1-154
1
Simultaneous (Twin) -Type
1-1. Unit Specifi cations
PEY1
2. Ceiling Type S-36PT2E5A×2 / U-71PEY1E5
INDOOR
MODEL
S-36PT2E5A×2
PANEL
MODEL
OUTDOOR
MODEL
U-71PEY1E5
Branch pipe
MODEL
CZ-P155BK1
PERFORMANCE TEST CONDITION
ISO5151 / EN14511 / EN14825 / EN12102
POWER SUPPLY
ø, Hz
1ø 50Hz
1ø 50Hz
V
220
230
240
220
230
240
Min
Max
C
O
O
L
I
N
G
CAPACITY
kW
7.1
7.1
7.1
2.0
7.7
BTU/h
24200
24200
24200
6800
26300
CURRENT
A
0.37×2
0.36×2
0.35×2
10.8
10.3
9.85
-
-
INPUT POWER
W
35×2
35×2
35×2
2.155k
2.155k
2.155k
-
-
TOTAL W
-
2.225k
2.225k
2.225k
325
2.820k
ANNUAL CONSUMPTION TOTAL kWh
*
4
-
-
1113
-
-
-
EER/EER CLASS
TOTAL(W/W)
*
5/("A"~"G")
-
-
-
3.19
3.19 / B
3.19
6.15
2.73
Erp
*
6
Pdsign
kW
-
-
-
-
7.1
-
SEER
(W/W)
-
-
-
-
6.1
-
Annual consumption
kWh
-
-
-
-
408
-
Class
-
-
-
-
A++
-
POWER FACTOR
%
-
-
-
91
91
91
-
-
NOISE INDOOR
(H/M/L)
dB-A
36/32/29
-
Power Level dB
54/50/47
-
NOISE OUTDOOR
(H/L)
dB-A
50/-
Power Level dB
70/-
H
E
A
T
I
N
G
CAPACITY
kW
7.1
7.1
7.1
1.8
8.1
BTU/h
24200
24200
24200
6100
27600
CURRENT
A
0.37×2
0.36×2
0.35×2
8.75
8.35
8.00
-
-
INPUT POWER
W
35×2
35×2
35×2
1.765k
1.765k
1.765k
-
-
TOTAL W
-
1.835k
1.835k
1.835k
275
2.510k
COP/COP CLASS
TOTAL(W/W)
*
5/("A"~"G")
-
-
-
3.87
3.87 / A
3.87
6.55
3.23
Erp
*
6
Pdsign
kW
-
-
-
-
6.0
-
Tbivalen
°C
-
-
-
-
-6
-
SCOP
(W/W)
-
-
-
-
4.0
-
Annual consumption
kWh
-
-
-
-
2100
-
Class
-
-
-
-
A+
-
POWER FACTOR
%
-
-
-
92
92
92
-
-
NOISE INDOOR
(H/M/L)
dB-A
36/32/29
-
⁄
⁄
Power Level dB
54/50/47
-
NOISE OUTDOOR
(H/L)
dB-A
-
52/-
⁄
⁄
Power Level dB
-
70/-
EXTRA LOW TEMP Total CAPACITY(kW)/INPUT POWER(W)/COP
-
MAX CURRENT(A)/MAX INPUT POWER(W)
0.37×2/35×2 0.36×2/35×2 0.35×2/35×2
18.0/3.60k
18.0/3.77k
18.0/3.93k
⁄
STARTING CURRENT(A)/COMP OUTPUT(W)
-
-
-
10.8/1.0k
10.3/1.0k
9.85/1.0k
⁄
NETWORK IMPEDANCE (ΩMAX.)
-
-
FM OUTPUT (W)
43
90
⁄
MOISTURE REMOVAL VOLUME
L/h(Pt/h)
4.2
(2.1×2)
(8.8)
-
External static pressure
Pa
-
I/D AIR
FLOW
COOL
m
3
/min (ft
3
/min)
[14/12/10.5 (494/424/371)]×2
HEAT
m
3
/min (ft
3
/min)
[14/12/10.5 (494/424/371)]×2
O/D AIR
FLOW
COOL
m
3
/min (ft
3
/min)
39
(1377)
HEAT
m
3
/min (ft
3
/min)
39
(1377)
REFRIGERANT TYPE, AMOUNT
g
(oz)
R410A 1.70k
(60.0)
/
P
R
O
D
I
M
HEIGHT : H mm(inch)
235 (9-1/4)
569 (22-13/32)
/
WIDTH : W mm(inch)
960 (37-25/32)
790 (31-7/64)
/
DEPTH : D mm(inch)
690 (27-5/32)
285 (11-7/32)
/
P
A
C
D
I
M
HEIGHT : H mm
360
645
/
WIDTH : W mm
1025
921
/
DEPTH : D mm
820
386
/
MASS
(NET) k
g
(lb)
27 (60)
42 (93)
/
(GROSS) k
g
(lb)
34 (75)
46 (101)
/
LAYERS LIMIT (actually)
9 (10)
4 (5)
Operation
Condition
Cool O.D(DBT)
18°C ~ 32°C
-10°C ~ 43°C
Heat O.D(DBT)
16°C ~ 30°C
-15°C ~ 24°C
P
I
P
I
N
G
PIPE DIAMETER mm (inch)
(Liquid)ø6.35(1/4) (Gas)ø12.7(1/2)
(Liquid)ø9.52(3/8) (Gas)ø15.88(5/8)
CONNECT METHOD, STD LENGTH m (ft)
fl ared type, 5.0(16.4)
fl ared type, 5.0(16.4)
PIPE LENGTH RANGE m (ft)
5 ~ 50
(16.4 ~ 164.0)
~
~
I/D&O/D HEIGHT DIFFERENCE m (ft)
15 (OD located lower) / 30 (OD located higher)
(49.2/98.4)
ADD GAS AMOUNT
g
/m (oz/ft)
40
(0.430)
PIPE LENGTH FOR ADDITIONAL GAS m (ft)
20
(65.6)
*1
:
In case it is necessary to indicate the air fl ow volume in (l/s), the value in (m
3
/min.) shall be multiplied by 16.7 and rounded down the decimal point.
*2
:
If the EUROVENT Certifi ed models can be operated under the “extra-low” temperature condition, -7°C dry bulb and -8°C wet-bulb temperatures with rated voltage
230 V shall be used.
*3
:
Network Impedance shall be applicable for EUROPE and CHINA models.
*4
:
The annual consumption is calculated by multiplying the input power at 230 V (400 V) by an average of 500 hours per year in cooling mode.
*5
:
EER and COP classification is at 230 V (400 V) only in accordance with EU directive 2002/31/EC.
*6
:
SEER and SCOP classification is at 230V(400V) only in accordance with EN-14825. For heating, SCOP indicates the value of only Average heating season,
Other fiche data indicates in an attached sheet.