 5 5 19 12 5 4 90 13 13...

Page 315: ... 4 2 88 13 9 2 85 13 5 2 81 12 6 2 74 13 7 16 3 2 94 15 3 2 87 14 4 2 80 13 9 2 76 13 5 2 73 12 6 2 66 Combination 80 Capacity index kW 12 80 TC Total Capacity kW PI Power Input kW Outdoor Indoor Air Temperature CDB Air Temp 16 0 18 0 20 0 21 0 22 0 24 0 CWB TC PI TC PI TC PI TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW 15 12 5 4 47 12 4 4 32 12 4 4 17 12 4 4 09 12 0 4 02 11 2 3 88 13 13 ...

Page 316: ...1 2 2 04 10 8 2 01 10 5 1 97 9 76 1 90 13 7 12 6 2 10 11 9 2 03 11 2 1 96 10 8 1 92 10 5 1 89 9 76 1 82 Combination 60 Capacity index kW 9 60 TC Total Capacity kW PI Power Input kW Outdoor Indoor Air Temperature CDB Air Temp 16 0 18 0 20 0 21 0 22 0 24 0 CWB TC PI TC PI TC PI TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW 15 10 8 3 55 10 2 3 40 9 60 3 25 9 29 3 17 8 98 3 10 8 37 2 96 13 10 ...

Page 317: ...9 03 2 34 8 51 2 22 8 00 2 11 7 74 2 05 7 49 1 99 6 97 1 88 5 6 9 03 2 24 8 51 2 14 8 00 2 03 7 74 1 97 7 49 1 92 6 97 1 81 3 7 9 03 2 18 8 51 2 07 8 00 1 96 7 74 1 91 7 49 1 86 6 97 1 76 0 7 9 03 2 06 8 51 1 97 8 00 1 87 7 74 1 82 7 49 1 78 6 97 1 68 2 2 9 03 1 98 8 51 1 88 8 00 1 79 7 74 1 75 7 49 1 70 6 97 1 62 4 1 9 03 1 92 8 51 1 83 8 00 1 75 7 74 1 70 7 49 1 66 6 97 1 58 6 9 03 1 88 8 51 1 7...

Page 318: ... 4 50 21 8 4 31 21 8 4 22 21 8 4 13 20 4 3 95 13 7 22 6 4 59 22 5 4 41 22 5 4 23 22 4 4 14 21 9 4 06 20 4 3 89 Combination 120 Capacity index kW 21 60 TC Total Capacity kW PI Power Input kW Outdoor Indoor Air Temperature CDB Air Temp 16 0 18 0 20 0 21 0 22 0 24 0 CWB TC PI TC PI TC PI TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW 15 12 9 5 92 12 9 6 01 12 8 6 10 12 8 6 14 12 8 6 19 12 8 5 ...

Page 319: ... 8 4 60 19 2 4 51 18 5 4 42 17 3 4 24 13 7 22 3 4 88 21 1 4 70 19 8 4 52 19 2 4 43 18 5 4 35 17 3 4 18 Combination 100 Capacity index kW 18 00 TC Total Capacity kW PI Power Input kW Outdoor Indoor Air Temperature CDB Air Temp 16 0 18 0 20 0 21 0 22 0 24 0 CWB TC PI TC PI TC PI TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW 15 12 8 5 63 12 8 5 72 12 7 5 81 12 7 5 85 12 7 5 90 12 7 5 61 13 13...

Page 320: ... 2 3 51 15 7 3 48 15 2 3 44 14 1 3 37 13 7 18 3 3 57 17 2 3 50 16 2 3 43 15 7 3 39 15 2 3 36 14 1 3 29 Combination 80 Capacity index kW 14 40 TC Total Capacity kW PI Power Input kW Outdoor Indoor Air Temperature CDB Air Temp 16 0 18 0 20 0 21 0 22 0 24 0 CWB TC PI TC PI TC PI TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW 15 12 7 5 07 12 7 4 92 12 6 4 77 12 6 4 69 12 6 4 62 12 6 4 48 13 13 ...

Page 321: ... 6 2 51 12 2 2 48 11 8 2 44 11 0 2 37 13 7 14 2 2 57 13 4 2 50 12 6 2 43 12 2 2 39 11 8 2 36 11 0 2 29 Combination 60 Capacity index kW 10 80 TC Total Capacity kW PI Power Input kW Outdoor Indoor Air Temperature CDB Air Temp 16 0 18 0 20 0 21 0 22 0 24 0 CWB TC PI TC PI TC PI TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW 15 12 2 3 84 11 5 3 69 10 8 3 54 10 5 3 46 10 1 3 39 9 41 3 25 13 12 ...

Page 322: ...10 2 2 67 9 58 2 55 9 00 2 44 8 71 2 38 8 42 2 32 7 84 2 21 5 6 10 2 2 57 9 58 2 47 9 00 2 36 8 71 2 30 8 42 2 25 7 84 2 14 3 7 10 2 2 51 9 58 2 40 9 00 2 29 8 71 2 24 8 42 2 19 7 84 2 09 0 7 10 2 2 39 9 58 2 30 9 00 2 20 8 71 2 15 8 42 2 11 7 84 2 01 2 2 10 2 2 31 9 58 2 21 9 00 2 12 8 71 2 08 8 42 2 03 7 84 1 95 4 1 10 2 2 25 9 58 2 16 9 00 2 08 8 71 2 03 8 42 1 99 7 84 1 91 6 10 2 2 21 9 58 2 1...

Page 323: ...2 5 2 4 2 3 2 2 11 0 9 8 2 8 2 7 2 5 2 4 2 3 2 2 13 0 11 8 2 8 2 7 2 5 2 4 2 3 2 2 15 0 13 7 2 8 2 7 2 5 2 4 2 3 2 2 Indoor Unit S 28KA1E5 S 28KA1E5S Nominal Capacity kW 3 2 Outdoor Indoor Air Temperature CDB Air Temp 16 0 18 0 20 0 21 0 22 0 24 0 CDB CWB kW kW kW kW kW kW 14 7 15 0 2 2 2 2 2 2 2 2 2 2 2 1 12 6 13 0 2 3 2 3 2 3 2 3 2 3 2 3 10 5 11 0 2 4 2 4 2 4 2 4 2 4 2 4 9 5 10 0 2 5 2 4 2 4 2 4...

Page 324: ...7 11 0 9 8 4 7 4 5 4 2 4 1 3 9 3 7 13 0 11 8 4 7 4 5 4 2 4 1 3 9 3 7 15 0 13 7 4 7 4 5 4 2 4 1 3 9 3 7 Indoor Unit S 45KA1E5 S 45KA1E5S Nominal Capacity kW 5 1 Outdoor Indoor Air Temperature CDB Air Temp 16 0 18 0 20 0 21 0 22 0 24 0 CDB CWB kW kW kW kW kW kW 14 7 15 0 3 5 3 5 3 5 3 5 3 5 3 5 12 6 13 0 3 7 3 7 3 7 3 6 3 6 3 6 10 5 11 0 3 8 3 8 3 8 3 8 3 8 3 8 9 5 10 0 3 9 3 9 3 9 3 9 3 9 3 9 8 5 9...

Page 325: ...6 11 0 9 8 7 1 6 8 6 4 6 2 6 0 5 6 13 0 11 8 7 2 6 8 6 4 6 2 6 0 5 6 15 0 13 7 7 2 6 8 6 4 6 2 6 0 5 6 Indoor Unit S 63KA1E5 Nominal Capacity kW 7 1 Outdoor Indoor Air Temperature CDB Air Temp 16 0 18 0 20 0 21 0 22 0 24 0 CDB CWB kW kW kW kW kW kW 14 7 15 0 4 8 4 8 4 8 4 8 4 8 4 8 12 6 13 0 5 1 5 1 5 1 5 1 5 1 5 1 10 5 11 0 5 3 5 3 5 3 5 3 5 3 5 3 9 5 10 0 5 4 5 4 5 4 5 4 5 4 5 4 8 5 9 1 5 6 5 6 ...

Page 326: ...6 0 6 0 6 0 5 9 9 5 10 0 6 1 6 1 6 1 6 1 6 1 6 1 8 5 9 1 6 3 6 3 6 2 6 2 6 2 6 2 7 0 7 6 6 5 6 5 6 4 6 4 6 4 6 4 5 0 5 6 6 8 6 7 6 7 6 7 6 7 6 7 3 0 3 7 7 0 7 0 7 0 7 0 7 0 7 0 0 0 0 7 7 5 7 4 7 4 7 4 7 4 7 0 3 0 2 2 7 9 7 8 7 8 7 7 7 5 7 0 5 0 4 1 8 1 8 1 8 0 7 7 7 5 7 0 7 0 6 0 8 4 8 4 8 0 7 7 7 5 7 0 9 0 7 9 8 7 8 5 8 0 7 7 7 5 7 0 11 0 9 8 8 9 8 5 8 0 7 7 7 5 7 0 13 0 11 8 9 0 8 5 8 0 7 7 7 5 ...

Page 327: ...2 4 2 3 2 2 11 0 9 8 2 8 2 7 2 5 2 4 2 3 2 2 13 0 11 8 2 8 2 7 2 5 2 4 2 3 2 2 15 0 13 7 2 8 2 7 2 5 2 4 2 3 2 2 Indoor Unit S 28YA1E5 Nominal Capacity kW 3 2 Outdoor Indoor Air Temperature CDB Air Temp 16 0 18 0 20 0 21 0 22 0 24 0 CDB CWB kW kW kW kW kW kW 14 7 15 0 2 2 2 2 2 2 2 2 2 2 2 1 12 6 13 0 2 3 2 3 2 3 2 3 2 3 2 3 10 5 11 0 2 4 2 4 2 4 2 4 2 4 2 4 9 5 10 0 2 5 2 4 2 4 2 4 2 4 2 4 8 5 9 ...

Page 328: ...7 11 0 9 8 4 7 4 5 4 2 4 1 3 9 3 7 13 0 11 8 4 7 4 5 4 2 4 1 3 9 3 7 15 0 13 7 4 7 4 5 4 2 4 1 3 9 3 7 Indoor Unit S 45YA1E5 Nominal Capacity kW 5 1 Outdoor Indoor Air Temperature CDB Air Temp 16 0 18 0 20 0 21 0 22 0 24 0 CDB CWB kW kW kW kW kW kW 14 7 15 0 3 5 3 5 3 5 3 5 3 5 3 5 12 6 13 0 3 7 3 7 3 7 3 6 3 6 3 6 10 5 11 0 3 8 3 8 3 8 3 8 3 8 3 8 9 5 10 0 3 9 3 9 3 9 3 9 3 9 3 9 8 5 9 1 4 0 4 0 ...

Page 329: ...4 8 4 8 4 8 4 8 9 5 10 0 4 9 4 9 4 9 4 9 4 9 4 9 8 5 9 1 5 0 5 0 5 0 5 0 5 0 5 0 7 0 7 6 5 2 5 2 5 2 5 2 5 2 5 2 5 0 5 6 5 4 5 4 5 4 5 4 5 4 5 4 3 0 3 7 5 6 5 6 5 6 5 6 5 6 5 6 0 0 0 7 6 0 6 0 5 9 5 9 5 9 5 6 3 0 2 2 6 3 6 3 6 3 6 2 6 0 5 6 5 0 4 1 6 5 6 5 6 4 6 2 6 0 5 6 7 0 6 0 6 7 6 7 6 4 6 2 6 0 5 6 9 0 7 9 6 9 6 8 6 4 6 2 6 0 5 6 11 0 9 8 7 1 6 8 6 4 6 2 6 0 5 6 13 0 11 8 7 2 6 8 6 4 6 2 6 0 ...

Page 330: ...6 9 6 7 6 2 11 0 9 8 7 9 7 6 7 1 6 9 6 7 6 2 13 0 11 8 8 0 7 6 7 1 6 9 6 7 6 2 15 0 13 7 8 0 7 6 7 1 6 9 6 7 6 2 Indoor Unit S 71UA1E5 Nominal Capacity kW 8 0 Outdoor Indoor Air Temperature CDB Air Temp 16 0 18 0 20 0 21 0 22 0 24 0 CDB CWB kW kW kW kW kW kW 14 7 15 0 5 4 5 4 5 4 5 4 5 4 5 4 12 6 13 0 5 7 5 7 5 7 5 7 5 7 5 7 10 5 11 0 6 0 6 0 6 0 6 0 6 0 5 9 9 5 10 0 6 1 6 1 6 1 6 1 6 1 6 1 8 5 9 ...

Page 331: ...7 4 7 4 9 5 10 0 7 7 7 7 7 7 7 6 7 6 7 6 8 5 9 1 7 8 7 8 7 8 7 8 7 8 7 8 7 0 7 6 8 1 8 1 8 1 8 1 8 0 8 0 5 0 5 6 8 4 8 4 8 4 8 4 8 4 8 4 3 0 3 7 8 8 8 8 8 7 8 7 8 7 8 7 0 0 0 7 9 3 9 3 9 3 9 3 9 3 8 7 3 0 2 2 9 8 9 8 9 8 9 7 9 4 8 7 5 0 4 1 10 2 10 1 10 0 9 7 9 4 8 7 7 0 6 0 10 5 10 5 10 0 9 7 9 4 8 7 9 0 7 9 10 8 10 6 10 0 9 7 9 4 8 7 11 0 9 8 11 2 10 6 10 0 9 7 9 4 8 7 13 0 11 8 11 3 10 6 10 0 9...

Page 332: ...2 4 2 3 2 2 11 0 9 8 2 8 2 7 2 5 2 4 2 3 2 2 13 0 11 8 2 8 2 7 2 5 2 4 2 3 2 2 15 0 13 7 2 8 2 7 2 5 2 4 2 3 2 2 Indoor Unit S 28NA1E5 Nominal Capacity kW 3 2 Outdoor Indoor Air Temperature CDB Air Temp 16 0 18 0 20 0 21 0 22 0 24 0 CDB CWB kW kW kW kW kW kW 14 7 15 0 2 2 2 2 2 2 2 2 2 2 2 1 12 6 13 0 2 3 2 3 2 3 2 3 2 3 2 3 10 5 11 0 2 4 2 4 2 4 2 4 2 4 2 4 9 5 10 0 2 5 2 4 2 4 2 4 2 4 2 4 8 5 9 ...

Page 333: ...2 11 0 9 8 4 1 3 9 3 6 3 5 3 4 3 2 13 0 11 8 4 1 3 9 3 6 3 5 3 4 3 2 15 0 13 7 4 1 3 9 3 6 3 5 3 4 3 2 Indoor Unit S 36NA1E5 Nominal Capacity kW 4 2 Outdoor Indoor Air Temperature CDB Air Temp 16 0 18 0 20 0 21 0 22 0 24 0 CDB CWB kW kW kW kW kW kW 14 7 15 0 2 9 2 9 2 9 2 9 2 9 2 9 12 6 13 0 3 1 3 0 3 0 3 0 3 0 3 0 10 5 11 0 3 2 3 2 3 2 3 2 3 2 3 2 9 5 10 0 3 3 3 3 3 3 3 3 3 2 3 2 8 5 9 1 3 3 3 3 ...

