1-144
1
Simultaneous (Twin) -Type
1-1. Unit Specifi cations
PEY1
1. 4-Way Cassette Type S-60PU1E5A×2 / U-125PEY1E5
INDOOR
MODEL
S-60PU1E5A×2
PANEL
MODEL
CZ-KPU21×2
OUTDOOR
MODEL
U-125PEY1E5
Branch pipe
MODEL
CZ-P155BK1
PERFORMANCE TEST CONDITION
ISO5151 / EN14511 / EN12102
POWER SUPPLY
ø, Hz
1ø 50Hz
1ø 50Hz
V
220
230
240
220
230
240
Min
Max
C
O
O
L
I
N
G
CAPACITY
kW
12.5
12.5
12.5
3.8
13.5
BTU/h
42700
42700
42700
13000
46100
CURRENT
A
0.32×2
0.31×2
0.30×2
19.4
18.5
17.7
-
-
INPUT POWER
W
35×2
35×2
35×2
3.950k
3.950k
3.950k
-
-
TOTAL W
-
4.020k
4.020k
4.020k
900
5.000k
ANNUAL CONSUMPTION TOTAL kWh
*
4
-
-
2010
-
-
-
EER/EER CLASS
TOTAL(W/W)
*
5/("A"~"G")
-
-
-
3.11
3.11 / B
3.11
4.22
2.70
Erp
*
6
Pdsign
kW
-
-
-
-
-
-
SEER
(W/W)
-
-
-
-
-
-
Annual consumption
kWh
-
-
-
-
-
-
Class
-
-
-
-
-
-
POWER FACTOR
%
-
-
-
93
93
93
-
-
NOISE INDOOR
(H/M/L)
dB-A
36/31/28
-
Power Level dB
53/48/45
-
NOISE OUTDOOR
(H/L)
dB-A
56/-
Power Level dB
73/-
H
E
A
T
I
N
G
CAPACITY
kW
12.5
12.5
12.5
3.4
15.0
BTU/h
42700
42700
42700
11600
51200
CURRENT
A
0.30×2
0.30×2
0.29×2
15.6
14.9
14.3
-
-
INPUT POWER
W
35×2
35×2
35×2
3.220k
3.220k
3.220k
-
-
TOTAL W
-
3.290k
3.290k
3.290k
730
4.400k
COP/COP CLASS
TOTAL(W/W)
*
5/("A"~"G")
-
-
-
3.80
3.80 / A
3.80
4.66
3.41
Erp
*
6
Pdsign
kW
-
-
-
-
-
-
Tbivalen
°C
-
-
-
-
-
-
SCOP
(W/W)
-
-
-
-
-
-
Annual consumption
kWh
-
-
-
-
-
-
Class
-
-
-
-
-
-
POWER FACTOR
%
-
-
-
94
94
94
-
-
NOISE INDOOR
(H/M/L)
dB-A
36/31/28
-
⁄
⁄
Power Level dB
53/48/45
-
NOISE OUTDOOR
(H/L)
dB-A
-
56/-
⁄
⁄
Power Level dB
-
73/-
EXTRA LOW TEMP Total CAPACITY(kW)/INPUT POWER(W)/COP
-
MAX CURRENT(A)/MAX INPUT POWER(W)
0.32×2/35×2 0.31×2/35×2 0.30×2/35×2 29.0/6.000k
29.0/6.300k
29.0/6.600k
⁄
STARTING CURRENT(A)/COMP OUTPUT(W)
-
-
-
19.4/3.0k
18.5/3.0k
17.7/3.0k
⁄
NETWORK IMPEDANCE (ΩMAX.)
-
-
FM OUTPUT (W)
60×2
90
⁄
MOISTURE REMOVAL VOLUME
L/h(Pt/h)
7.9
(3.95×2)
(16.6)
-
External static pressure
Pa
-
I/D AIR
FLOW
COOL
m
3
/min (ft
3
/min)
[21/17/14 (742/600/494)]×2
HEAT
m
3
/min (ft
3
/min)
[21/17/14 (742/600/494)]×2
O/D AIR
FLOW
COOL
m
3
/min (ft
3
/min)
80
(2825)
HEAT
m
3
/min (ft
3
/min)
73
(2578)
REFRIGERANT TYPE, AMOUNT
g
(oz)
R410A 3.20k
(112.9)
/
P
R
O
D
I
M
HEIGHT : H mm(inch)
256 (10-3/32)
996 (39-7/32)
/
WIDTH : W mm(inch)
840 (33-3/32)
940 (37-1/32)
/
DEPTH : D mm(inch)
840 (33-3/32)
340 (13-13/32)
/
P
A
C
D
I
M
HEIGHT : H mm
298
1136
/
WIDTH : W mm
929
1055
/
DEPTH : D mm
929
485
/
MASS
(NET) k
g
(lb)
24 (53)
85 (187)
/
(GROSS) k
g
(lb)
30 (67)
93 (205)
/
LAYERS LIMIT (actually)
11 (12)
2 (3)
Operation
Condition
Cool O.D(DBT)
18°C ~ 32°C
-10°C ~ 43°C
Heat O.D(DBT)
16°C ~ 30°C
-15°C ~ 24°C
P
I
P
I
N
G
PIPE DIAMETER mm (inch)
(Liquid)ø9.52(3/8) (Gas)ø15.88(5/8)
(Liquid)ø9.52(3/8) (Gas)ø15.88(5/8)
CONNECT METHOD, STD LENGTH m (ft)
fl ared type, 5.0(16.4)
fl ared type, 5.0(16.4)
PIPE LENGTH RANGE m (ft)
5 ~ 50
(16.4 ~ 164.0)
~
~
I/D&O/D HEIGHT DIFFERENCE m (ft)
15 (OD located lower) / 30 (OD located higher)
(49.2/98.4)
ADD GAS AMOUNT
g
/m (oz/ft)
50
(0.538)
PIPE LENGTH FOR ADDITIONAL GAS m (ft)
30
(98.4)
*1
:
In case it is necessary to indicate the air fl ow volume in (l/s), the value in (m
3
/min.) shall be multiplied by 16.7 and rounded down the decimal point.
*2
:
If the EUROVENT Certifi ed models can be operated under the “extra-low” temperature condition, -7°C dry bulb and -8°C wet-bulb temperatures with rated voltage
230 V shall be used.
*3
:
Network Impedance shall be applicable for EUROPE and CHINA models.
*4
:
The annual consumption is calculated by multiplying the input power at 230 V (400 V) by an average of 500 hours per year in cooling mode.
*5
:
EER and COP classification is at 230 V (400 V) only in accordance with EU directive 2002/31/EC.
*6
:
SEER and SCOP classification is at 230V(400V) only in accordance with EN-14825. For heating, SCOP indicates the value of only Average heating season,
Other fiche data indicates in an attached sheet.