41
12.1.5 Automatic
Operation
This mode can be set using remote control and the operation is decided by remote control setting temperature,
remote control operation mode and indoor intake air temperature.
During operation mode judgment, indoor fan motor (with speed of Lo-) is running for 30 seconds to detect the
indoor intake air temperature.
Every 10 minutes, the indoor temperature is judged.
For the 1st judgment
o
If indoor intake temperature - remote control setting temperature
≥
2°C, COOL mode is decided.
o
If
-2°C
≤
indoor intake temperature - remote control setting temperature < 2°C, DRY mode is decided.
o
If indoor intake temperature - remote control setting temperature < -2°C, HEAT mode is decided.
For the 2nd judgment onwards
o
If indoor intake temperature - remote control setting temperature
≥
4°C, if previous operate in DRY mode,
then continue in DRY mode. otherwise COOL mode is decided.
o
If
-2.5°C
≤
indoor intake temperature - remote control setting temperature < 4°C, maintain with previous
mode.
o
If indoor intake temperature - remote control setting temperature < -2.5°C, HEAT mode is decided.
12.2 Indoor Fan Motor Operation
12.2.1 Basic Rotation Speed (rpm)
A. Basic Rotation Speed (rpm)
i. Manual Fan Speed
[Cooling, Dry]
Fan motor’s number of rotation is determined according to remote control setting.
Remote control
○
○
○
○
○
Tab Hi
Me+
Me
Me-
Lo
[Heating]
Fan motor’s number of rotation is determined according to remote control setting.
Remote control
○
○
○
○
○
Tab SHi
Me+
Me
Me-
Lo
ii Auto Fan Speed
[Cooling, Dry]
According to room temperature and setting temperature, indoor fan speed is determined automatically.
When set temperature is not achieved, the indoor fan will operate according to pattern below.
When set temperature achieved, the indoor fan speed will be fixed. When thermostat off, the fan stop periodically.
Summary of Contents for CS-E12QB4RW
Page 12: ...12 4 Location of Controls and Components 4 1 Indoor Unit 4 2 Outdoor Unit 4 3 Remote Control ...
Page 13: ...13 5 Dimensions 5 1 Indoor Unit ...
Page 14: ...14 5 2 Outdoor Unit 5 2 1 CU E12QB4R 5 2 2 CU E18QB4R ...
Page 15: ...15 6 Refrigeration Cycle Diagram ...
Page 16: ...16 7 Block Diagram 7 1 CS E12QB4RW CU E12QB4R ...
Page 17: ...17 7 2 CS E18QB4RW CU E18QB4R ...
Page 18: ...18 8 Wiring Connection Diagram 8 1 Indoor Unit ...
Page 21: ...21 9 Electronic Circuit Diagram 9 1 Indoor Unit ...
Page 22: ...22 9 2 Outdoor Unit 9 2 1 CU E12QB4R ...
Page 23: ...23 9 2 2 CU E18QB4R ...
Page 24: ...24 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board ...
Page 25: ...25 10 1 2 Display Printed Circuit Board ...
Page 26: ...26 10 2 Outdoor Unit 10 2 1 Main Printed Circuit Board 10 2 1 1 CU E12QB4R ...
Page 27: ...27 10 2 1 2 CU E18QB4R ...
Page 28: ...28 10 2 2 Demand Control Printed Circuit Board 10 2 2 1 CU E12QB4R 10 2 2 2 CU E18QB4R ...
Page 54: ...54 CU E18QB4R ...
Page 92: ...92 18 1 2 CS E18QB4RW CU E18QB4R ...
Page 94: ...94 18 2 2 CS E18QB4RW CU E18QB4R ...
Page 97: ...97 19 Exploded View and Replacement Parts List 19 1 Indoor Unit ...