Page 334: ...5 11 0 9 8 5 7 5 4 5 1 4 9 4 8 4 5 13 0 11 8 5 7 5 4 5 1 4 9 4 8 4 5 15 0 13 7 5 7 5 4 5 1 4 9 4 8 4 5 Indoor Unit S 56NA1E5 Nominal Capacity kW 6 4 Outdoor Indoor Air Temperature CDB Air Temp 16 0 18 0 20 0 21 0 22 0 24 0 CDB CWB kW kW kW kW kW kW 14 7 15 0 4 4 4 4 4 4 4 3 4 3 4 3 12 6 13 0 4 6 4 6 4 6 4 6 4 6 4 6 10 5 11 0 4 8 4 8 4 8 4 8 4 8 4 8 9 5 10 0 4 9 4 9 4 9 4 9 4 9 4 9 8 5 9 1 5 0 5 0 ...

Page 335: ...4 9 4 8 4 5 11 0 9 8 5 7 5 4 5 1 4 9 4 8 4 5 13 0 11 8 5 7 5 4 5 1 4 9 4 8 4 5 15 0 13 7 5 7 5 4 5 1 4 9 4 8 4 5 Indoor Unit S 56MA1E5 Nominal Capacity kW 6 4 Outdoor Indoor Air Temperature CDB Air Temp 16 0 18 0 20 0 21 0 22 0 24 0 CDB CWB kW kW kW kW kW kW 14 7 15 0 4 4 4 4 4 4 4 3 4 3 4 3 12 6 13 0 4 6 4 6 4 6 4 6 4 6 4 6 10 5 11 0 4 8 4 8 4 8 4 8 4 8 4 8 9 5 10 0 4 9 4 9 4 9 4 9 4 9 4 9 8 5 9 ...

Page 336: ...2 11 0 9 8 7 9 7 6 7 1 6 9 6 7 6 2 13 0 11 8 8 0 7 6 7 1 6 9 6 7 6 2 15 0 13 7 8 0 7 6 7 1 6 9 6 7 6 2 Indoor Unit S 71MA1E5 Nominal Capacity kW 8 0 Outdoor Indoor Air Temperature CDB Air Temp 16 0 18 0 20 0 21 0 22 0 24 0 CDB CWB kW kW kW kW kW kW 14 7 15 0 5 4 5 4 5 4 5 4 5 4 5 4 12 6 13 0 5 7 5 7 5 7 5 7 5 7 5 7 10 5 11 0 6 0 6 0 6 0 6 0 6 0 5 9 9 5 10 0 6 1 6 1 6 1 6 1 6 1 6 1 8 5 9 1 6 3 6 3 ...

Page 337: ...7 4 7 4 9 5 10 0 7 7 7 7 7 7 7 6 7 6 7 6 8 5 9 1 7 8 7 8 7 8 7 8 7 8 7 8 7 0 7 6 8 1 8 1 8 1 8 1 8 0 8 0 5 0 5 6 8 4 8 4 8 4 8 4 8 4 8 4 3 0 3 7 8 8 8 8 8 7 8 7 8 7 8 7 0 0 0 7 9 3 9 3 9 3 9 3 9 3 8 7 3 0 2 2 9 8 9 8 9 8 9 7 9 4 8 7 5 0 4 1 10 2 10 1 10 0 9 7 9 4 8 7 7 0 6 0 10 5 10 5 10 0 9 7 9 4 8 7 9 0 7 9 10 8 10 6 10 0 9 7 9 4 8 7 11 0 9 8 11 2 10 6 10 0 9 7 9 4 8 7 13 0 11 8 11 3 10 6 10 0 9...

Page 338: ...4 15 16 17 18 19 20 21 22 total indoor rated cooling capacity kW cooling capacity kW cooling power input 6HP 0 00 1 00 2 00 3 00 4 00 5 00 6 00 0 5 10 15 20 25 total indoor rated cooling capacity kW cooling power input kw cooling capacity 5HP 0 2 4 6 8 10 12 14 16 18 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 total indoor rated cooling capacity kW cooling capa city kW cooling power input...

Page 339: ... 16 18 20 0 5 10 15 20 25 total indoo r rated heating capacity kW heating capacity kW heating power input 5HP 0 00 1 00 2 00 3 00 4 00 5 00 0 5 10 15 20 25 total indoo r rated heating capacity kW heating power input kW heating capacity 4HP 0 2 4 6 8 10 12 14 16 0 2 4 6 8 10 12 14 16 18 total indoo r rated heating capacity kW heating capacity kW heating power input 4HP 0 00 1 00 2 00 3 00 4 00 0 2 ...

Page 340: ...nit U 5LA1E5 maximum combination capacity 18 2kW Indoor units S 22KA1E5 2 2kW x 7 S 28KA1E5 2 8kW Total capacity of indoor units selected 18 2kW o 5HP an example of maximum kW Outdoor unit U 5LA1E5 maximum combination capacity 7 0kW Indoor units S 36KA1E5 3 6kW x 2 Total capacity of indoor units selected 7 2 kW o 6HP an example of maximum kW Outdoor unit U 6LA1E5 maximum combination capacity 20 2k...

Page 341: ...3 min 15 3 16 0 17 4 Me m3 min 13 2 13 7 14 7 Cooling Lo m3 min 11 1 11 4 12 0 Hi m3 min 16 7 17 1 18 3 Me m3 min 15 0 15 1 16 0 Heating Lo m3 min 13 4 13 1 13 7 20 7 2 60 x 60 Cassette Type Indoor Unit S 22YA1E5 S 28YA1E5 S 36YA1E5 S 45YA1E5 Hi m3 min 8 3 8 6 9 0 9 3 Me m3 min 7 3 7 4 7 7 7 9 Cooling Lo m3 min 6 2 6 2 6 4 6 5 Hi m3 min 9 3 9 6 9 9 10 3 Me m3 min 8 1 8 4 8 7 9 0 Heating Lo m3 min ...

Page 342: ...m Height m 1m sec over 0 5 1m sec 0 0 5m sec 2 Cooling Me Air velocity distribution 0 0 5 1 1 5 2 2 5 3 3 5 4 0 2 4 6 8 10 12 14 Reaching distance m Height m 1m sec over 0 5 1m sec 0 0 5m sec 3 Cooling Lo Air velocity distribution 0 0 5 1 1 5 2 2 5 3 3 5 4 0 2 4 6 8 10 12 14 Reaching distance m Height m 1m sec over 0 5 1m sec 0 0 5m sec ...

Page 343: ...ght m 1m sec over 0 5 1m sec 0 0 5m sec 2 Heating Me Air velocity distribution 0 0 5 1 1 5 2 2 5 3 3 5 4 0 2 4 6 8 10 12 14 Reaching distance m Height m 1m sec over 0 5 1m sec 0 0 5m sec 3 Heating Lo Air velocity distribution 0 0 5 1 1 5 2 2 5 3 3 5 4 0 2 4 6 8 10 12 14 Reaching distance m Height m 1m sec over 0 5 1m sec 0 0 5m sec ...

Page 344: ...m Height m 1m sec over 0 5 1m sec 0 0 5m sec 2 Cooling Me Air velocity distribution 0 0 5 1 1 5 2 2 5 3 3 5 4 0 2 4 6 8 10 12 14 Reaching distance m Height m 1m sec over 0 5 1m sec 0 0 5m sec 3 Cooling Lo Air velocity distribution 0 0 5 1 1 5 2 2 5 3 3 5 4 0 2 4 6 8 10 12 14 Reaching distance m Height m 1m sec over 0 5 1m sec 0 0 5m sec ...

Page 345: ...ght m 1m sec over 0 5 1m sec 0 0 5m sec 2 Heating Me Air velocity distribution 0 0 5 1 1 5 2 2 5 3 3 5 4 0 2 4 6 8 10 12 14 Reaching distance m Height m 1m sec over 0 5 1m sec 0 0 5m sec 3 Heating Lo Air velocity distribution 0 0 5 1 1 5 2 2 5 3 3 5 4 0 2 4 6 8 10 12 14 Reaching distance m Height m 1m sec over 0 5 1m sec 0 0 5m sec ...

Page 346: ...m Height m 1m sec over 0 5 1m sec 0 0 5m sec 2 Cooling Me Air velocity distribution 0 0 5 1 1 5 2 2 5 3 3 5 4 0 2 4 6 8 10 12 14 Reaching distance m Height m 1m sec over 0 5 1m sec 0 0 5m sec 3 Cooling Lo Air velocity distribution 0 0 5 1 1 5 2 2 5 3 3 5 4 0 2 4 6 8 10 12 14 Reaching distance m Height m 1m sec over 0 5 1m sec 0 0 5m sec ...

Page 347: ...ght m 1m sec over 0 5 1m sec 0 0 5m sec 2 Heating Me Air velocity distribution 0 0 5 1 1 5 2 2 5 3 3 5 4 0 2 4 6 8 10 12 14 Reaching distance m Height m 1m sec over 0 5 1m sec 0 0 5m sec 3 Heating Lo Air velocity distribution 0 0 5 1 1 5 2 2 5 3 3 5 4 0 2 4 6 8 10 12 14 Reaching distance m Height m 1m sec over 0 5 1m sec 0 0 5m sec ...

Page 348: ...m Height m 1m sec over 0 5 1m sec 0 0 5m sec 2 Cooling Me Air velocity distribution 0 0 5 1 1 5 2 2 5 3 3 5 4 0 2 4 6 8 10 12 14 Reaching distance m Height m 1m sec over 0 5 1m sec 0 0 5m sec 3 Cooling Lo Air velocity distribution 0 0 5 1 1 5 2 2 5 3 3 5 4 0 2 4 6 8 10 12 14 Reaching distance m Height m 1m sec over 0 5 1m sec 0 0 5m sec ...

Page 349: ...ght m 1m sec over 0 5 1m sec 0 0 5m sec 2 Heating Me Air velocity distribution 0 0 5 1 1 5 2 2 5 3 3 5 4 0 2 4 6 8 10 12 14 Reaching distance m Height m 1m sec over 0 5 1m sec 0 0 5m sec 3 Heating Lo Air velocity distribution 0 0 5 1 1 5 2 2 5 3 3 5 4 0 2 4 6 8 10 12 14 Reaching distance m Height m 1m sec over 0 5 1m sec 0 0 5m sec ...

Page 350: ...m Height m 1m sec over 0 5 1m sec 0 0 5m sec 2 Cooling Me Air velocity distribution 0 0 5 1 1 5 2 2 5 3 3 5 4 0 2 4 6 8 10 12 14 Reaching distance m Height m 1m sec over 0 5 1m sec 0 0 5m sec 3 Cooling Lo Air velocity distribution 0 0 5 1 1 5 2 2 5 3 3 5 4 0 2 4 6 8 10 12 14 Reaching distance m Height m 1m sec over 0 5 1m sec 0 0 5m sec ...

Page 351: ...ght m 1m sec over 0 5 1m sec 0 0 5m sec 2 Heating Me Air velocity distribution 0 0 5 1 1 5 2 2 5 3 3 5 4 0 2 4 6 8 10 12 14 Reaching distance m Height m 1m sec over 0 5 1m sec 0 0 5m sec 3 Heating Lo Air velocity distribution 0 0 5 1 1 5 2 2 5 3 3 5 4 0 2 4 6 8 10 12 14 Reaching distance m Height m 1m sec over 0 5 1m sec 0 0 5m sec ...

Page 352: ...tribution 0 0 5 1 1 5 2 2 5 3 3 5 4 0 2 4 6 8 10 12 14 Reaching distance m Height m 1m sec over 0 5 1m sec 0 0 5m sec 2 Cooling Me Air velocity distribution 0 0 5 1 1 5 2 2 5 3 3 5 4 0 2 4 6 8 10 12 14 Reaching distance m Height m 1m sec over 0 5 1m sec 0 0 5m sec 3 Cooling Lo Air velocity distribution 0 0 5 1 1 5 2 2 5 3 3 5 4 0 2 4 6 8 10 12 14 Reaching distance m Height m 1m sec over 0 5 1m sec...

Page 353: ...ght m 1m sec over 0 5 1m sec 0 0 5m sec 2 Heating Me Air velocity distribution 0 0 5 1 1 5 2 2 5 3 3 5 4 0 2 4 6 8 10 12 14 Reaching distance m Height m 1m sec over 0 5 1m sec 0 0 5m sec 3 Heating Lo Air velocity distribution 0 0 5 1 1 5 2 2 5 3 3 5 4 0 2 4 6 8 10 12 14 Reaching distance m Height m 1m sec over 0 5 1m sec 0 0 5m sec ...

Page 354: ...m Height m 1m sec over 0 5 1m sec 0 0 5m sec 2 Cooling Me Air velocity distribution 0 0 5 1 1 5 2 2 5 3 3 5 4 0 2 4 6 8 10 12 14 Reaching distance m Height m 1m sec over 0 5 1m sec 0 0 5m sec 3 Cooling Lo Air velocity distribution 0 0 5 1 1 5 2 2 5 3 3 5 4 0 2 4 6 8 10 12 14 Reaching distance m Height m 1m sec over 0 5 1m sec 0 0 5m sec ...

Page 355: ...ght m 1m sec over 0 5 1m sec 0 0 5m sec 2 Heating Me Air velocity distribution 0 0 5 1 1 5 2 2 5 3 3 5 4 0 2 4 6 8 10 12 14 Reaching distance m Height m 1m sec over 0 5 1m sec 0 0 5m sec 3 Heating Lo Air velocity distribution 0 0 5 1 1 5 2 2 5 3 3 5 4 0 2 4 6 8 10 12 14 Reaching distance m Height m 1m sec over 0 5 1m sec 0 0 5m sec ...

Page 356: ...m Height m 1m sec over 0 5 1m sec 0 0 5m sec 2 Cooling Me Air velocity distribution 0 0 5 1 1 5 2 2 5 3 3 5 4 0 2 4 6 8 10 12 14 Reaching distance m Height m 1m sec over 0 5 1m sec 0 0 5m sec 3 Cooling Lo Air velocity distribution 0 0 5 1 1 5 2 2 5 3 3 5 4 0 2 4 6 8 10 12 14 Reaching distance m Height m 1m sec over 0 5 1m sec 0 0 5m sec ...

