5-40
5
H05 Sensor Failure, Compressor Discharge Temperature Sensor (TD) Disconnected
Error Detection Method
(In case of outdoor temperature over 5°C) For 10 minutes since started, variation of discharge temperature is always
detected within 2°C comparing with the temperature just before starting.
1.
•
(In case of outdoor temperature less than 5°C) For 30 minutes since started, variation of discharge temperature is
always detected within 2°C comparing with the temperature just before starting.
•
1-1
1-2
Reinstall correctly.
Yes
No
1 Sensor
Trouble
Replace the sensor with a new one.
1-2
Is the sensor properly installed at the holder side?
SM830231-02̲Single̲欧州.indb 40
SM830231-02̲Single̲欧州.indb 40
2014/09/11 15:44:13
2014/09/11 15:44:13