15.4.6 H19 (Indoor Fan Motor – DC Motor Mechanism Locked)
Malfunction Decision Conditions
The rotation speed detected by the Hall IC during fan motor operation is used to determine abnormal fan motor
(feedback of rotation > 2550rpm or < 50rpm)
Malfunction Caused
Operation stops due to short circuit inside the fan motor winding.
Operation stops due to breaking of wire inside the fan motor.
Operation stops due to breaking of fan motor lead wires.
Operation stops due to Hall IC malfunction.
Operation error due to faulty indoor unit PCB.
Troubleshooting
Summary of Contents for CS-E12QB4RW
Page 12: ...12 4 Location of Controls and Components 4 1 Indoor Unit 4 2 Outdoor Unit 4 3 Remote Control ...
Page 13: ...13 5 Dimensions 5 1 Indoor Unit ...
Page 14: ...14 5 2 Outdoor Unit 5 2 1 CU E12QB4R 5 2 2 CU E18QB4R ...
Page 15: ...15 6 Refrigeration Cycle Diagram ...
Page 16: ...16 7 Block Diagram 7 1 CS E12QB4RW CU E12QB4R ...
Page 17: ...17 7 2 CS E18QB4RW CU E18QB4R ...
Page 18: ...18 8 Wiring Connection Diagram 8 1 Indoor Unit ...
Page 21: ...21 9 Electronic Circuit Diagram 9 1 Indoor Unit ...
Page 22: ...22 9 2 Outdoor Unit 9 2 1 CU E12QB4R ...
Page 23: ...23 9 2 2 CU E18QB4R ...
Page 24: ...24 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board ...
Page 25: ...25 10 1 2 Display Printed Circuit Board ...
Page 26: ...26 10 2 Outdoor Unit 10 2 1 Main Printed Circuit Board 10 2 1 1 CU E12QB4R ...
Page 27: ...27 10 2 1 2 CU E18QB4R ...
Page 28: ...28 10 2 2 Demand Control Printed Circuit Board 10 2 2 1 CU E12QB4R 10 2 2 2 CU E18QB4R ...
Page 54: ...54 CU E18QB4R ...
Page 92: ...92 18 1 2 CS E18QB4RW CU E18QB4R ...
Page 94: ...94 18 2 2 CS E18QB4RW CU E18QB4R ...
Page 97: ...97 19 Exploded View and Replacement Parts List 19 1 Indoor Unit ...