1-111
1
Single -Type
1-1. Unit Specifi cations
PE1
5. Ducted Type S-71PN1E5A / U-71PE1E5A
INDOOR
MODEL
S-71PN1E5A
OUTDOOR
MODEL
U-71PE1E5A
Branch pipe
MODEL
-
PERFORMANCE TEST CONDITION
ISO13253 / EN14511 / EN14825 / EN12102
POWER SUPPLY
ø, Hz
1ø 50Hz
1ø 50Hz
V
220
230
240
220
230
240
Min
Max
C
O
O
L
I
N
G
CAPACITY
kW
7.1
7.1
7.1
2.5
8.0
BTU/h
24200
24200
24200
8500
27300
CURRENT
A
1.12
1.08
1.04
9.70
9.40
9.20
-
-
INPUT POWER
W
140
140
140
2.010k
2.010k
2.010k
-
-
TOTAL W
-
2.150k
2.150k
2.150k
550
2.750k
ANNUAL CONSUMPTION TOTAL kWh
*
4
-
-
1075
-
-
-
EER/EER CLASS
TOTAL(W/W)
*
5/("A"~"G")
-
-
-
3.30
3.30 / A
3.30
4.55
2.91
Erp
*
6
Pdsign
kW
-
-
-
-
7.1
-
SEER
(W/W)
-
-
-
-
5.5
-
Annual consumption
kWh
-
-
-
-
448
-
Class
-
-
-
-
A
-
POWER FACTOR
%
-
-
-
94
93
91
-
-
NOISE INDOOR
(H/M/L)
dB-A
43/41/36
Power Level dB
60/58/53
NOISE OUTDOOR
(H/L)
dB-A
48/-
Power Level dB
65/-
H
E
A
T
I
N
G
CAPACITY
kW
8.0
8.0
8.0
2.0
9.0
BTU/h
27300
27300
27300
6800
30700
CURRENT
A
1.12
1.08
1.04
10.2
9.90
9.70
-
-
INPUT POWER
W
140
140
140
2.120k
2.120k
2.120k
-
-
TOTAL W
-
2.260k
2.260k
2.260k
500
2.920k
COP/COP CLASS
TOTAL(W/W)
*
5/("A"~"G")
-
-
-
3.54
3.54 / B
3.54
4.00
3.08
Erp
*
6
Pdsign
kW
-
-
-
-
6.2
-
Tbivalen
°C
-
-
-
-
-9
-
SCOP
(W/W)
-
-
-
-
3.8
-
Annual consumption
kWh
-
-
-
-
2284
-
Class
-
-
-
-
A
-
POWER FACTOR
%
-
-
-
94
93
91
-
-
NOISE INDOOR
(H/M/L)
dB-A
43/41/36
-
⁄
⁄
Power Level dB
60/58/53
-
NOISE OUTDOOR
(H/L)
dB-A
-
50/-
⁄
⁄
Power Level dB
-
67/-
EXTRA LOW TEMP Total CAPACITY(kW)/INPUT POWER(W)/COP
-
MAX CURRENT(A)/MAX INPUT POWER(W)
1.28/160
1.24/160
1.20/160
18.0/3.800k
18.0/3.930k
18.0/4.060k
⁄
STARTING CURRENT(A)/COMP OUTPUT(W)
-
-
-
10.2/2.0k
9.9/2.0k
9.7/2.0k
⁄
NETWORK IMPEDANCE (ΩMAX.)
-
-
FM OUTPUT (W)
120
90
⁄
MOISTURE REMOVAL VOLUME
L/h(Pt/h)
4.2
(8.8)
-
External static pressure
Pa
50 (MIN10 - MAX80)
I/D AIR
FLOW
COOL
m
3
/min (ft
3
/min)
22/20/16 (777/706/565)
HEAT
m
3
/min (ft
3
/min)
22/20/16 (777/706/565)
O/D AIR
FLOW
COOL
m
3
/min (ft
3
/min)
60
(2119)
HEAT
m
3
/min (ft
3
/min)
60
(2119)
REFRIGERANT TYPE, AMOUNT
g
(oz)
R410A 2.35k
(82.9)
/
P
R
O
D
I
M
HEIGHT : H mm(inch)
250 (9-27/32)
996 (39-7/32)
/
WIDTH : W mm(inch)
1000 (+100) (39-5/16) (+3-15/16)
940 (37-1/32)
/
DEPTH : D mm(inch)
650 (25-19/32)
340 (13-13/32)
/
P
A
C
D
I
M
HEIGHT : H mm
338
1136
/
WIDTH : W mm
1211
1055
/
DEPTH : D mm
761
485
/
MASS
(NET) k
g
(lb)
32 (71)
69 (152)
/
(GROSS) k
g
(lb)
38 (84)
77 (170)
/
LAYERS LIMIT (actually)
6 (7)
2 (3)
Operation
Condition
Cool O.D(DBT)
18°C ~ 32°C
-15°C ~ 46°C
Heat O.D(DBT)
16°C ~ 30°C
-20°C ~ 24°C
P
I
P
I
N
G
PIPE DIAMETER mm (inch)
(Liquid)ø9.52(3/8) (Gas)ø15.88(5/8)
(Liquid)ø9.52(3/8) (Gas)ø15.88(5/8)
CONNECT METHOD, STD LENGTH m (ft)
fl ared type, 5.0(16.4)
fl ared type, 5.0(16.4)
PIPE LENGTH RANGE m (ft)
5 ~ 50
(16.4 ~ 164.0)
~
~
I/D&O/D HEIGHT DIFFERENCE m (ft)
15 (OD located lower) / 30 (OD located higher)
(49.2/98.4)
ADD GAS AMOUNT
g
/m (oz/ft)
50
(0.538)
PIPE LENGTH FOR ADDITIONAL GAS m (ft)
30
(98.4)
*1
:
In case it is necessary to indicate the air fl ow volume in (l/s), the value in (m
3
/min.) shall be multiplied by 16.7 and rounded down the decimal point.
*2
:
If the EUROVENT Certifi ed models can be operated under the “extra-low” temperature condition, -7°C dry bulb and -8°C wet-bulb temperatures with rated voltage
230 V shall be used.
*3
:
Network Impedance shall be applicable for EUROPE and CHINA models.
*4
:
The annual consumption is calculated by multiplying the input power at 230 V (400 V) by an average of 500 hours per year in cooling mode.
*5
:
EER and COP classification is at 230 V (400 V) only in accordance with EU directive 2002/31/EC.
*6
:
SEER and SCOP classification is at 230V(400V) only in accordance with EN-14825. For heating, SCOP indicates the value of only Average heating season,
Other fiche data indicates in an attached sheet.