Parts and Functions
22
Ethernet interface, RJ45
The Ethernet interface supports autonegotiation and Auto MDI-X, with 10/100Mbit, full or half
duplex operation.
2.4.6 FP-FNS Block BACnet MS/TP
This FP-FNS block connects the unit to a BACnetMS/TP network.
Front view
No.
Item
1
Network status LED
2
Module status LED
3
BACnet MS/TP connector
Network Status
During start-up, a test sequence is performed on this LED.
State
Indication
Off
No power
Green
On-line, one or more BACnet messages have arrived
Module has active COV subscriptions
At least one value object has one or more events enabled
Flashing green (1Hz)
On-line, waiting for first BACnet message
Red
FATAL error
Flashing red (1Hz)
Connection timeout. No BACnet message has been received within the configured
‘process active timeout’ time.
A COV or Alarm/Event notification could not be sent to its recipient
Module Status
During start-up, a test sequence is performed on this LED.
State
Indication
Off
No power
Green
Operating in normal condition
Red
Major fault (EXCEPTION-state, FATAL error etc.)
Flashing red (1Hz)
Recoverable fault(s)
Summary of Contents for FPSIGMA
Page 1: ...programmable controller FPS FP2 Fieldbus Slave Units Technical Manual ...
Page 7: ......
Page 8: ...Chapter 1 Features and Restrictions ...
Page 11: ......
Page 12: ...Chapter 2 Parts and Functions ...
Page 14: ...FP2 FNS Unit 13 2 2 FP2 FNS Unit ...
Page 25: ......
Page 26: ...Chapter 3 Specifications ...
Page 32: ...Chapter 4 Installation and Wiring ...
Page 48: ...Chapter 5 Programming Examples for FPWIN Pro ...
Page 84: ...Chapter 6 Outline Dimensions ...
Page 85: ...Outline Dimensions 84 6 1 Outline Dimensions of FP2 FNS Unit ...
Page 86: ...Outline Dimensions of FPΣ FNS Unit 85 6 2 Outline Dimensions of FPΣ FNS Unit ...
Page 87: ...Outline Dimensions 86 6 3 Dimensions of the FP FNS Blocks ...