Page 357: ...ght m 1m sec over 0 5 1m sec 0 0 5m sec 2 Heating Me Air velocity distribution 0 0 5 1 1 5 2 2 5 3 3 5 4 0 2 4 6 8 10 12 14 Reaching distance m Height m 1m sec over 0 5 1m sec 0 0 5m sec 3 Heating Lo Air velocity distribution 0 0 5 1 1 5 2 2 5 3 3 5 4 0 2 4 6 8 10 12 14 Reaching distance m Height m 1m sec over 0 5 1m sec 0 0 5m sec ...

Page 358: ...25 30 35 40 45 50 6 7 8 9 10 11 12 Air flow volume m3 min External static pressure Pa 0mmAq 0Pa 3mmAq 29Pa H H M M L L S 28NA1E5 3mmAq 29Pa Q P Q P Q P 標準 11 0 29 4 10 0 20 6 8 0 14 7 下限 9 9 43 7 9 2 32 2 7 3 26 6 センター 11 0 29 4 10 0 20 6 8 0 14 7 上限 12 1 11 2 10 8 5 7 8 5 2 6 0mmAq 0Pa Q P Q P Q P 標準 11 0 0 0 10 0 0 0 8 0 0 0 下限 9 9 23 2 9 2 17 3 7 3 16 2 センター 11 0 0 0 10 0 0 0 8 0 0 0 上限 11 0 0 ...

Page 359: ... 7 8 9 10 11 12 13 Air flow volume m3 min External static pressure Pa 0mmAq 0Pa 3mmAq 29Pa H H M M L L S 36NA1E5 3mmAq 29Pa Q P Q P Q P 標準 11 0 29 4 9 0 20 6 7 0 14 7 下限 9 9 43 8 8 2 32 1 6 3 26 6 センター 11 0 29 4 9 0 20 6 7 0 14 7 上限 12 1 11 4 9 8 5 6 7 5 2 6 0mmAq 0Pa Q P Q P Q P 標準 11 0 0 0 9 0 0 0 7 0 0 0 下限 9 9 23 2 8 2 17 2 6 3 16 2 センター 11 0 0 0 9 0 0 0 7 0 0 0 上限 11 0 0 0 9 0 0 0 7 0 0 0 H M...

Page 360: ...8 9 10 11 12 13 14 Air flow volume m3 min External static pressure Pa 0mmAq 0Pa 3mmAq 29Pa H H M M L L S 56NA1E5 3mmAq 29Pa Q P Q P Q P 標準 12 5 29 4 10 5 20 6 8 5 14 7 下限 11 3 43 8 9 6 32 2 7 7 26 6 センター 12 5 29 4 10 5 20 6 8 5 14 7 上限 13 8 11 3 11 4 5 7 9 1 2 6 0mmAq 0Pa Q P Q P Q P 標準 12 5 0 0 10 5 0 0 8 5 0 0 下限 11 3 23 1 9 6 17 3 7 7 16 2 センター 12 5 0 0 10 5 0 0 8 5 0 0 上限 12 5 0 0 10 5 0 0 8 5...

Page 361: ...0 80 90 100 10 11 12 13 14 15 16 17 18 19 20 Air flow volume m3 min External static pressure Pa 5mmAq 49Pa 7mmAq 69Pa H H M M L L S 56MA1E5 5mmAq 49Pa Q P Q P Q P 標準 15 0 49 0 13 0 32 1 11 0 25 6 下限 13 5 74 1 12 0 57 2 10 2 47 8 センター 15 0 49 0 13 0 32 1 11 0 25 6 上限 16 5 11 1 14 0 6 8 11 6 3 5 7mmAq 69Pa Q P Q P Q P 標準 15 0 69 0 13 0 50 0 11 0 41 0 下限 13 5 86 3 12 0 70 9 10 2 60 0 センター 15 0 69 0 1...

Page 362: ...15 16 17 18 19 20 Air flow volume m3 min External static pressure Pa 5mmAq 49Pa 7mmAq 69Pa H H M M L L S 71MA1E5 5mmAq 49Pa Q P Q P Q P 標準 17 0 49 0 14 0 35 8 12 0 26 6 下限 15 3 77 4 13 0 59 2 11 2 49 8 センター 17 0 49 0 14 0 35 8 12 0 26 6 上限 18 7 12 1 15 0 6 8 12 6 3 7 7mmAq 69Pa Q P Q P Q P 標準 17 0 69 0 14 0 51 0 12 0 41 0 下限 15 3 90 5 13 0 72 9 11 2 61 5 センター 17 0 69 0 14 0 51 0 12 0 41 0 上限 18 7 ...

Page 363: ... 0 17 0 57 0 14 0 41 0 下限 17 1 94 7 15 5 83 1 13 0 65 1 センター 19 0 69 0 17 0 57 0 14 0 41 0 上限 20 9 37 2 18 4 27 1 14 8 16 1 H M L H M L Standard air flow volume H19 M17 L14m3 min 0 10 20 30 40 50 60 70 80 90 100 12 13 14 15 16 17 18 19 20 21 22 Air flow volume m3 min External static pressure Pa 5mmAq 49Pa 7mmAq 69Pa H H M M L L 20 7 6 Outdoor Units U 4LA1E5 U 5LA1E5 U 6LA1E5 Hi m3 min 92 0 95 0 98...

Page 364: ... NC 60 NC 50 NC 30 NC 20 H M L H M L Frequency 50Hz Fan Speed C scale dB Back Ground Noise12dB H 33 39 M L 38 44 A scale dB 41 36 10 20 30 40 50 60 70 80 63 125 250 500 1000 2000 4000 8000 Frequency Hz Octave Band Sound Pressure Level dB OdB 0 0002μbar S 36KA1E5 S 36KA1E5S Octave Band Central Frequency Hz NC 40 NC 50 NC 30 NC 20 H M L H M L NC 60 50Hz Frequency H 40 34 42 M L 40 38 43 46 Fan Speed...

Page 365: ...0 4000 8000 Frequency Hz Octave Band Sound Pressure Level dB OdB 0 0002μbar S 63KA1E5 Octave Band Central Frequency Hz NC 40 NC 60 NC 50 NC 30 NC 20 H M L H M L Frequency 50Hz Fan Speed C scale dB Back Ground Noise12dB H 39 46 M L 44 51 A scale dB 47 43 10 20 30 40 50 60 70 80 63 125 250 500 1000 2000 4000 8000 Frequency Hz Octave Band Sound Pressure Level dB OdB 0 0002μbar S 71KA1E5 Octave Band C...

Page 366: ... NC 50 NC 30 NC 20 H M L H M L Frequency 50Hz Fan Speed C scale dB Back Ground Noise12dB H 33 37 M L 38 42 A scale dB 40 35 10 20 30 40 50 60 70 80 63 125 250 500 1000 2000 4000 8000 Frequency Hz Octave Band Sound Pressure Level dB OdB 0 0002μbar S 36YA1E5 Octave Band Central Frequency Hz NC 40 NC 50 NC 30 NC 20 H M L H M L NC 60 50Hz Frequency H 40 34 38 M L 40 36 41 43 Fan Speed Back Ground Nois...

Page 367: ...8000 Frequency Hz Octave Band Sound Pressure Level dB OdB 0 0002μbar S 56YA1E5 Octave Band Central Frequency Hz NC 40 NC 50 NC 30 NC 20 H M L H M L NC 60 50Hz Frequency H 40 36 40 M L 41 38 43 44 Fan Speed Back Ground Noise12dB C scale dB A scale dB C scale dB ...

Page 368: ...5 250 500 1000 2000 4000 8000 Frequency Hz Octave Band Sound Pressure Level dB OdB 0 0002μbar S 71UA1E5 230V Octave Band Central Frequency Hz NC 40 NC 60 NC 50 NC 30 NC 20 H M L H M L Frequency 50Hz Fan Speed C scale dB Back Ground Noise12dB H 36 42 M L 42 47 A scale dB 45 40 10 20 30 40 50 60 70 80 63 125 250 500 1000 2000 4000 8000 Frequency Hz Octave Band Sound Pressure Level dB OdB 0 0002μbar ...

Page 369: ...NC 50 NC 30 NC 20 H M L H M L Frequency 50Hz Fan Speed C scale dB Back Ground Noise12dB H 30 37 M L 35 42 A scale dB 39 33 10 20 30 40 50 60 70 80 63 125 250 500 1000 2000 4000 8000 Frequency Hz Octave Band Sound Pressure Level dB OdB 0 0002μbar S 32NA1E5 230V Octave Band Central Frequency Hz NC 40 NC 50 NC 30 NC 20 H M L H M L NC 60 50Hz Frequency H 40 31 38 M L 36 34 40 43 Fan Speed Back Ground ...

Page 370: ...60 50Hz Frequency H 40 32 39 M L 38 37 42 44 Fan Speed Back Ground Noise12dB C scale dB A scale dB C scale dB 10 20 30 40 50 60 70 80 63 125 250 500 1000 2000 4000 8000 Frequency Hz Octave Band Sound Pressure Level dB OdB 0 0002μbar S 56NA1E5 230V Octave Band Central Frequency Hz NC 40 NC 60 NC 50 NC 30 NC 20 H M L H M L Frequency 50Hz Fan Speed C scale dB Back Ground Noise12dB H 32 39 M L 38 44 A...

Page 371: ...0 NC 50 NC 30 NC 20 H M L H M L Frequency 50Hz Fan Speed C scale dB Back Ground Noise12dB H 35 42 M L 39 46 A scale dB 44 40 10 20 30 40 50 60 70 80 63 125 250 500 1000 2000 4000 8000 Frequency Hz Octave Band Sound Pressure Level dB OdB 0 0002μbar S 63MA1E5 230V Octave Band Central Frequency Hz NC 40 NC 50 NC 30 NC 20 H M L H M L NC 60 50Hz Frequency H 40 36 43 M L 40 41 45 47 Fan Speed Back Groun...

Page 372: ...0 Frequency Hz Octave Band Sound Pressure Level dB OdB 0 0002μbar S 90MA1E5 230V Octave Band Central Frequency Hz NC 40 NC 50 NC 30 NC 20 H M L H M L NC 60 50Hz Frequency H 40 37 44 M L 42 42 47 49 Fan Speed Back Ground Noise12dB C scale dB A scale dB C scale dB ...

Page 373: ... Hz NC 40 NC 60 NC 50 NC 30 NC 20 H Frequency 50Hz Fan Speed C scale dB Back Ground Noise12dB H 54 58 A scale dB 10 20 30 40 50 60 70 80 63 125 250 500 1000 2000 4000 8000 Frequency Hz Octave Band Sound Pressure Level dB OdB 0 0002μbar U 5LA1E5 Cooling Octave Band Central Frequency Hz NC 40 NC 50 NC 30 NC 20 H NC 60 Frequency 50Hz Fan Speed C scale dB Back Ground Noise12dB H 53 58 A scale dB 10 20...

Page 374: ...NC 50 NC 30 NC 20 H NC 60 Frequency 50Hz Fan Speed C scale dB Back Ground Noise12dB H 55 59 A scale dB 10 20 30 40 50 60 70 80 63 125 250 500 1000 2000 4000 8000 Frequency Hz Octave Band Sound Pressure Level dB OdB 0 0002μbar U 6LA1E5 Heating Octave Band Central Frequency Hz NC 40 NC 60 NC 50 NC 30 NC 20 H Frequency 50Hz Fan Speed C scale dB Back Ground Noise12dB H 57 60 A scale dB ...

Page 375: ...4 38 1 5m microphone outlet duct 2m inlet duct 1m indoor unit S 22YA1E5 36 33 36 33 S 28YA1E5 37 33 37 33 S 36YA1E5 38 34 38 34 S 45YA1E5 39 35 39 35 Mini Cassette S 56YA1E5 40 36 40 36 S 63UA1E5 41 35 41 36 41 35 41 36 S 71UA1E5 42 36 42 37 42 36 42 37 Cassette S 90UA1E5 42 36 42 37 42 36 42 37 1 5m microphone indoor unit S 22KA1E5 S 38 33 38 33 S 28KA1E5 S 39 33 39 33 S 36KA1E5 S 42 34 42 34 S 4...

Page 376: ...376 20 8 8 Outdoor Unit Measurement Specification dB A Cooling Heating 220 230 240V 50Hz microphone position U 4LA1E5 52 54 U 5LA1E5 53 55 U 6LA1E5 55 57 1 5m microphone 1 0m ...

Page 377: ... 25 10 15 20 30 35 5 0 5 10 15 20 25 30 35 40 45 indoor air temperature WB outdoor air temperature DB pull down area Heating 25 10 15 20 30 35 5 0 10 15 20 indoor air temperature DB outdoor air temperature WB 5 10 15 20 pull up area ...

Page 378: ... Main3 Main4 Total pipe length of Sub pipe 50m or less Sub1 Sub2 Sub3 Sub4 Sub5 Sub pipe length 15m or less From Outdoor unit to innermost indoor unit difference 55m or less Allowable pipe length From 1st branch to innermost indoor unit difference 30m or less Pipe connection example 1st branch Main 1 Main 2 Main 3 Main 4 Sub 1 Sub 2 Sub 3 Sub 5 Sub 4 IN OUT height difference IN IN height differenc...

Page 379: ... D3 NO Cooling capacity 2 2 kW 2 8 kW 3 2 kW 3 6 kW 4 5 kW 5 6 kW 6 3 kW 7 1 kW 9 0 kW Total indoor capacity Total indoor unit number 1 5 1 14 6 6 2 4 2 14 4 6 3 5 1 14 2 6 4 5 1 13 8 6 5 6 13 2 6 6 1 1 3 14 6 5 7 1 2 1 1 14 6 5 8 2 2 1 14 5 5 9 4 1 14 4 5 10 2 1 2 14 4 5 11 2 2 1 14 4 5 12 4 1 14 4 5 13 3 1 1 14 3 5 14 1 2 2 14 2 5 15 1 3 1 14 2 5 16 2 3 14 5 17 5 14 5 18 2 1 1 1 14 5 19 3 1 1 13...

Page 380: ...48 1 2 1 14 2 4 49 3 1 14 1 4 50 1 2 1 14 1 4 51 1 1 1 1 14 1 4 52 1 1 2 14 4 53 1 3 14 4 54 3 1 14 4 55 2 1 1 13 9 4 56 1 2 1 13 9 4 57 1 1 1 1 13 8 4 58 3 1 13 7 4 59 2 1 1 13 7 4 60 1 2 1 13 7 4 61 1 3 13 6 4 62 2 2 13 6 4 63 2 1 1 13 6 4 64 2 1 1 13 5 4 65 1 1 1 1 13 5 4 66 2 2 13 4 4 67 1 2 1 13 4 4 68 2 1 1 13 3 4 69 3 1 13 2 4 70 2 1 1 13 2 4 71 1 1 2 13 2 4 72 1 2 1 13 1 4 73 1 1 1 1 13 1 ...

