Installing feed-in cap with a circuit breaker equipped
7
Note
●
To connect the cable (B), be sure to put the polarity
indication side of the Fact-line duct on the grounding side.
●
if the polarity is changed by processing the duct end or
using he auxiliary duct unit (DH2310), the arrangement of
terminals of the feed-in cap will be inverted.
●
The cable (A) must be 14 to 38 mm
2
in size.
●
The cable (B) must be a single-conductor cable of 1.6 to
2.0 mm in size or a stranded-conductor cable of 2 to 3.5
mm
2
in size.
●
To use a terminal plug with a remote-control circuit breaker
equipped, apply a 100V operating voltage. (200V operating
voltage is not available for this product.)
●
Connect a grounding cable to the grounding terminal screw
by the use of a crimp-style terminal or winding the cable
around the terminal.
1
.Strip the sheath of the cable (A) by 13 to 15 mm in length, and
then mount a crimp-style terminal to the electrical cable (A).
2
.Securely connect the electrical cable (A) to the
terminal block of the circuit breaker.
After connecting,post the polarity indication label near the
screw terminals.(Tightening torque 5.0 N ・ m 〜 7.0 N ・ m)
3
.Strip the sheath of the electrical cable (B) by 10 to 12 mm in
length, unfasten the terminal screw (B) to put the electrical
cable (B) under the washer, and then fasten the terminal
screw (B) to securely connect the electrical cable (B).
(Tightening torque 2.1 N ・ m 〜 2.6 N ・ m)
4
.Mount the cover to the feed-in cap with the circuit
breaker equipped.
Connecting cables
Put a feed-in cap with a circuit breaker equipped in the
Factory Line duct, and then fasten the setscrew to fix the cap.
Connecting to Factory Line duct
●
Securely fasten the setscrews and terminal screws.
Doing so may result in an electric shock, or a fire
Caution
Cover
Circuit breaker
Terminal screw (B)(M5)
Feed-in cap with a circuit breaker equipped
Pilot lamp
Setscrew
Electrical cable(A)
Electrical cable(B)
Terminal screw(M8)
Terminal block
Grounding
terminal screw
Polarity indication
(Grounding side)
Feed-in Cap
with a circuit breaker equipped
Put the polarity indication label
Duct
The plug front
The plug
right side
The plug
left side
Polarity indication
(Green line)
Polarity indication label
24