Diagnosing output malfunction
<First check the output condition and then the input condition>
1
1
Output condition: the output indicators are ON
• If the power is properly supplied to the load, there is probably an abnormality in the
load. Check the load again.
• If the power is not supplied to the load, there is probably an abnormality in the FP-M’s
output.
Please contact your dealer.
2
2
Output condition: the output indicators are OFF
How to monitor the outputs:
• Using the NPST-GR Software Ver. 3.1
• Using the FP Programmer II
ACLR
(–)
OP
7
ENT
ENT
AN
Y-WY
0
READ
▼
Press the keys on the FP Programmer II
as shown on the right.
If the output monitored is turned ON,
there is probably a duplicated output
error or I/O allocation error.
Check the program and the I/O
allocation.
<If you are using MENU 1 screen type>
Open [NPST MENU] by pressing
Esc
,
then select “MONITOR” to skip to the
[MONITOR] subwindow.
In the [MONITOR] subwindow, select
“3. MONITOR LISTED RELAYS”.
<If you are using MENU 2 screen type>
Open [ONLINE MONITOR
FUNCTION MENU] by pressing
Ctrl
and
F10
together, then select
“I. LISTED RELAYS”.
Monitor the output condition using a
programming tool.
Check if the power is properly supplied
to the output devices.
Check the wiring of the output devices.
118