Page 381: ... 2 4 101 4 11 2 4 102 3 1 11 1 4 103 1 2 1 11 4 104 2 1 1 10 8 4 105 2 2 10 8 4 106 1 3 10 6 4 107 2 1 1 10 4 4 108 3 1 10 2 4 109 2 2 10 4 110 3 1 9 8 4 111 3 1 9 4 4 112 4 8 8 4 113 2 1 14 6 3 114 2 1 14 6 3 115 1 1 1 14 4 3 116 1 1 1 14 4 3 117 1 2 14 4 3 118 1 1 1 14 4 3 119 2 1 14 3 3 120 1 1 1 14 1 3 121 1 1 1 14 3 122 1 2 14 3 123 1 1 1 14 3 124 1 1 1 13 9 3 125 1 1 1 13 8 3 126 1 1 1 13 7 ...

Page 382: ... 153 2 1 12 3 154 2 1 11 9 3 155 1 2 11 8 3 156 1 1 1 11 7 3 157 2 1 11 7 3 158 1 1 1 11 6 3 159 2 1 11 5 3 160 1 1 1 11 4 3 161 1 1 1 11 3 3 162 1 1 1 11 3 3 163 1 2 11 2 3 164 2 1 11 2 3 165 1 1 1 11 3 166 1 1 1 10 9 3 167 2 1 10 9 3 168 3 10 8 3 169 2 1 10 7 3 170 1 1 1 10 6 3 171 1 1 1 10 5 3 172 1 2 10 4 3 173 1 1 1 10 3 3 174 2 1 10 1 3 175 2 1 10 3 176 1 2 10 3 177 2 1 10 3 178 1 1 1 9 9 3 ...

Page 383: ... 204 1 1 12 2 2 205 1 1 11 9 2 206 1 1 11 8 2 207 1 1 11 6 2 208 1 1 11 2 2 209 2 11 2 2 210 1 1 10 8 2 211 1 1 10 7 2 212 1 1 10 3 2 213 1 1 10 1 2 214 1 1 9 9 2 215 1 1 9 9 2 216 1 1 9 5 2 217 1 1 9 3 2 218 1 1 9 2 2 219 1 1 9 1 2 220 2 9 2 221 1 1 8 8 2 222 1 1 8 5 2 223 1 1 8 4 2 224 1 1 8 1 2 225 1 1 7 8 2 226 1 1 7 7 2 227 1 1 7 3 2 228 2 7 2 2 229 1 1 6 8 2 230 1 1 6 7 2 231 1 1 6 4 2 232 2...

Page 384: ...16 1 6 4 5 1 15 7 6 5 6 15 6 6 1 1 3 16 5 5 7 1 2 1 1 16 7 5 8 2 2 1 16 5 5 9 4 1 16 4 5 10 2 1 2 16 6 5 11 2 2 1 16 4 5 12 4 1 16 4 5 13 3 1 1 16 2 5 14 1 2 2 16 1 5 15 1 3 1 16 3 5 16 2 3 15 8 5 17 5 16 5 18 2 1 1 1 16 5 19 3 1 1 15 8 5 20 3 2 15 9 5 21 1 3 1 15 7 5 22 2 1 2 15 4 5 23 2 2 1 15 6 5 24 3 1 1 15 3 5 25 1 4 15 3 5 26 4 1 15 1 5 27 2 2 1 15 5 28 3 1 1 14 9 5 29 3 2 14 7 5 30 2 3 14 6...

Page 385: ...1 15 7 4 60 1 2 1 15 5 4 61 1 3 15 8 4 62 2 2 15 6 4 63 2 1 1 15 6 4 64 2 1 1 15 3 4 65 1 1 1 1 15 4 4 66 2 2 15 2 4 67 1 2 1 15 3 4 68 2 1 1 15 1 4 69 3 1 15 4 70 2 1 1 15 4 71 1 1 2 15 2 4 72 1 2 1 14 8 4 73 1 1 1 1 15 4 74 1 3 15 1 4 75 3 1 14 6 4 76 3 1 14 7 4 77 2 1 1 14 6 4 78 2 2 14 8 4 79 4 14 4 4 80 1 2 1 14 6 4 81 1 1 1 1 14 4 4 82 1 1 2 14 5 4 83 2 1 1 14 3 4 84 1 3 14 4 85 2 1 1 14 2 4...

Page 386: ... 16 4 3 114 2 1 16 6 3 115 1 1 1 16 1 3 116 1 1 1 16 3 3 117 1 2 16 4 3 118 1 1 1 16 4 3 119 2 1 16 4 3 120 1 1 1 16 3 121 1 1 1 15 7 3 122 1 2 16 3 123 1 1 1 15 8 3 124 1 1 1 15 8 3 125 1 1 1 15 6 3 126 1 1 1 15 7 3 127 1 1 1 15 4 3 128 1 1 1 15 4 3 129 2 1 15 2 3 130 2 1 15 5 3 131 3 15 3 3 132 2 1 15 3 133 1 2 15 3 3 134 1 1 1 15 1 3 135 1 1 1 14 9 3 136 1 1 1 14 8 3 137 1 1 1 14 7 3 138 1 1 1 ...

Page 387: ...3 165 1 1 1 12 5 3 166 1 1 1 12 5 3 167 2 1 12 3 3 168 3 12 6 3 169 2 1 12 1 3 170 1 1 1 12 1 3 171 1 1 1 11 9 3 172 1 2 12 3 173 1 1 1 11 8 3 174 2 1 11 5 3 175 2 1 11 4 3 176 1 2 11 6 3 177 2 1 11 4 3 178 1 1 1 11 2 3 179 3 10 8 3 180 1 1 1 11 3 181 1 1 1 10 8 3 182 1 2 10 9 3 183 2 1 10 6 3 184 1 2 10 4 3 185 1 1 1 10 3 3 186 2 1 10 1 3 187 2 1 10 3 188 1 2 9 7 3 189 1 1 1 9 9 3 190 3 9 6 3 191...

Page 388: ... 210 1 1 12 2 2 211 1 1 12 2 2 212 1 1 11 6 2 213 1 1 11 5 2 214 1 1 11 3 2 215 1 1 11 2 2 216 1 1 10 7 2 217 1 1 10 5 2 218 1 1 10 6 2 219 1 1 10 3 2 220 2 10 2 2 221 1 1 10 2 222 1 1 9 6 2 223 1 1 9 6 2 224 1 1 9 3 2 225 1 1 8 9 2 226 1 1 8 7 2 227 1 1 8 3 2 228 2 8 4 2 229 1 1 7 8 2 230 1 1 7 6 2 231 1 1 7 4 2 232 2 7 2 2 233 1 1 6 8 2 234 1 1 6 7 2 235 2 6 4 2 ...

Page 389: ... 8 kW 3 2 kW 3 6 kW 4 5 kW 5 6 kW 6 3 kW 7 1 kW 9 0 kW Total indoor capacity Total indoor unit number 1 7 1 18 2 8 2 8 17 6 8 3 5 2 18 2 7 4 3 3 1 18 2 7 5 4 2 1 18 7 6 4 1 2 18 7 7 5 1 1 17 8 7 8 3 4 17 8 7 9 6 1 17 7 7 10 4 2 1 17 6 7 11 5 1 1 17 4 7 12 5 2 17 4 7 13 4 3 17 2 7 14 5 1 1 17 7 15 6 1 16 8 7 16 5 2 16 6 7 17 6 1 16 4 7 18 6 1 16 7 19 7 15 4 7 20 3 1 1 1 18 2 6 21 1 1 3 1 18 2 6 22 ...

Page 390: ... 17 3 6 51 2 3 1 17 3 6 52 4 1 1 17 2 6 53 2 1 2 1 17 2 6 54 2 4 17 2 6 55 2 2 2 17 2 6 56 5 1 17 2 6 57 3 1 1 1 17 1 6 58 3 1 2 17 6 59 1 4 1 17 6 60 1 3 2 17 6 61 4 1 1 16 9 6 62 2 2 1 1 16 8 6 63 2 1 3 16 8 6 64 6 16 8 6 65 3 2 1 16 7 6 66 5 1 16 6 6 67 3 2 1 16 6 6 68 1 4 1 16 6 6 69 4 1 1 16 5 6 70 2 3 1 16 4 6 71 2 2 2 16 4 6 72 3 1 1 1 16 2 6 73 3 3 16 2 6 74 1 5 16 2 6 75 4 1 1 16 1 6 76 4...

Page 391: ... 7 5 106 3 1 1 17 7 5 107 1 1 2 1 17 7 5 108 1 1 2 1 17 7 5 109 1 4 17 6 5 110 1 2 2 17 6 5 111 2 2 1 17 6 5 112 2 1 1 1 17 5 5 113 2 1 1 1 17 5 5 114 1 1 1 1 1 17 4 5 115 1 3 1 17 4 5 116 1 2 1 1 17 3 5 117 4 1 17 3 5 118 1 2 1 1 17 3 5 119 2 3 17 2 5 120 1 1 1 2 17 2 5 121 3 1 1 17 2 5 122 1 1 2 1 17 1 5 123 2 2 1 17 1 5 124 1 1 2 1 17 5 125 1 3 1 16 9 5 126 3 1 1 16 9 5 127 2 1 1 1 16 9 5 128 2...

Page 392: ... 5 157 3 1 1 15 4 5 158 1 3 1 15 4 5 159 1 1 1 2 15 4 5 160 2 2 1 15 3 5 161 2 1 1 1 15 3 5 162 2 3 15 2 5 163 2 3 15 2 5 164 3 1 1 15 2 5 165 4 1 15 1 5 166 1 3 1 15 1 5 167 1 1 2 1 15 5 168 1 4 15 5 169 1 2 2 15 5 170 3 1 1 15 5 171 2 1 1 1 14 9 5 172 2 1 2 14 8 5 173 3 2 14 8 5 174 4 1 14 8 5 175 3 1 1 14 7 5 176 1 1 3 14 6 5 177 1 2 1 1 14 6 5 178 2 2 1 14 5 5 179 2 2 1 14 4 5 180 2 1 2 14 4 5...

Page 393: ...18 4 212 1 1 1 1 17 9 4 213 2 1 1 17 8 4 214 1 2 1 17 8 4 215 1 1 1 1 17 6 4 216 1 1 1 1 17 6 4 217 1 2 1 17 6 4 218 2 2 17 6 4 219 1 2 1 17 5 4 220 1 1 1 1 17 3 4 221 1 1 1 1 17 2 4 222 1 1 2 17 2 4 223 2 1 1 17 2 4 224 2 1 1 17 1 4 225 1 1 1 1 17 4 226 1 1 1 1 16 9 4 227 1 1 1 1 16 8 4 228 3 1 16 7 4 229 1 1 1 1 16 7 4 230 1 2 1 16 7 4 231 1 3 16 7 4 232 2 1 1 16 6 4 233 1 1 2 16 6 4 234 2 1 1 1...

Page 394: ... 4 262 2 1 1 15 1 4 263 2 1 1 15 1 4 264 1 1 1 1 15 1 4 265 1 1 2 15 4 266 1 2 1 15 4 267 1 2 1 14 9 4 268 1 2 1 14 9 4 269 1 2 1 14 9 4 270 1 1 1 1 14 9 4 271 1 1 2 14 8 4 272 1 2 1 14 8 4 273 2 1 1 14 8 4 274 2 1 1 14 7 4 275 3 1 14 7 4 276 1 1 1 1 14 6 4 277 2 2 14 6 4 278 1 1 1 1 14 5 4 279 2 1 1 14 5 4 280 1 2 1 14 5 4 281 2 1 1 14 5 4 282 1 1 2 14 4 4 283 2 1 1 14 4 4 284 4 14 4 4 285 2 1 1 ...

Page 395: ...1 2 13 2 4 312 1 2 1 13 1 4 313 1 1 1 1 13 1 4 314 1 3 13 4 315 3 1 12 9 4 316 3 1 12 9 4 317 4 12 8 4 318 2 2 12 8 4 319 2 1 1 12 8 4 320 1 2 1 12 8 4 321 1 1 1 1 12 7 4 322 1 1 2 12 6 4 323 2 1 1 12 5 4 324 1 3 12 4 4 325 2 1 1 12 4 4 326 1 2 1 12 3 4 327 1 2 1 12 2 4 328 1 1 2 12 2 4 329 3 1 12 2 4 330 2 1 1 12 1 4 331 2 2 12 4 332 3 1 12 4 333 1 3 11 8 4 334 1 1 1 1 11 8 4 335 2 1 1 11 7 4 336...

Page 396: ... 3 362 1 1 1 15 5 3 363 2 1 15 4 3 364 1 1 1 15 4 3 365 1 2 15 4 3 366 2 1 15 3 3 367 1 1 1 15 2 3 368 1 1 1 15 1 3 369 1 1 1 15 3 370 1 1 1 14 9 3 371 1 1 1 14 8 3 372 1 1 1 14 8 3 373 1 2 14 8 3 374 1 2 14 8 3 375 1 1 1 14 7 3 376 2 1 14 6 3 377 2 1 14 6 3 378 1 1 1 14 4 3 379 1 2 14 4 3 380 1 1 1 14 4 3 381 1 1 1 14 4 3 382 2 1 14 3 3 383 1 1 1 14 1 3 384 1 1 1 14 3 385 1 1 1 14 3 386 1 2 14 3 ...

Page 397: ...411 1 1 1 12 3 3 412 1 2 12 2 3 413 1 1 1 12 1 3 414 1 1 1 12 1 3 415 2 1 12 3 416 1 1 1 12 3 417 2 1 11 9 3 418 1 2 11 8 3 419 1 1 1 11 7 3 420 2 1 11 7 3 421 1 1 1 11 6 3 422 2 1 11 5 3 423 1 1 1 11 4 3 424 1 1 1 11 3 3 425 1 1 1 11 3 3 426 1 2 11 2 3 427 2 1 11 2 3 428 1 1 1 11 3 429 2 1 10 9 3 430 1 1 1 10 9 3 431 3 10 8 3 432 2 1 10 7 3 433 1 1 1 10 6 3 434 1 1 1 10 5 3 435 1 2 10 4 3 436 1 1...

Page 398: ...0 1 1 14 6 2 461 2 14 2 2 462 1 1 13 5 2 463 1 1 13 4 2 464 1 1 12 7 2 465 1 1 12 6 2 466 2 12 6 2 467 1 1 12 2 2 468 1 1 11 9 2 469 1 1 11 8 2 470 1 1 11 6 2 471 1 1 11 2 2 472 2 11 2 2 473 1 1 10 8 2 474 1 1 10 7 2 475 1 1 10 3 2 476 1 1 10 1 2 477 1 1 9 9 2 478 1 1 9 9 2 479 1 1 9 5 2 480 1 1 9 3 2 481 1 1 9 2 2 482 1 1 9 1 2 483 2 9 2 484 1 1 8 8 2 485 1 1 8 5 2 486 1 1 8 4 2 487 1 1 8 1 2 488...

