15.4.21 F96 (IPM Overheating)
Malfunction Decision Conditions
During operating of cooling and heating, when IPM temperature data (100°C) is detected by the IPM temperature
sensor.
Multi Models only
o
Compressor Overheating: During operation of cooling and heating, when the compressor OL is activated.
o
Heat Sink Overheating: During operation of cooling and heating, when heat sink temperature data (90°C) is
detected by the heat sink temperature sensor.
Malfunction Caused
IPM overheats due to short circuit of hot discharge air flow.
IPM overheats due to defective of outdoor fan motor.
IPM overheats due to defective of internal circuitry of IPM.
IPM overheats due to defective IPM temperature sensor.
Multi Models Only
o
Compressor OL connector poor contact.
o
Compressor
OL
faulty.
Troubleshooting
Summary of Contents for CS-E12QB4RW
Page 12: ...12 4 Location of Controls and Components 4 1 Indoor Unit 4 2 Outdoor Unit 4 3 Remote Control ...
Page 13: ...13 5 Dimensions 5 1 Indoor Unit ...
Page 14: ...14 5 2 Outdoor Unit 5 2 1 CU E12QB4R 5 2 2 CU E18QB4R ...
Page 15: ...15 6 Refrigeration Cycle Diagram ...
Page 16: ...16 7 Block Diagram 7 1 CS E12QB4RW CU E12QB4R ...
Page 17: ...17 7 2 CS E18QB4RW CU E18QB4R ...
Page 18: ...18 8 Wiring Connection Diagram 8 1 Indoor Unit ...
Page 21: ...21 9 Electronic Circuit Diagram 9 1 Indoor Unit ...
Page 22: ...22 9 2 Outdoor Unit 9 2 1 CU E12QB4R ...
Page 23: ...23 9 2 2 CU E18QB4R ...
Page 24: ...24 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board ...
Page 25: ...25 10 1 2 Display Printed Circuit Board ...
Page 26: ...26 10 2 Outdoor Unit 10 2 1 Main Printed Circuit Board 10 2 1 1 CU E12QB4R ...
Page 27: ...27 10 2 1 2 CU E18QB4R ...
Page 28: ...28 10 2 2 Demand Control Printed Circuit Board 10 2 2 1 CU E12QB4R 10 2 2 2 CU E18QB4R ...
Page 54: ...54 CU E18QB4R ...
Page 92: ...92 18 1 2 CS E18QB4RW CU E18QB4R ...
Page 94: ...94 18 2 2 CS E18QB4RW CU E18QB4R ...
Page 97: ...97 19 Exploded View and Replacement Parts List 19 1 Indoor Unit ...