7-7
7
Item
code
Item
Setting data
No.
Description
No.
Description
Type
0001
4-Way Cassette (U1)
4-Way Cassette 60 x 60 (Y2)
0006
Low Silhouette Ducted (F1)
Ducted (N1)
Ceiling (T2)
0008
Indoor unit
capacity
0005
0007
0007
0009
0012
0017
0021
45 (Type 45)
56 (Type 50)
80 (Type 71)
140 (Type 125)
224 (Type 200)
0005
0011
0015
0018
0023
High Static Pressure Ducted (E1)
Wall mounted (K1)
36 (Type 36)
71 (Type 60)
112 (Type 100)
160 (Type 140)
280 (Type 250)
System
address
0001
0002
0003
Unit No. 1
Unit No. 2
Unit No. 3
0030
0099
Indoor unit
address
0001
0002
0003
Unit No. 30
Not set
Unit No. 1
Unit No. 2
Unit No. 3
0064
0099
Group control
address
0000
0001
0002
0099
Unit No. 64
Not set
Individual (1:1 = Indoor unit with no group wiring)
Main unit (One of the group-control indoor units)
Sub unit (All group-control indoor units except for main unit)
Not set
Cooling intake
temperature
shift
–010 Shifts intake temperature 10°C down.
–009 Shifts intake temperature 9°C down.
–001 Shifts intake temperature 1°C down.
0000
0001
No intake temperature shift
Shifts intake temperature 1°C up.
0009
0010
Shifts intake temperature 9°C up.
Shifts intake temperature 10°C up.
Automatic
stop time after
operation start
0000
0001
0002
Function disabled
Stops automatically 5 minutes after operation starts.
Stops automatically 10 minutes after operation starts.
Can be set
in 5-minute
units.
*
0123
0124
0125
Stops automatically 615 minutes after operation starts.
Stops automatically 620 minutes after operation starts.
Stops automatically 625 minutes after operation starts.
7-4. List of Detailed Setting Items