40
12. Operation
Control
12.1 Basic Function
Inverter control, which equipped with a microcomputer in determining the most suitable operating mode as time
passes, automatically adjusts output power for maximum comfort always. In order to achieve the suitable operating
mode, the microcomputer maintains the set temperature by measuring the temperature of the environment and
performing temperature shifting. The compressor at outdoor unit is operating following the frequency instructed by
the microcomputer at indoor unit that judging the condition according to internal setting temperature and intake air
temperature.
12.1.1 Internal Setting Temperature
Once the operation starts, remote control setting temperature will be taken as base value for temperature shifting
processes. These shifting processes are depending on the air conditioner settings and the operation environment.
The final shifted value will be used as internal setting temperature and it is updated continuously whenever the
electrical power is supplied to the unit.
12.1.2 Cooling
Operation
12.1.2.1 Thermostat
control
Compressor is OFF when Intake Air Temperature - Internal Setting Temperature < -1.5°C continue for 3 minutes.
When compressor is OFF (Thermostat OFF) and AUTO FAN is set, the fan will stop periodically.
Compressor is ON after waiting for 3 minutes, if the Intake Air Temperature - Internal Setting Temperature >
Compressor OFF point.
12.1.3 Soft Dry Operation
12.1.3.1 Thermostat
control
Compressor is OFF when Intake Air Temperature - Internal Setting Temperature < -1.0°C continue for 3 minutes.
When compressor is OFF (Thermostat OFF) and AUTO FAN is set, the fan will stop periodically.
Compressor is ON after waiting for 3 minutes, if the Intake Air Temperature - Internal Setting Temperature >
Compressor OFF point.
12.1.4 Heating
Operation
12.1.4.1 Thermostat
control
Compressor is OFF when Intake Air Temperature - Internal Setting Temperature > +2.0°C continue for 3 minutes.
Compressor is ON after waiting for 3 minutes, if the Intake Air Temperature - Internal Setting Temperature <
Compressor OFF point.
Summary of Contents for CS-E12QB4RW
Page 12: ...12 4 Location of Controls and Components 4 1 Indoor Unit 4 2 Outdoor Unit 4 3 Remote Control ...
Page 13: ...13 5 Dimensions 5 1 Indoor Unit ...
Page 14: ...14 5 2 Outdoor Unit 5 2 1 CU E12QB4R 5 2 2 CU E18QB4R ...
Page 15: ...15 6 Refrigeration Cycle Diagram ...
Page 16: ...16 7 Block Diagram 7 1 CS E12QB4RW CU E12QB4R ...
Page 17: ...17 7 2 CS E18QB4RW CU E18QB4R ...
Page 18: ...18 8 Wiring Connection Diagram 8 1 Indoor Unit ...
Page 21: ...21 9 Electronic Circuit Diagram 9 1 Indoor Unit ...
Page 22: ...22 9 2 Outdoor Unit 9 2 1 CU E12QB4R ...
Page 23: ...23 9 2 2 CU E18QB4R ...
Page 24: ...24 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board ...
Page 25: ...25 10 1 2 Display Printed Circuit Board ...
Page 26: ...26 10 2 Outdoor Unit 10 2 1 Main Printed Circuit Board 10 2 1 1 CU E12QB4R ...
Page 27: ...27 10 2 1 2 CU E18QB4R ...
Page 28: ...28 10 2 2 Demand Control Printed Circuit Board 10 2 2 1 CU E12QB4R 10 2 2 2 CU E18QB4R ...
Page 54: ...54 CU E18QB4R ...
Page 92: ...92 18 1 2 CS E18QB4RW CU E18QB4R ...
Page 94: ...94 18 2 2 CS E18QB4RW CU E18QB4R ...
Page 97: ...97 19 Exploded View and Replacement Parts List 19 1 Indoor Unit ...