Programming Example, FP-FNS Block Profinet IO
69
Outputs
Output
Data Type
Function
sName
STRING[16]
Name of installed FP-FNS block
sBusType
STRING[20]
Network type of installed FP-FNS block
bOnline
BOOL
Flag for online status
bError
BOOL
Error flag
wErrorCode
WORD
Error code if error flag is set
List of error codes for FP-FNS block CANopen
Errorcode
Indication
16#0000
No error
16#0001
Controller and Device process data configuration do not match
16#0002
Process data area is too large (max. 64 slots, max. 128 words in each direction)
16#0004
Bus off or cable disconnected, or no link established between controller and device.
16#0005
FP-FNS block is not installed correctly
16#0007
FP-FNS block has incorrect provider ID
16#0008
Wrong FP-FNS block installed
16#000A
Exception state entered; application watchdog timeout; unit needs resetting
Summary of Contents for FPSIGMA
Page 1: ...programmable controller FPS FP2 Fieldbus Slave Units Technical Manual ...
Page 7: ......
Page 8: ...Chapter 1 Features and Restrictions ...
Page 11: ......
Page 12: ...Chapter 2 Parts and Functions ...
Page 14: ...FP2 FNS Unit 13 2 2 FP2 FNS Unit ...
Page 25: ......
Page 26: ...Chapter 3 Specifications ...
Page 32: ...Chapter 4 Installation and Wiring ...
Page 48: ...Chapter 5 Programming Examples for FPWIN Pro ...
Page 84: ...Chapter 6 Outline Dimensions ...
Page 85: ...Outline Dimensions 84 6 1 Outline Dimensions of FP2 FNS Unit ...
Page 86: ...Outline Dimensions of FPΣ FNS Unit 85 6 2 Outline Dimensions of FPΣ FNS Unit ...
Page 87: ...Outline Dimensions 86 6 3 Dimensions of the FP FNS Blocks ...