Installation Procedure
Precautions on installation
●Determine a direction in which the duct is mounted after determining the
direction of plug.
●Install the duct pointing the font side of the plug and the polarity marking of
the duct to the same direction.
(The feed-in cap is located on the left when viewed from the front side of the plug.)
Relation between a direction in which the Factory Line duct is mounted and direction of plug
Relation between the power feed position (feed-in) and the direction of plug
When the power feed position is located in the middle:
Connect the feed-in cap to the side with no
joiner pins equipped of the duct.
1
.Cut the joiner pins side of the duct by 40 mm
using a metal saw.
3
.Thoroughly remove burrs and chips from the cut surface.
(Be sure to chamfer the inner surface of the
conductors in particular.)
2
.Cut the ribs (three places) of the duct using a drill of
φ3 mm in diameter (10 to 11 mm in depth).
In this case, the joiner pins part of the duct
needs to be cut.
Polarity indication
(Grounding side)
(Green line)
Duct
Duct
Front side of plug
End cap
(Figure viewed from the bottom)
Joiner pins
Front side of plug
Front side of plug
End cap
(Figure viewed from the bottom)
Front side of plug
Auxiliary duct
(Figure viewed from the bottom)
(Figure viewed from the bottom)
Feed-in cap
Feed-in cap
Cut by 40 mm.
Center feed-in joiner
Front side of plug
End cap
End cap
Feed-in cap
Joiner pin
Cut by 40 mm.
Rib
Core
Conductors
Caution
●
To cut the ribs, prevent the exposure of the
conductors and cores.
Not doing so may result in an electric shock.
Note
●
Using an power saw may cause insulating coating to peel or
burn
Note
●
Since each end of Fact-line 60 is specially processed, do
not cut the end.
Factory Line 100
Use the auxiliary duct unit (DH2310) for Factory
Line 60.
Factory Line 60
Connect the docts both ends of the center
feed-in joiner
Standard installation
To connect the feed-in cap to the joiner pins side of the duct:
Polarity indication
(Grounding side)
(Green line)
φ3-mm
drill
The ribs 3 places
Cut by 10 to 11 mm in length
from the cut surface.
The side of breaker's
handle or nameplate
28
29