Page 399: ...20 7 7 5 4 2 1 20 6 7 6 4 1 2 20 4 7 7 5 1 1 20 3 7 8 3 4 20 3 7 9 6 1 20 1 7 10 4 2 1 20 7 11 5 1 1 19 9 7 12 5 2 19 7 7 13 4 3 19 6 7 14 5 1 1 19 3 7 15 6 1 19 2 7 16 5 2 18 9 7 17 6 1 18 6 7 18 6 1 18 2 7 19 7 17 5 7 20 3 1 1 1 20 7 6 21 1 1 3 1 20 7 6 22 1 2 1 2 20 9 6 23 1 5 20 5 6 24 5 1 20 5 6 25 2 2 1 1 20 7 6 26 2 1 2 1 20 5 6 27 4 1 1 20 6 6 28 2 1 3 20 8 6 29 2 2 2 20 6 6 30 4 1 1 20 6 ...

Page 400: ... 4 1 19 5 6 60 1 3 2 19 3 6 61 4 1 1 19 3 6 62 2 2 1 1 19 2 6 63 2 1 3 19 6 64 6 19 2 6 65 3 2 1 19 6 66 5 1 18 9 6 67 3 2 1 18 9 6 68 1 4 1 18 9 6 69 4 1 1 18 7 6 70 2 3 1 18 8 6 71 2 2 2 18 6 6 72 3 1 1 1 18 5 6 73 3 3 18 3 6 74 1 5 18 5 6 75 4 1 1 18 3 6 76 4 2 18 4 6 77 2 3 1 18 2 6 78 3 1 2 17 9 6 79 3 2 1 18 1 6 80 4 1 1 17 8 6 81 2 4 17 8 6 82 5 1 17 6 6 83 3 2 1 17 5 6 84 4 1 1 17 4 6 85 4...

Page 401: ... 9 5 114 1 1 1 1 1 19 9 5 115 1 3 1 19 7 5 116 1 2 1 1 19 6 5 117 4 1 19 5 5 118 1 2 1 1 19 7 5 119 2 3 19 8 5 120 1 1 1 2 19 5 5 121 3 1 1 19 6 5 122 1 1 2 1 19 6 5 123 2 2 1 19 3 5 124 1 1 2 1 19 3 5 125 1 3 1 19 1 5 126 3 1 1 19 1 5 127 2 1 1 1 19 3 5 128 2 1 1 1 19 2 5 129 1 1 3 19 4 5 130 3 2 19 2 5 131 1 2 1 1 19 5 132 2 1 1 1 18 9 5 133 2 1 2 18 8 5 134 1 2 1 1 18 9 5 135 2 2 1 18 7 5 136 4...

Page 402: ...166 1 3 1 17 2 5 167 1 1 2 1 17 1 5 168 1 4 16 9 5 169 1 2 2 17 3 5 170 3 1 1 17 1 5 171 2 1 1 1 16 9 5 172 2 1 2 17 5 173 3 2 16 8 5 174 4 1 17 5 175 3 1 1 16 8 5 176 1 1 3 16 5 5 177 1 2 1 1 16 7 5 178 2 2 1 16 5 5 179 2 2 1 16 4 5 180 2 1 2 16 6 5 181 4 1 16 4 5 182 4 1 16 4 5 183 3 1 1 16 2 5 184 1 3 1 16 3 5 185 2 3 15 8 5 186 2 1 1 1 16 5 187 5 16 5 188 3 1 1 15 8 5 189 3 2 15 9 5 190 1 3 1 ...

Page 403: ... 2 1 20 4 220 1 1 1 1 19 6 4 221 1 1 1 1 19 3 4 222 1 1 2 19 6 4 223 2 1 1 19 4 4 224 2 1 1 19 4 4 225 1 1 1 1 19 2 4 226 1 1 1 1 19 3 4 227 1 1 1 1 19 4 228 3 1 18 8 4 229 1 1 1 1 19 4 230 1 2 1 19 1 4 231 1 3 18 9 4 232 2 1 1 18 6 4 233 1 1 2 18 9 4 234 2 1 1 18 7 4 235 2 1 1 18 5 4 236 1 2 1 18 4 4 237 1 1 1 1 18 3 4 238 1 1 1 1 18 3 4 239 1 1 1 1 18 3 4 240 1 2 1 18 4 4 241 3 1 17 9 4 242 2 1 ...

Page 404: ...16 9 4 270 1 1 1 1 17 4 271 1 1 2 16 9 4 272 1 2 1 16 8 4 273 2 1 1 17 4 274 2 1 1 16 6 4 275 3 1 16 7 4 276 1 1 1 1 16 7 4 277 2 2 16 6 4 278 1 1 1 1 16 4 4 279 2 1 1 16 5 4 280 1 2 1 16 7 4 281 2 1 1 16 5 4 282 1 1 2 16 3 4 283 2 1 1 16 4 4 284 4 16 8 4 285 2 1 1 16 2 4 286 2 1 1 16 3 4 287 1 2 1 16 1 4 288 1 1 1 1 16 3 4 289 3 1 15 9 4 290 1 1 1 1 16 1 4 291 1 2 1 16 4 292 1 3 16 2 4 293 1 1 2 ...

Page 405: ... 6 4 320 1 2 1 14 6 4 321 1 1 1 1 14 4 4 322 1 1 2 14 5 4 323 2 1 1 14 3 4 324 1 3 14 4 325 2 1 1 14 2 4 326 1 2 1 14 4 327 1 2 1 13 9 4 328 1 1 2 14 1 4 329 3 1 13 9 4 330 2 1 1 13 7 4 331 2 2 13 6 4 332 3 1 13 8 4 333 1 3 13 3 4 334 1 1 1 1 13 5 4 335 2 1 1 13 3 4 336 2 2 13 4 4 337 3 1 13 2 4 338 1 1 2 12 9 4 339 1 2 1 13 1 4 340 2 1 1 12 8 4 341 4 12 8 4 342 3 1 12 6 4 343 1 2 1 12 5 4 344 2 2...

Page 406: ...16 8 3 370 1 1 1 16 9 3 371 1 1 1 16 7 3 372 1 1 1 16 7 3 373 1 2 16 7 3 374 1 2 17 3 375 1 1 1 16 7 3 376 2 1 16 4 3 377 2 1 16 6 3 378 1 1 1 16 1 3 379 1 2 16 4 3 380 1 1 1 16 3 3 381 1 1 1 16 4 3 382 2 1 16 4 3 383 1 1 1 16 3 384 1 1 1 15 8 3 385 1 1 1 15 7 3 386 1 2 16 3 387 1 1 1 15 8 3 388 1 1 1 15 6 3 389 1 1 1 15 7 3 390 1 1 1 15 4 3 391 2 1 15 2 3 392 1 1 1 15 4 3 393 2 1 15 5 3 394 3 15 ...

Page 407: ...19 1 1 1 13 2 3 420 2 1 13 5 3 421 1 1 1 13 2 3 422 2 1 13 3 423 1 1 1 13 1 3 424 1 1 1 12 9 3 425 1 1 1 12 8 3 426 1 2 12 7 3 427 2 1 12 8 3 428 1 1 1 12 5 3 429 2 1 12 3 3 430 1 1 1 12 5 3 431 3 12 6 3 432 2 1 12 1 3 433 1 1 1 12 1 3 434 1 1 1 11 9 3 435 1 2 12 3 436 1 1 1 11 8 3 437 2 1 11 5 3 438 2 1 11 4 3 439 1 2 11 6 3 440 2 1 11 4 3 441 1 1 1 11 2 3 442 3 10 8 3 443 1 1 1 11 3 444 1 1 1 10...

Page 408: ...1 14 4 2 465 1 1 14 2 2 466 2 14 2 2 467 1 1 13 6 2 468 1 1 13 5 2 469 1 1 13 2 2 470 1 1 13 1 2 471 1 1 12 5 2 472 2 12 8 2 473 1 1 12 2 2 474 1 1 12 2 2 475 1 1 11 6 2 476 1 1 11 5 2 477 1 1 11 3 2 478 1 1 11 2 2 479 1 1 10 7 2 480 1 1 10 5 2 481 1 1 10 6 2 482 1 1 10 3 2 483 2 10 2 2 484 1 1 10 2 485 1 1 9 6 2 486 1 1 9 6 2 487 1 1 9 3 2 488 1 1 8 9 2 489 1 1 8 7 2 490 1 1 8 3 2 491 2 8 4 2 ...

Page 409: ... 3 2 kW 3 6 kW 4 5 kW 5 6 kW 6 3 kW 7 1 kW 9 0 kW Total indoor capacity Total indoor unit number 1 5 2 1 20 2 8 2 6 1 1 20 8 3 4 4 20 8 4 7 1 19 9 8 5 5 2 1 19 8 8 6 6 2 19 6 8 7 6 1 1 19 6 8 8 6 1 1 19 2 8 9 7 1 19 8 10 6 2 18 8 8 11 7 1 18 6 8 12 7 1 18 2 8 13 8 17 6 8 14 3 1 3 20 2 7 15 1 4 1 1 20 2 7 16 1 3 3 20 2 7 17 5 1 1 20 2 7 18 5 1 1 20 1 7 19 2 4 1 20 1 7 20 2 2 2 1 20 7 21 2 1 4 20 7 ...

Page 410: ...0 1 6 19 7 51 4 2 1 18 9 7 52 2 4 1 18 8 7 53 4 2 1 18 8 7 54 4 1 2 18 8 7 55 6 1 18 8 7 56 5 1 1 18 7 7 57 3 2 2 18 6 7 58 3 3 1 18 6 7 59 4 1 1 1 18 4 7 60 4 3 18 4 7 61 2 5 18 4 7 62 5 1 1 18 3 7 63 3 3 1 18 2 7 64 5 2 18 2 7 65 4 1 2 18 7 66 4 2 1 18 7 67 5 1 1 17 8 7 68 3 4 17 8 7 69 6 1 17 7 7 70 4 2 1 17 6 7 71 5 1 1 17 4 7 72 5 2 17 4 7 73 4 3 17 2 7 74 5 1 1 17 7 75 6 1 16 8 7 76 5 2 16 6...

Page 411: ...9 6 106 2 3 1 19 9 6 107 2 2 1 1 19 9 6 108 1 1 4 19 8 6 109 2 2 2 19 8 6 110 2 1 1 2 19 8 6 111 1 2 2 1 19 8 6 112 1 3 1 1 19 8 6 113 3 1 1 1 19 7 6 114 2 3 1 19 7 6 115 2 3 1 19 7 6 116 3 1 1 1 19 7 6 117 1 4 1 19 7 6 118 2 1 1 1 1 19 6 6 119 2 3 1 19 6 6 120 1 3 2 19 6 6 121 5 1 19 6 6 122 4 1 1 19 6 6 123 5 1 19 6 6 124 1 3 2 19 6 6 125 2 2 1 1 19 5 6 126 1 1 2 1 1 19 5 6 127 1 4 1 19 5 6 128 ...

Page 412: ... 6 158 2 2 1 1 18 9 6 159 2 1 2 1 18 9 6 160 4 1 1 18 9 6 161 3 1 2 18 8 6 162 2 3 1 18 8 6 163 1 5 18 8 6 164 2 4 18 8 6 165 2 2 1 1 18 8 6 166 3 1 2 18 8 6 167 4 1 1 18 7 6 168 1 2 2 1 18 7 6 169 4 1 1 18 7 6 170 1 3 1 1 18 7 6 171 3 2 1 18 6 6 172 1 1 2 2 18 6 6 173 1 4 1 18 6 6 174 1 2 3 18 6 6 175 3 1 1 1 18 6 6 176 2 1 1 1 1 18 5 6 177 2 3 1 18 5 6 178 3 2 1 18 5 6 179 5 1 18 5 6 180 2 1 3 1...

Page 413: ... 1 1 2 17 6 6 211 4 2 17 6 6 212 2 3 1 17 6 6 213 5 1 17 6 6 214 3 2 1 17 5 6 215 3 1 1 1 17 5 6 216 1 2 3 17 4 6 217 3 3 17 4 6 218 1 3 1 1 17 4 6 219 5 1 17 3 6 220 2 3 1 17 3 6 221 2 1 2 1 17 2 6 222 2 4 17 2 6 223 4 1 1 17 2 6 224 5 1 17 2 6 225 2 2 2 17 2 6 226 3 1 1 1 17 1 6 227 3 1 2 17 6 228 1 3 2 17 6 229 1 4 1 17 6 230 4 1 1 16 9 6 231 2 2 1 1 16 8 6 232 2 1 3 16 8 6 233 6 16 8 6 234 3 2...

Page 414: ...263 2 1 1 1 20 2 5 264 1 2 1 1 20 2 5 265 2 1 2 20 2 5 266 1 1 1 2 20 2 5 267 1 1 1 1 1 20 2 5 268 1 2 1 1 20 2 5 269 1 4 20 2 5 270 4 1 20 2 5 271 2 2 1 20 2 5 272 2 1 1 1 20 1 5 273 1 3 1 20 1 5 274 1 2 1 1 20 1 5 275 3 1 1 20 1 5 276 2 1 2 20 1 5 277 1 1 1 1 1 20 1 5 278 1 2 1 1 20 5 279 1 1 2 1 20 5 280 2 1 2 20 5 281 1 2 1 1 20 5 282 4 1 20 5 283 3 1 1 20 5 284 3 1 1 20 5 285 2 1 1 1 20 5 286...

Page 415: ...312 1 3 1 19 6 5 313 3 2 19 6 5 314 2 1 1 1 19 5 5 315 2 1 1 1 19 5 5 316 1 1 2 1 19 5 5 317 1 1 3 19 5 5 318 1 3 1 19 5 5 319 3 1 1 19 5 5 320 1 2 1 1 19 5 5 321 1 2 1 1 19 4 5 322 2 1 1 1 19 4 5 323 1 1 1 2 19 4 5 324 1 2 2 19 4 5 325 1 2 1 1 19 4 5 326 1 1 1 1 1 19 4 5 327 1 2 1 1 19 3 5 328 1 3 1 19 3 5 329 1 1 3 19 3 5 330 1 2 1 1 19 3 5 331 1 1 2 1 19 3 5 332 3 1 1 19 3 5 333 2 1 1 1 19 3 5 ...

