Assembly
900-0123-01-00 Rev
A
17
Remove Interior Cover
In order to make any wiring connections or install components, the interior cover must be removed to
expose the interior of the enclosure.
Figure 11
Removing the Interior Cover from the GSLC
Installing the Internal Hardware
Table 2
Bus Bar and Circuit Breaker Size and Torque Requirements
Item
Terminal/Bolt Size
Torque Requirements
Inverter Positive Bus Bars
M8
60 in-lb (6.8 Nm)
Shunt Bolts
3/8”
60 in-lb (6.8 Nm)
DC Positive Cable Plate
Top Holes (x3)
60 in-lb (6.8 Nm)
Bottom Holes (x7)
50 in-lb (5.7 Nm)
Circuit Breaker Studs
M8
20 in-lb (2.3 Nm)
1/4”
35 in-lb (4 Nm)
5/16”
50 in-lb (5.7 Nm)
3/8”
225 in-lb (25.5 Nm)
Figure 12
DC Positive Cable Plate
Top Holes
Bottom Holes
0.5”(12.7 mm)
0.31”(8 mm)
0.4”(10 mm)
Remove (x3)
Remove (x3)
Interior
Cover
To Remove the Interior Cover:
1.
Remove the three screws along the top of the
enclosure.
2.
Remove the three screws along the bottom of
the enclosure.
3.
Lift the front cover off the enclosure.
PDF compression, OCR, web optimization using a watermarked evaluation copy of CVISION PDFCompressor