Installation and Wiring
42
2. Wrap the end of the cable with 38mm (1.5in.) of shrink wrap, covering part of the
exposed conductors and part of the trunk line insulation.
3. Strip 8.1mm (0.32in.) of the insulation from the end of each of the insulated
conductors.
4. Insert each conductor into the appropriate clamping cavity of the open style
connector or the screw terminal on the device, according to the color of the cable
insulation:
Wire color
Wire identity
Usage
White
CAN_H
Signal
Blue
CAN_L
Signal
Bare
Drain
Shield
Black
V-
Power
Red
V+
Power
5. Tighten the clamping screws to secure each conductor. The male contacts of the
device connector must match the female contacts of the connector.
When removing the wire's insulation, be careful not to scratch the core wire.
Do not twist the wires to connect them.
Do not solder the wires to connect them. The solder may break due to
vibration.
Summary of Contents for FPSIGMA
Page 1: ...programmable controller FPS FP2 Fieldbus Slave Units Technical Manual ...
Page 7: ......
Page 8: ...Chapter 1 Features and Restrictions ...
Page 11: ......
Page 12: ...Chapter 2 Parts and Functions ...
Page 14: ...FP2 FNS Unit 13 2 2 FP2 FNS Unit ...
Page 25: ......
Page 26: ...Chapter 3 Specifications ...
Page 32: ...Chapter 4 Installation and Wiring ...
Page 48: ...Chapter 5 Programming Examples for FPWIN Pro ...
Page 84: ...Chapter 6 Outline Dimensions ...
Page 85: ...Outline Dimensions 84 6 1 Outline Dimensions of FP2 FNS Unit ...
Page 86: ...Outline Dimensions of FPΣ FNS Unit 85 6 2 Outline Dimensions of FPΣ FNS Unit ...
Page 87: ...Outline Dimensions 86 6 3 Dimensions of the FP FNS Blocks ...