Page 416: ... 5 363 3 1 1 18 8 5 364 2 1 1 1 18 8 5 365 1 1 2 1 18 8 5 366 2 1 1 1 18 8 5 367 1 2 1 1 18 7 5 368 1 3 1 18 7 5 369 2 2 1 18 7 5 370 2 1 1 1 18 7 5 371 1 1 1 1 1 18 7 5 372 3 1 1 18 7 5 373 1 1 1 2 18 6 5 374 3 2 18 6 5 375 1 3 1 18 6 5 376 1 2 1 1 18 6 5 377 1 3 1 18 5 5 378 1 1 2 1 18 5 5 379 1 2 1 1 18 5 5 380 1 2 1 1 18 5 5 381 1 1 2 1 18 5 5 382 1 1 3 18 5 5 383 3 1 1 18 5 5 384 3 1 1 18 5 5...

Page 417: ... 2 1 17 9 5 413 3 1 1 17 9 5 414 2 2 1 17 9 5 415 2 1 1 1 17 9 5 416 2 3 17 9 5 417 1 2 1 1 17 9 5 418 2 1 2 17 8 5 419 1 2 1 1 17 8 5 420 4 1 17 8 5 421 3 2 17 8 5 422 1 1 2 1 17 8 5 423 2 1 1 1 17 7 5 424 3 1 1 17 7 5 425 1 1 2 1 17 7 5 426 1 1 2 1 17 7 5 427 1 2 1 1 17 7 5 428 1 3 1 17 7 5 429 1 4 17 6 5 430 1 2 2 17 6 5 431 2 2 1 17 6 5 432 1 1 1 2 17 6 5 433 3 1 1 17 6 5 434 2 1 1 1 17 5 5 43...

Page 418: ...2 2 1 1 1 16 9 5 463 1 3 1 16 9 5 464 2 1 1 1 16 8 5 465 1 1 3 16 8 5 466 3 2 16 8 5 467 1 2 2 16 8 5 468 4 1 16 8 5 469 1 2 1 1 16 7 5 470 3 1 1 16 7 5 471 2 1 1 1 16 7 5 472 1 1 2 1 16 7 5 473 2 1 2 16 6 5 474 1 2 1 1 16 6 5 475 1 4 16 6 5 476 2 2 1 16 5 5 477 3 1 1 16 5 5 478 3 1 1 16 5 5 479 3 1 1 16 5 5 480 4 1 16 4 5 481 2 2 1 16 4 5 482 1 2 2 16 4 5 483 2 3 16 4 5 484 2 1 1 1 16 4 5 485 1 3...

Page 419: ...5 512 1 2 1 1 15 5 5 513 3 1 1 15 4 5 514 1 3 1 15 4 5 515 1 1 1 2 15 4 5 516 2 2 1 15 3 5 517 2 1 1 1 15 3 5 518 2 3 15 2 5 519 2 3 15 2 5 520 3 1 1 15 2 5 521 4 1 15 1 5 522 1 3 1 15 1 5 523 1 1 2 1 15 5 524 1 4 15 5 525 1 2 2 15 5 526 3 1 1 15 5 527 2 1 1 1 14 9 5 528 2 1 2 14 8 5 529 3 2 14 8 5 530 4 1 14 8 5 531 3 1 1 14 7 5 532 1 1 3 14 6 5 533 1 2 1 1 14 6 5 534 2 2 1 14 5 5 535 2 2 1 14 4 ...

Page 420: ... 563 1 1 1 1 20 2 4 564 1 1 2 20 2 4 565 1 2 1 20 2 4 566 2 1 1 20 2 4 567 2 2 20 2 4 568 1 1 1 1 20 1 4 569 1 1 1 1 20 4 570 1 1 2 20 4 571 1 1 1 1 20 4 572 1 1 1 1 20 4 573 1 3 20 4 574 2 1 1 19 9 4 575 2 1 1 19 9 4 576 1 1 1 1 19 9 4 577 1 1 2 19 9 4 578 3 1 19 8 4 579 2 2 19 8 4 580 3 1 19 8 4 581 2 1 1 19 8 4 582 2 2 19 8 4 583 1 1 1 1 19 8 4 584 1 2 1 19 7 4 585 2 1 1 19 7 4 586 1 2 1 19 7 4...

Page 421: ...12 1 2 1 19 4 613 1 1 2 19 4 614 2 1 1 19 4 615 1 3 19 4 616 1 1 1 1 18 9 4 617 1 1 2 18 9 4 618 1 2 1 18 9 4 619 1 2 1 18 9 4 620 1 1 1 1 18 8 4 621 2 1 1 18 8 4 622 1 1 1 1 18 7 4 623 1 1 1 1 18 7 4 624 1 1 1 1 18 6 4 625 1 1 2 18 6 4 626 3 1 18 6 4 627 2 2 18 6 4 628 1 1 1 1 18 6 4 629 1 2 1 18 5 4 630 1 1 1 1 18 5 4 631 1 1 1 1 18 5 4 632 1 1 2 18 5 4 633 1 1 1 1 18 4 4 634 1 1 1 1 18 4 4 635 ...

Page 422: ... 1 1 17 7 4 663 1 1 1 1 17 7 4 664 1 1 1 1 17 6 4 665 1 1 1 1 17 6 4 666 1 2 1 17 6 4 667 2 2 17 6 4 668 1 1 1 1 17 6 4 669 1 1 2 17 6 4 670 1 1 2 17 6 4 671 1 2 1 17 5 4 672 1 2 1 17 5 4 673 2 1 1 17 5 4 674 1 1 1 1 17 4 4 675 3 1 17 4 4 676 1 2 1 17 4 4 677 1 1 1 1 17 3 4 678 2 1 1 17 3 4 679 1 1 1 1 17 2 4 680 1 1 2 17 2 4 681 2 1 1 17 2 4 682 2 1 1 17 2 4 683 1 1 1 1 17 2 4 684 2 1 1 17 1 4 68...

Page 423: ...4 4 712 2 1 1 16 3 4 713 1 2 1 16 3 4 714 1 3 16 3 4 715 2 1 1 16 3 4 716 1 2 1 16 3 4 717 2 1 1 16 3 4 718 1 1 1 1 16 2 4 719 2 2 16 2 4 720 2 1 1 16 2 4 721 1 1 2 16 2 4 722 1 1 1 1 16 1 4 723 1 1 1 1 16 1 4 724 1 2 1 16 4 725 2 1 1 16 4 726 3 1 15 9 4 727 2 1 1 15 9 4 728 1 1 1 1 15 9 4 729 1 1 1 1 15 9 4 730 1 1 2 15 8 4 731 1 1 1 1 15 8 4 732 1 2 1 15 7 4 733 1 1 1 1 15 7 4 734 1 2 1 15 7 4 7...

Page 424: ...14 9 4 762 1 1 2 14 8 4 763 1 2 1 14 8 4 764 2 1 1 14 8 4 765 2 1 1 14 7 4 766 3 1 14 7 4 767 1 1 1 1 14 6 4 768 2 2 14 6 4 769 1 1 1 1 14 5 4 770 2 1 1 14 5 4 771 1 2 1 14 5 4 772 2 1 1 14 5 4 773 1 1 2 14 4 4 774 2 1 1 14 4 4 775 4 14 4 4 776 2 1 1 14 3 4 777 2 1 1 14 3 4 778 1 2 1 14 2 4 779 1 1 1 1 14 2 4 780 3 1 14 1 4 781 1 1 1 1 14 1 4 782 1 2 1 14 1 4 783 1 3 14 4 784 1 1 2 14 4 785 3 1 14...

Page 425: ... 2 1 12 8 4 812 1 1 1 1 12 7 4 813 1 1 2 12 6 4 814 2 1 1 12 5 4 815 1 3 12 4 4 816 2 1 1 12 4 4 817 1 2 1 12 3 4 818 1 2 1 12 2 4 819 1 1 2 12 2 4 820 3 1 12 2 4 821 2 1 1 12 1 4 822 2 2 12 4 823 3 1 12 4 824 1 3 11 8 4 825 1 1 1 1 11 8 4 826 2 1 1 11 7 4 827 2 2 11 6 4 828 3 1 11 6 4 829 1 1 2 11 4 4 830 1 2 1 11 4 4 831 2 1 1 11 2 4 832 4 11 2 4 833 3 1 11 1 4 834 1 2 1 11 4 835 2 2 10 8 4 836 ...

Page 426: ...8 2 3 862 1 1 1 18 1 3 863 2 1 18 3 864 1 1 1 17 9 3 865 1 2 17 8 3 866 1 1 1 17 8 3 867 1 1 1 17 5 3 868 2 1 17 5 3 869 1 1 1 17 4 3 870 1 2 17 4 3 871 1 1 1 17 2 3 872 1 1 1 17 1 3 873 1 2 17 1 3 874 1 2 17 3 875 1 1 1 17 3 876 1 1 1 16 8 3 877 3 16 8 3 878 1 1 1 16 7 3 879 1 1 1 16 6 3 880 1 2 16 4 3 881 1 1 1 16 4 3 882 1 1 1 16 3 3 883 1 1 1 16 3 3 884 1 1 1 16 2 3 885 2 1 16 2 3 886 1 2 16 2...

Page 427: ... 1 14 4 3 912 1 1 1 14 4 3 913 1 1 1 14 4 3 914 1 2 14 4 3 915 2 1 14 3 3 916 1 1 1 14 1 3 917 1 1 1 14 3 918 1 2 14 3 919 1 1 1 14 3 920 1 1 1 13 9 3 921 1 1 1 13 8 3 922 1 1 1 13 7 3 923 1 1 1 13 6 3 924 1 1 1 13 5 3 925 2 1 13 5 3 926 3 13 5 3 927 2 1 13 5 3 928 2 1 13 4 3 929 1 2 13 4 3 930 1 1 1 13 3 3 931 1 1 1 13 1 3 932 1 1 1 13 1 3 933 1 1 1 13 3 934 1 1 1 12 9 3 935 1 1 1 12 9 3 936 2 1 ...

Page 428: ...60 2 1 11 2 3 961 1 1 1 11 3 962 1 1 1 10 9 3 963 2 1 10 9 3 964 3 10 8 3 965 2 1 10 7 3 966 1 1 1 10 6 3 967 1 1 1 10 5 3 968 1 2 10 4 3 969 1 1 1 10 3 3 970 2 1 10 1 3 971 1 2 10 3 972 2 1 10 3 973 2 1 10 3 974 1 1 1 9 9 3 975 3 9 6 3 976 1 1 1 9 6 3 977 1 1 1 9 5 3 978 1 2 9 4 3 979 2 1 9 2 3 980 1 2 9 2 3 981 1 1 1 9 3 982 2 1 8 9 3 983 2 1 8 8 3 984 1 2 8 6 3 985 1 1 1 8 6 3 986 3 8 4 3 987 1...

Page 429: ... 2 1001 1 1 11 9 2 1002 1 1 11 8 2 1003 1 1 11 6 2 1004 1 1 11 2 2 1005 2 11 2 2 1006 1 1 10 8 2 1007 1 1 10 7 2 1008 1 1 10 3 2 1009 1 1 10 1 2 1010 1 1 9 9 2 1011 1 1 9 9 2 1012 1 1 9 5 2 1013 1 1 9 3 2 1014 1 1 9 2 2 1015 1 1 9 1 2 1016 2 9 2 1017 1 1 8 8 2 1018 1 1 8 5 2 1019 1 1 8 4 2 1020 1 1 8 1 2 1021 1 1 7 8 2 ...

Page 430: ...1 22 6 8 5 5 2 1 22 5 8 6 6 2 22 2 8 7 6 1 1 22 4 8 8 6 1 1 21 8 8 9 7 1 21 7 8 10 6 2 21 4 8 11 7 1 21 1 8 12 7 1 20 7 8 13 8 20 8 14 3 1 3 23 3 7 15 1 4 1 1 23 1 7 16 1 3 3 22 9 7 17 5 1 1 23 1 7 18 5 1 1 22 8 7 19 2 4 1 22 9 7 20 2 2 2 1 22 8 7 21 2 1 4 22 6 7 22 2 3 2 23 7 23 5 2 22 7 7 24 4 2 1 22 8 7 25 3 2 1 1 22 6 7 26 3 3 1 22 5 7 27 3 1 1 2 22 7 7 28 1 5 1 22 7 7 29 5 1 1 22 5 7 30 1 4 2...

Page 431: ...1 1 1 21 7 60 4 3 20 8 7 61 2 5 21 7 62 5 1 1 20 8 7 63 3 3 1 20 7 7 64 5 2 20 9 7 65 4 1 2 20 4 7 66 4 2 1 20 6 7 67 5 1 1 20 3 7 68 3 4 20 3 7 69 6 1 20 1 7 70 4 2 1 20 7 71 5 1 1 19 9 7 72 5 2 19 7 7 73 4 3 19 6 7 74 5 1 1 19 3 7 75 6 1 19 2 7 76 5 2 18 9 7 77 6 1 18 6 7 78 6 1 18 2 7 79 7 17 5 7 80 2 1 1 2 23 6 81 1 2 1 1 1 23 1 6 82 1 5 23 5 6 83 4 2 23 6 84 3 2 1 22 7 6 85 2 2 1 1 22 9 6 86 ...

Page 432: ...1 22 3 6 114 2 3 1 22 3 6 115 2 3 1 22 7 6 116 3 1 1 1 22 4 6 117 1 4 1 22 4 6 118 2 1 1 1 1 22 4 6 119 2 3 1 22 2 6 120 1 3 2 22 4 6 121 5 1 22 2 6 122 4 1 1 22 2 6 123 5 1 22 4 6 124 1 3 2 22 3 6 125 2 2 1 1 22 1 6 126 1 1 2 1 1 22 2 6 127 1 4 1 22 6 128 4 1 1 22 2 6 129 1 2 2 1 22 4 6 130 1 2 3 22 3 6 131 2 1 1 2 22 6 132 1 3 1 1 22 1 6 133 1 1 4 22 5 6 134 3 2 1 22 3 6 135 2 1 2 1 22 1 6 136 3...

Page 433: ...3 1 2 21 6 6 167 4 1 1 21 2 6 168 1 2 2 1 21 2 6 169 4 1 1 21 3 6 170 1 3 1 1 21 4 6 171 3 2 1 21 1 6 172 1 1 2 2 21 3 6 173 1 4 1 21 1 6 174 1 2 3 21 5 6 175 3 1 1 1 21 3 6 176 2 1 1 1 1 21 1 6 177 2 3 1 20 9 6 178 3 2 1 21 6 179 5 1 21 1 6 180 2 1 3 21 2 6 181 3 2 1 21 6 182 2 4 20 8 6 183 4 2 21 2 6 184 2 3 1 21 6 185 4 1 1 20 7 6 186 3 2 1 21 6 187 1 3 1 1 20 8 6 188 3 1 1 1 20 7 6 189 1 1 3 1...

