Problem
Cause of problem
Solution
Ref.Page
The stove does not light with electric
ignition
Wall outlet not powered
Use a tester to check for current on line.
Also check if there is an earth + unipolar circuit
breaker
7
Faulty plug
Use a tester to check and, where necessary, replace
7
Fuse blown
Replace 2A fuse: can be reached via control unit
18
Control panel ON/OFF switch faulty
Replace control panel
12
Control unit memory failure
Reset stove by setting ON/OFF switch to OFF
and unplug for a few seconds before switching
back on.
12-7
General control unit faulty (electrical-type sounds can
be heard)
Check whether it has been damaged by a
thunderbolt and replace
Microswitch on “Ecofire” does not produce contact
when operated
Check whether it has been tampered with and
check for incorrect activation
11
The stove is not fed with pellets (the
auger does not turn)
Auger clogged by pellet residues
Clean the feed pipe, reached via the pellet
hopper: remove the safety guard
6-16
No pellets in hopper
Load with fuel
6
Auger motor failure
Check with a tester and replace
17
Pressure switch does not detect vacuum
Clean the exchanger and flue pipe. Stove
clogged. Clean smoke exchanger, smoke holes,
vent pipe, any bends, draught-diverter cowl.
Wind blowing in from outside: install draught-
diverter cowl.
8-14-15
145° C safety thermostat trips
Reset the thermostat manually. Check why the
safety device tripped:
• thermostat faulty
• hot-air blower faulty
• break in 100° C max. thermostat
• current was cut off before the automatic
switch-off cycle had finished
16-17
The resistor does not come on
Resistor not powered, or burnt out; incorrect hole
alignment
Check connections, replace, correct hole
alignment
17-18
The stove does not make the transition
from Startup phase to Operating phase
(switches off 18’ after switch-on)
46° C minimum smoke temperature thermostat
tripped
Check and replace
16-18
Irregular combustion, glass goes black
and stove tends to go out
Air getting in owing to worn door gasket
Check and replace
Excessive moisture in pellets or wood
Check quality of fuel
6
Exchanger and flue pipe clogged
Perform recommended cleaning
14-15
Stove tends to go out when set to first
heat output setting
Too few pellets fed into burn pot
Adjust minimum trimmer on back of control panel
18
Excessive moisture in pellets
Check fuel type and place used for storage
6
Not enough combustion air to burn pot as stove is
dirty
Perform recommended cleaning
14-15
Fuelled with wood
Increase fan power to setting 4
13
Excessive consumption in position 1
Trimmer on control panel set to max.
Adjust minimum trimmer on back of control
panel, setting it to “-“
18
Room temp. thermostat tripped and automatic mode
set to position 2
Set room temp. thermostat knob to maximum
(35° C) and feeding potentiometer to minimum
12
The hot-air blower does not come on
46° C minimum blower thermostat contact always
open
Check and replace
16-18
Fan works all the time, even when the
stove is cold
46° C minimum blower thermostat contact always
closed
Check and replace
16-18
Fan operating at top speed the whole
time
100° C maximum blower thermostat contact always
closed
Check and replace
16-18
The stove does not turn off and the
draught fan works all the time, even
when the stove is cold
46° C minimum smoke temperature thermostat
contact always closed
Check and replace
16-18
Wind blowing in from outside
Install draught-diverter cowl
9
Smoke released into the room
Internal pipe couplings are not airtight
Check, seal or replace
9
No power supply and combustion in progress
Connect vent pipe with difference between levels
of at least 1.5 metres, as per instruction booklet
9
The first time the stove is turned on, no
pellets fall into burn pot
New stove with auger empty or pellets run out
Fill the burn pot manually with a handful of
pellets
12
4 - ECOFIRE: TROUBLESHOOTING TABLE
18
GB