Wiring of the FP-FNS Blocks
41
4.6 Wiring of the FP-FNS Blocks
4.6.1 FP-FNS Block PROFIBUS DP Wiring
Use a standard PROFIBUS cable and standard 9-pin Sub-D male PROFIBUS connectors.
We recommend using a straight (0°) bus interface connector (e.g. PR 103-658). When a
horizontal (90°) bus interface connector is used, the cables will be directed toward the top of
the unit, which may cause difficulties when installing other devices in a control cabinet.
4.6.2 FP-FNS Block DeviceNet Wiring
Open style connector/suitable wire
DeviceNet has a standard open style connector.
If additional connectors are needed, use the standard CAN 5-pin open style
connectors
manufactured by Phoenix Contact.
No. of contacts
Phoenix Contact product ID
5
Model no.
Product no.
MSTB 2,5/ 5-ST-5,08 ABGY AU
1849037
Terminal block for DeviceNet
For a suitable wire, please refer to cable selection (see page 40).
Wiring method
Attach a plug-in, open style connector to a cable.
1. Strip 65mm (2.6in.) to 75mm (3in.) of the outer jacket from the end of the cable,
leaving no more than 6.4mm (0.25in.) of the braided shield exposed.
Summary of Contents for FPSIGMA
Page 1: ...programmable controller FPS FP2 Fieldbus Slave Units Technical Manual ...
Page 7: ......
Page 8: ...Chapter 1 Features and Restrictions ...
Page 11: ......
Page 12: ...Chapter 2 Parts and Functions ...
Page 14: ...FP2 FNS Unit 13 2 2 FP2 FNS Unit ...
Page 25: ......
Page 26: ...Chapter 3 Specifications ...
Page 32: ...Chapter 4 Installation and Wiring ...
Page 48: ...Chapter 5 Programming Examples for FPWIN Pro ...
Page 84: ...Chapter 6 Outline Dimensions ...
Page 85: ...Outline Dimensions 84 6 1 Outline Dimensions of FP2 FNS Unit ...
Page 86: ...Outline Dimensions of FPΣ FNS Unit 85 6 2 Outline Dimensions of FPΣ FNS Unit ...
Page 87: ...Outline Dimensions 86 6 3 Dimensions of the FP FNS Blocks ...