Page 434: ...9 9 6 219 5 1 19 6 6 220 2 3 1 19 7 6 221 2 1 2 1 19 6 6 222 2 4 19 4 6 223 4 1 1 19 6 6 224 5 1 19 6 6 225 2 2 2 19 8 6 226 3 1 1 1 19 4 6 227 3 1 2 19 5 6 228 1 3 2 19 3 6 229 1 4 1 19 5 6 230 4 1 1 19 3 6 231 2 2 1 1 19 2 6 232 2 1 3 19 6 233 6 19 2 6 234 3 2 1 19 6 235 3 2 1 18 9 6 236 3 1 2 19 1 6 237 5 1 18 9 6 238 1 4 1 18 9 6 239 4 1 1 18 7 6 240 2 2 2 18 6 6 241 2 3 1 18 8 6 242 3 1 1 1 1...

Page 435: ... 271 2 2 1 23 5 272 2 1 1 1 22 9 5 273 1 3 1 23 1 5 274 1 2 1 1 23 1 5 275 3 1 1 22 6 5 276 2 1 2 22 9 5 277 1 1 1 1 1 22 8 5 278 1 2 1 1 22 5 5 279 1 1 2 1 22 7 5 280 2 1 2 22 8 5 281 1 2 1 1 22 6 5 282 4 1 23 2 5 283 3 1 1 22 6 5 284 3 1 1 22 7 5 285 2 1 1 1 22 8 5 286 2 2 1 22 7 5 287 1 3 1 22 9 5 288 1 2 1 1 22 6 5 289 2 3 22 5 5 290 4 1 22 4 5 291 2 2 1 22 8 5 292 1 1 3 22 7 5 293 2 1 1 1 22 ...

Page 436: ... 320 1 2 1 1 22 4 5 321 1 2 1 1 21 9 5 322 2 1 1 1 21 8 5 323 1 1 1 2 22 1 5 324 1 2 2 22 2 5 325 1 2 1 1 22 5 326 1 1 1 1 1 22 1 5 327 1 2 1 1 21 9 5 328 1 3 1 22 2 5 329 1 1 3 22 5 330 1 2 1 1 21 9 5 331 1 1 2 1 22 1 5 332 3 1 1 21 9 5 333 2 1 1 1 22 1 5 334 2 1 1 1 21 7 5 335 2 2 1 22 5 336 1 3 1 22 2 5 337 3 1 1 21 7 5 338 3 2 21 7 5 339 3 1 1 21 8 5 340 2 1 2 22 5 341 1 1 1 1 1 21 8 5 342 2 2...

Page 437: ...5 370 2 1 1 1 21 3 5 371 1 1 1 1 1 21 4 5 372 3 1 1 21 2 5 373 1 1 1 2 21 2 5 374 3 2 21 5 375 1 3 1 21 5 5 376 1 2 1 1 21 1 5 377 1 3 1 21 3 5 378 1 1 2 1 20 9 5 379 1 2 1 1 21 5 380 1 2 1 1 21 1 5 381 1 1 2 1 21 2 5 382 1 1 3 21 5 383 3 1 1 21 5 384 3 1 1 21 1 5 385 2 1 1 1 20 8 5 386 1 2 1 1 21 5 387 4 1 20 8 5 388 1 2 2 21 1 5 389 2 2 1 21 2 5 390 3 1 1 20 7 5 391 2 1 2 21 5 392 2 1 1 1 20 8 5...

Page 438: ... 5 420 4 1 20 5 421 3 2 20 3 5 422 1 1 2 1 20 5 5 423 2 1 1 1 20 1 5 424 3 1 1 20 1 5 425 1 1 2 1 20 3 5 426 1 1 2 1 20 5 427 1 2 1 1 20 2 5 428 1 3 1 20 1 5 429 1 4 20 4 5 430 1 2 2 19 9 5 431 2 2 1 20 5 432 1 1 1 2 20 1 5 433 3 1 1 20 2 5 434 2 1 1 1 19 8 5 435 2 1 1 1 19 9 5 436 1 3 1 20 2 5 437 4 1 19 9 5 438 3 1 1 19 7 5 439 1 1 1 1 1 19 9 5 440 1 3 1 19 7 5 441 3 2 19 8 5 442 1 2 1 1 19 6 5 ...

Page 439: ...19 5 470 3 1 1 19 5 471 2 1 1 1 18 9 5 472 1 1 2 1 19 2 5 473 2 1 2 18 8 5 474 1 2 1 1 18 9 5 475 1 4 19 3 5 476 2 2 1 18 7 5 477 3 1 1 18 7 5 478 3 1 1 18 8 5 479 3 1 1 18 9 5 480 4 1 18 6 5 481 2 2 1 18 6 5 482 1 2 2 18 8 5 483 2 3 19 5 484 2 1 1 1 18 8 5 485 1 3 1 18 4 5 486 2 2 1 18 5 5 487 1 1 1 1 1 18 6 5 488 1 1 3 18 7 5 489 2 1 2 18 4 5 490 1 3 1 18 5 5 491 3 1 1 18 2 5 492 2 2 1 18 5 5 49...

Page 440: ... 17 6 5 520 3 1 1 17 4 5 521 4 1 17 1 5 522 1 3 1 17 2 5 523 1 1 2 1 17 1 5 524 1 4 16 9 5 525 1 2 2 17 3 5 526 3 1 1 17 1 5 527 2 1 1 1 16 9 5 528 2 1 2 17 5 529 3 2 16 8 5 530 4 1 17 5 531 3 1 1 16 8 5 532 1 1 3 16 5 5 533 1 2 1 1 16 7 5 534 2 2 1 16 5 5 535 2 2 1 16 4 5 536 2 1 2 16 6 5 537 4 1 16 4 5 538 4 1 16 4 5 539 3 1 1 16 2 5 540 1 2 2 16 1 5 541 1 3 1 16 3 5 542 2 3 15 8 5 543 2 1 1 1 1...

Page 441: ...2 7 4 571 1 1 1 1 22 7 4 572 1 1 1 1 22 8 4 573 1 3 22 8 4 574 2 1 1 22 3 4 575 2 1 1 22 8 4 576 1 1 1 1 22 5 4 577 1 1 2 22 5 4 578 3 1 22 6 4 579 2 2 22 6 4 580 3 1 22 4 4 581 2 1 1 22 3 4 582 2 2 22 4 4 583 1 1 1 1 22 5 4 584 1 2 1 22 4 4 585 2 1 1 22 1 4 586 1 2 1 22 4 4 587 1 1 2 22 1 4 588 1 1 1 1 22 2 4 589 1 1 1 1 22 1 4 590 1 3 22 4 4 591 1 1 1 1 21 9 4 592 1 1 1 1 22 2 4 593 1 1 1 1 21 9...

Page 442: ... 1 1 1 1 21 2 4 621 2 1 1 21 5 4 622 1 1 1 1 21 2 4 623 1 1 1 1 21 3 4 624 1 1 1 1 21 4 625 1 1 2 21 4 626 3 1 20 8 4 627 2 2 21 4 628 1 1 1 1 21 1 4 629 1 2 1 20 9 4 630 1 1 1 1 21 1 4 631 1 1 1 1 20 8 4 632 1 1 2 21 1 4 633 1 1 1 1 20 9 4 634 1 1 1 1 20 8 4 635 1 2 1 20 9 4 636 1 1 2 20 9 4 637 2 2 21 2 4 638 2 1 1 20 7 4 639 1 1 1 1 20 9 4 640 1 2 1 20 7 4 641 2 1 1 20 8 4 642 1 2 1 20 4 4 643 ...

Page 443: ... 670 1 1 2 20 2 4 671 1 2 1 20 4 672 1 2 1 19 8 4 673 2 1 1 19 9 4 674 1 1 1 1 19 8 4 675 3 1 19 6 4 676 1 2 1 19 8 4 677 1 1 1 1 19 6 4 678 2 1 1 19 9 4 679 1 1 1 1 19 3 4 680 1 1 2 19 6 4 681 2 1 1 19 4 4 682 2 1 1 19 5 4 683 1 1 1 1 19 6 4 684 2 1 1 19 4 4 685 1 2 1 19 6 4 686 3 1 19 7 4 687 1 3 19 5 4 688 2 1 1 19 4 4 689 1 1 1 1 19 2 4 690 2 1 1 19 2 4 691 2 2 19 2 4 692 1 1 2 19 5 4 693 1 1 ...

Page 444: ... 4 720 2 1 1 18 2 4 721 1 1 2 18 5 4 722 1 1 1 1 18 3 4 723 1 1 1 1 18 3 4 724 1 2 1 18 4 4 725 2 1 1 18 1 4 726 3 1 17 9 4 727 2 1 1 18 4 728 1 1 1 1 18 2 4 729 1 1 1 1 18 1 4 730 1 1 2 18 4 731 1 1 1 1 17 9 4 732 1 2 1 17 7 4 733 1 1 1 1 17 9 4 734 1 2 1 18 4 735 1 3 17 8 4 736 2 1 1 17 9 4 737 3 1 17 5 4 738 2 1 1 17 8 4 739 1 2 1 18 4 740 2 2 17 8 4 741 1 1 1 1 17 6 4 742 1 2 1 17 5 4 743 2 1 ...

Page 445: ...1 1 16 4 4 770 2 1 1 16 5 4 771 1 2 1 16 7 4 772 2 1 1 16 5 4 773 1 1 2 16 3 4 774 2 1 1 16 4 4 775 4 16 8 4 776 2 1 1 16 2 4 777 2 1 1 16 3 4 778 1 2 1 16 1 4 779 1 1 1 1 16 3 4 780 3 1 15 9 4 781 1 1 1 1 16 1 4 782 1 2 1 16 4 783 1 3 16 2 4 784 1 1 2 15 9 4 785 3 1 16 4 786 2 1 1 15 7 4 787 1 2 1 16 4 788 1 1 1 1 15 7 4 789 1 2 1 15 5 4 790 3 1 15 5 4 791 2 1 1 15 7 4 792 2 2 15 6 4 793 1 3 15 8...

Page 446: ...1 1 2 14 1 4 820 3 1 13 9 4 821 2 1 1 13 7 4 822 2 2 13 6 4 823 3 1 13 8 4 824 1 3 13 3 4 825 1 1 1 1 13 5 4 826 2 1 1 13 3 4 827 2 2 13 4 4 828 3 1 13 2 4 829 1 1 2 12 9 4 830 1 2 1 13 1 4 831 2 1 1 12 8 4 832 4 12 8 4 833 3 1 12 6 4 834 1 2 1 12 5 4 835 2 2 12 2 4 836 2 1 1 12 4 4 837 1 3 12 1 4 838 2 1 1 11 8 4 839 3 1 11 7 4 840 2 2 11 4 4 841 3 1 11 1 4 842 3 1 10 7 4 843 4 10 4 844 1 2 22 5 ...

Page 447: ...19 6 3 870 1 2 19 6 3 871 1 1 1 19 5 3 872 1 1 1 19 3 3 873 1 2 19 3 3 874 1 2 19 2 3 875 1 1 1 19 3 3 876 1 1 1 18 9 3 877 3 19 2 3 878 1 1 1 18 7 3 879 1 1 1 18 7 3 880 1 2 18 5 3 881 1 1 1 18 6 3 882 1 1 1 18 3 3 883 1 1 1 18 6 3 884 1 1 1 18 3 3 885 2 1 18 4 3 886 1 2 18 4 3 887 2 1 18 2 3 888 1 1 1 18 3 889 1 1 1 17 8 3 890 1 2 17 8 3 891 1 1 1 17 6 3 892 1 2 17 9 3 893 1 1 1 17 6 3 894 1 1 1...

Page 448: ...5 8 3 920 1 1 1 15 8 3 921 1 1 1 15 6 3 922 1 1 1 15 7 3 923 1 1 1 15 4 3 924 1 1 1 15 4 3 925 2 1 15 5 3 926 3 15 3 3 927 2 1 15 2 3 928 2 1 15 3 929 1 2 15 3 3 930 1 1 1 15 1 3 931 1 1 1 14 9 3 932 1 1 1 14 8 3 933 1 1 1 14 7 3 934 1 1 1 14 7 3 935 1 1 1 14 7 3 936 2 1 14 8 3 937 2 1 14 4 3 938 1 1 1 14 5 3 939 2 1 14 3 3 940 1 2 14 4 3 941 1 1 1 14 1 3 942 1 1 1 14 2 3 943 1 1 1 14 3 944 1 1 1 ...

Page 449: ... 1 2 12 3 969 1 1 1 11 8 3 970 2 1 11 5 3 971 1 2 11 6 3 972 2 1 11 4 3 973 2 1 11 4 3 974 1 1 1 11 2 3 975 3 10 8 3 976 1 1 1 11 3 977 1 1 1 10 8 3 978 1 2 10 9 3 979 2 1 10 6 3 980 1 2 10 4 3 981 1 1 1 10 3 3 982 2 1 10 1 3 983 2 1 10 3 984 1 2 9 7 3 985 1 1 1 9 9 3 986 3 9 6 3 987 1 1 1 9 3 3 988 2 1 9 2 3 989 1 2 8 9 3 990 2 20 2 991 1 1 18 2 992 1 1 17 1 2 993 1 1 16 4 2 994 2 16 2 995 1 1 15...

Page 450: ...5 2 1005 2 12 8 2 1006 1 1 12 2 2 1007 1 1 12 2 2 1008 1 1 11 6 2 1009 1 1 11 5 2 1010 1 1 11 3 2 1011 1 1 11 2 2 1012 1 1 10 7 2 1013 1 1 10 5 2 1014 1 1 10 6 2 1015 1 1 10 3 2 1016 2 10 2 2 1017 1 1 10 2 1018 1 1 9 6 2 1019 1 1 9 6 2 1020 1 1 9 3 2 1021 1 1 8 9 2 ...

Page 451: ...5S S 45KA1E5 S 45KA1E5S 19 18 16 10 13 14 22 21 17 15 12 20 42 33 25 26 29 28 34 27 30 23 41 40 37 38 36 7 1 24 43 39 2 3 4 48 5 9 8 50 45 46 I I 47 O I O I CWH55025J CWH55051AJ 44 31 49 Note The above exploded view is for the purpose of parts disassembly and replacement The non numbered parts are not kept as standard service parts ...

Page 452: ... GRILLE COMPLETE 1 CWE20C3084 CWE20C3083 24 BACK COVER CHASSIS 1 CWD933019 CWD933019A 25 FULCRUM 1 CWH621102 CWH621102 26 VERTICAL VANE 11 CWE241287 CWE241287 27 CONNECTING BAR 1 CWE261152 CWE261152 28 CONNECTING BAR 1 CWE261153 CWE261153 29 CONNECTING BAR 1 CWE261154 CWE261154 30 CONNECTING BAR 1 CWE261155 CWE261155 31 AIR SWING MOTOR 1 CWA981240 CWA981240 O 33 CAP DRAIN TRAY 1 CWH521096 CWH52109...

Page 453: ...GRILLE COMPLETE 1 CWE20C3084 CWE20C3083 24 BACK COVER CHASSIS 1 CWD933019 CWD933019A 25 FULCRUM 1 CWH621102 CWH621102 26 VERTICAL VANE 11 CWE241287 CWE241287 27 CONNECTING BAR 1 CWE261152 CWE261152 28 CONNECTING BAR 1 CWE261153 CWE261153 29 CONNECTING BAR 1 CWE261154 CWE261154 30 CONNECTING BAR 1 CWE261155 CWE261155 31 AIR SWING MOTOR 1 CWA981240 CWA981240 O 33 CAP DRAIN TRAY 1 CWH521096 CWH521096...

Page 454: ...GRILLE COMPLETE 1 CWE20C3084 CWE20C3083 24 BACK COVER CHASSIS 1 CWD933019 CWD933019A 25 FULCRUM 1 CWH621102 CWH621102 26 VERTICAL VANE 11 CWE241287 CWE241287 27 CONNECTING BAR 1 CWE261152 CWE261152 28 CONNECTING BAR 1 CWE261153 CWE261153 29 CONNECTING BAR 1 CWE261154 CWE261154 30 CONNECTING BAR 1 CWE261155 CWE261155 31 AIR SWING MOTOR 1 CWA981240 CWA981240 O 33 CAP DRAIN TRAY 1 CWH521096 CWH521096...

Page 455: ...GRILLE COMPLETE 1 CWE20C3084 CWE20C3083 24 BACK COVER CHASSIS 1 CWD933019 CWD933019A 25 FULCRUM 1 CWH621102 CWH621102 26 VERTICAL VANE 11 CWE241287 CWE241287 27 CONNECTING BAR 1 CWE261152 CWE261152 28 CONNECTING BAR 1 CWE261153 CWE261153 29 CONNECTING BAR 1 CWE261154 CWE261154 30 CONNECTING BAR 1 CWE261155 CWE261155 31 AIR SWING MOTOR 1 CWA981240 CWA981240 O 33 CAP DRAIN TRAY 1 CWH521096 CWH521096...

Page 456: ... 8 9 50 3 5 4 49 16 26 28 21 22 17 25 24 30 31 27 29 42 32 23 33 34 36 37 38 41 40 CWH55025J CWH55051AJ 44 45 46 I I 47 O I O I 48 Note The above exploded view is for the purpose of parts disassembly and replacement The non numbered parts are not kept as standard service parts ...

Page 457: ...FRONT COVER 1 CWH13C1212 CWH13C1212 CWH13C1212 23 DISCHARGE GRILLE COMPLETE 1 CWE20C3008 CWE20C3008 CWE20C3008 24 BACK COVER CHASSIS 1 CWD933031 CWD933031 CWD933031 25 FULCRUM 2 CWH621103 CWH621103 CWH621103 26 VERTICAL VANE 15 CWE241289 CWE241289 CWE241289 27 CONNECTING BAR 1 CWE261156 CWE261156 CWE261156 28 CONNECTING BAR 1 CWE261158 CWE261158 CWE261158 29 CONNECTING BAR 1 CWE261167 CWE261167 CW...

Page 458: ...OIL COMPLETE 1 CWA43C2371 CWA43C2371 CWA43C2371 50 DRAIN PAN 1 CWH401062 CWH401062 CWH401062 Note All parts are supplied from PHAAM Malaysia Vendor Code 00029488 O marked parts are recommended to be kept in stock ...

Page 459: ... 1 3 S 22YA1E5 S 28YA1E5 S 36YA1E5 S 45YA1E5 S 56YA1E5 42 20 Note The above exploded view is for the purpose of parts disassembly and replacement The non numbered parts are not kept as standard service parts ...

Page 460: ...460 Note The above exploded view is for the purpose of parts disassembly and replacement The non numbered parts are not kept as standard service parts ...

Page 461: ...EVAPORATOR SUPPORTER 3 CWD911529A CWD911529A CWD911529A 26 DRAIN PUMP COMPLETE 1 CWB53C1038 CWB53C1038 CWB53C1038 27 PANEL DRAIN PUMP ASS Y 1 CWD93K1021 CWD93K1021 CWD93K1021 28 DRAIN PUMP 1 CWB532093 CWB532093 CWB532093 29 ANTI VIBRATION BUSHING 3 CWH501080 CWH501080 CWH501080 30 FLOAT SWITCH DRAIN PUMP 1 CWA121285 CWA121285 CWA121285 31 FLEXIBLE PIPE 1 CWH85C1033 CWH85C1033 CWH85C1033 32 DRAIN N...

Page 462: ...24 EVAPORATOR SUPPORTER 3 CWD911529A CWD911529A 26 DRAIN PUMP COMPLETE 1 CWB53C1038 CWB53C1038 27 PANEL DRAIN PUMP ASS Y 1 CWD93K1021 CWD93K1021 28 DRAIN PUMP 1 CWB532093 CWB532093 29 ANTI VIBRATION BUSHING 3 CWH501080 CWH501080 30 FLOAT SWITCH DRAIN PUMP 1 CWA121285 CWA121285 31 FLEXIBLE PIPE 1 CWH85C1033 CWH85C1033 32 DRAIN NOZZLE 1 CWH411011 CWH411011 33 DRAIN HOSE HEAT INSULATION 1 CWG321050 C...

Page 463: ...463 Note The above exploded view is for the purpose of parts disassembly and replacement The non numbered parts are not kept as standard service parts ...

Page 464: ...H081007 10 BEARING 6 CWH641008 12 PLATE COVER FOR A S MOTOR 1 CWD911459 13 PLATE COVER FOR CONNECTING SHAFT 2 CWD911460 14 PLATE COVER FOR END SHAFT 1 CWD911461 21 ELECTRONIC CONT RECEIVER INDICATOR 1 CWA744545 22 LEAD WIRE COMPLETE 1 CWA67C8578 24 INTAKE GRILLE 1 CWE221131 28 LEVER ARM 2 CWH651029 29 AIR FILTER 1 CWD001142 Note All parts are supplied from PHAAM Malaysia Vendor Code 00029488 O mar...

Page 465: ...465 24 1 4 S 63UA1E5 S 71UA1E5 S 90UA1E5 Note The above exploded view is for the purpose of parts disassembly and replacement The non numbered parts are not kept as standard service parts ...

Page 466: ...466 Note The above exploded view is for the purpose of parts disassembly and replacement The non numbered parts are not kept as standard service parts ...

Page 467: ...COMPLETE 1 B53C1023 B53C1023 B53C1023 27 PANEL DRAIN PUMP ASS Y 1 D93K1016 D93K1016 D93K1016 28 DRAIN PUMP 1 B532065 B532065 B532065 29 ANTI VIBRATION BUSHING 3 H501097 H501097 H501097 30 FLOAT SWITCH DRAIN PUMP 1 A121245 A121245 A121245 31 FLEXIBLE PIPE 1 CWH851156 CWH851156 CWH851156 32 DRAIN NOZZLE 1 H411013 H411013 H411013 33 DRAIN HOSE HEAT INSULATION 1 G101284 G101284 G101284 35 DRAIN PAN CO...

Page 468: ...MPLETE 1 A43C2388 A43C2388 A43C2388 100 CORD HOLDER 1 D741022 D741022 D741022 55 OPERATING INSTRUCTION 1 F567158 F567158 F567158 56 OPERATING INSTRUCTION 1 F567159 F567159 F567159 57 INSTALLATION INSTRUCTION 1 F614112 F614112 F614112 Note All parts are supplied from PHAAG China O marked parts are recommended to be kept in stock ...

Page 469: ...A1E5 1 1 1 2 2 3 1 23 25 24 26 28 30 9 2 33 8 11 15 14 12 13 16 10 18 21 20 19 7 22 34 35 36 37 32 31 17 16 5 3 4 6 29 27 Note The above exploded view is for the purpose of parts disassembly and replacement The non numbered parts are not kept as standard service parts ...

Page 470: ... O 18 DRAIN PAN COMPLETE 1 CWH40C1063 CWH40C1063 CWH40C1063 19 BOTTOM PLATE DRAIN SIDE 1 CWE051025 CWE051025 CWE051025 20 BOTTOM PLATE MIDDLE 1 CWE051026 CWE051026 CWE051026 21 BOTTOM PLATE FAN SIDE 1 CWE051011 CWE051011 CWE051011 22 FLANGE COMPLETE 1 CWD60K1009 CWD60K1009 CWD60K1009 23 C BOX COMPLETE 1 CWH14C7300 CWH14C7301 CWH14C7302 24 CONTROL BOARD CASING 1 CWH10K1097 CWH10K1097 CWH10K1097 25 ...

Page 471: ... O 18 DRAIN PAN COMPLETE 1 CWH40C1063 CWH40C1063 CWH40C1063 19 BOTTOM PLATE DRAIN SIDE 1 CWE051025 CWE051025 CWE051025 20 BOTTOM PLATE MIDDLE 1 CWE051026 CWE051026 CWE051026 21 BOTTOM PLATE FAN SIDE 1 CWE051011 CWE051011 CWE051011 22 FLANGE COMPLETE 1 CWD60K1009 CWD60K1009 CWD60K1009 23 C BOX COMPLETE 1 CWH14C7303 CWH14C7304 CWH14C7305 24 CONTROL BOARD CASING 1 CWH10K1097 CWH10K1097 CWH10K1097 25 ...

Page 472: ...0MA1E5 5 24 25 26 6 9 16 14 34 15 35 12 23 10 22 21 20 33 36 18 11 19 13 7 8 4 27 28 32 2 3 1 31 30 29 17 37 Note The above exploded view is for the purpose of parts disassembly and replacement The non numbered parts are not kept as standard service parts ...

Page 473: ...VER RELAY BOX P06 T05830 1 1 18 HEADER PIPE ASSY P45 T07850 1 1 19 MULTIBENT TUBE P05 T14780 1 1 20 MAINFOLD TUBE ASSY P45 T09110 1 1 21 STRAINER B111033 1 1 22 SILENCER B121017 1 1 23 L SHAPED TUBE P05 T14770 1 1 24 EXPANSION VALVE COIL P05 T15110 1 1 25 EXPANSION VALVE P05 T14970 1 1 26 L SHAPED TUBE P05 T14760 1 1 27 RELAY BOX ASSY CMPT P46 T08090 1 P46 T08120 1 28 PCB BOARD PROGRAM A73C4608 1 ...

Page 474: ... RELAY BOX P06 T05830 1 1 1 18 HEADER PIPE ASSY P45 T09390 1 P45 T08820 1 1 19 MULTIBENT TUBE P05 T15240 1 P05 T14320 1 1 20 MAINFOLD TUBE ASSY P45 T08840 1 1 1 21 STRAINER B111033 1 1 1 22 SILENCER B121017 1 1 1 23 L SHAPED TUBE P05 T15260 1 1 1 24 EXPANSION VALVE COIL P05 T15110 1 1 1 25 EXPANSION VALVE P05 T14960 1 1 1 26 L SHAPED TUBE P05 T15250 1 1 1 27 RELAY BOX ASSY CMPT P46 T08070 1 P46 T0...

Page 475: ...10 7 12 13 36 34 27 26 28 15 16 23 31 32 33 30 29 24 69 6 4 4 3 2 55 56 19 5 18 17 20 21 22 14 34 32 8 36 37 34 25 34 11 57 33 Note The above exploded view is for the purpose of parts disassembly and replacement The non numbered parts are not kept as standard service parts ...

Page 476: ...476 49 48 47 43 45 44 42 41 46 38 39 40 54 Note The above exploded view is for the purpose of parts disassembly and replacement The non numbered parts are not kept as standard service parts ...

Page 477: ...4 64 63 61 59 58 53 67 50 63 51 1 52 9 59 61 60 60 71 70 63 65 62 Note The above exploded view is for the purpose of parts disassembly and replacement The non numbered parts are not kept as standard service parts ...

Page 478: ... 1 CWB021389 CWB021389 CWB021389 23 V COIL COMPLETE 1 CWA43C2296 CWA43C2296 CWA43C2296 24 RECEIVER 1 CWB141035 CWB141035 CWB141035 25 TUBE ASS Y 1 CWT025274 CWT026846 CWT026846 26 2 WAYS VALVE 1 CWB021389 CWB021389 CWB021389 27 V COIL COMPLETE 1 CWA43C2268 CWA43C2268 CWA43C2268 28 DISCHARGE MUFFLER 1 CWB121024 CWB121024 CWB121024 29 TUBE ASS Y 1 CWT026848 CWT026847 CWT026847 30 EXPANTION VALVE 1 C...

Page 479: ...IUM DC 2 CWEHDS83AAC CWEHDS83AAC CWEHDS83AAC 60 FAN ASSY 2 CWH03K1041 CWH03K1041 CWH03K1041 61 NUT 2 CWH561051 CWH561051 CWH561051 62 CABINET FRONT PLATE 1 CWE061135A CWE061135A CWE061135A 63 HANDLE 3 CWE161008 CWE161008 CWE161008 64 DISCHARGE GRILLE 2 CWE201088 CWE201088 CWE201088 65 CABINET SIDE PLATE 1 CWE041235A CWE041235A CWE041235A 66 WIRE NET RESIN NET 1 CWD041107A CWD041107A CWD041107A 67 ...

Page 480: ...1 CWA43C2296 CWA43C2296 CWA43C2296 24 RECEIVER 1 CWB141035 CWB141035 CWB141035 25 TUBE ASS Y 1 CWT025274 CWT026846 CWT026846 26 2 WAYS VALVE 1 CWB021389 CWB021389 CWB021389 27 V COIL COMPLETE 1 CWA43C2268 CWA43C2268 CWA43C2268 28 DISCHARGE MUFFLER 1 CWB121024 CWB121024 CWB121024 29 TUBE ASS Y 1 CWT026848 CWT026847 CWT026847 30 EXPANTION VALVE 1 CWB051020J CWB051020J CWB051020J 31 V COIL COMPLETE 1...

Page 481: ...3AAC CWEHDS83AAC CWEHDS83AAC 60 FAN ASSY 2 CWH03K1041 CWH03K1041 CWH03K1041 61 NUT 2 CWH561051 CWH561051 CWH561051 62 CABINET FRONT PLATE 1 CWE061135A CWE061135A CWE061135A 63 HANDLE 3 CWE161008 CWE161008 CWE161008 64 DISCHARGE GRILLE 2 CWE201088 CWE201088 CWE201088 65 CABINET SIDE PLATE 1 CWE041235A CWE041235A CWE041235A 66 WIRE NET RESIN NET 1 CWD041107A CWD041107A CWD041107A 67 WIRE NET RESIN N...