Expansion module with outer components
3-stage
(1/3 - 2/3 output distribution)
Stage order, 3-stage DX
DX-1
DX-2
Cooling not active
Off
Off
1st stage
On
Off
2nd stage
Off
On
3rd stage
On
On
13
Start
DX-1
Cooling
unit
DX-C
11
12
14
86
Alarm
indiction
87
EXP1
Start
DX-2
Alarm DX cooling
Alarm signal or operation indication (feedback) from the DX cooling unit can be used.
An alarm in the DX cooling unit will then be presented as Alarm Cooling in the HMI.
For activation/configuration:
Parameter name
Area
Select
Main index > Configuration > Configuration 1
Expansion
module
No, One, Two
One
Cooling
No, Water
DX 1stage, DX 2stage, DX
3stage
….
Select suitable DX stage
Restart
√
, Execute
Execute
Main index > Configuration > Configuration 2
Alarm DX cooling
No / Alarm / Return / Alarm+
Return
(Alarm+return, not applicable to
HERU® CX )
-
No
If no alarm/ind. is used
-
Alarm
Common alarm in DX
cooling unit
-
Return
Operation indication in DX
cooling unit
Restart
√
, Execute
Execute
Main index > Configuration > Config. IOs > Digital alarms
DX cooling
…
X16
Main index > Configuration > Config. IOs > Outputs temp.control
DX cooling
output 1
…
DO11
DX cooling
output 2
…
DO12
Restart
√
, Execute
Execute
Connection
Parameter
Summary of Contents for HERU 400-2400 S
Page 1: ...U S E R M A N U A L E N H E R U 4 0 0 2 4 0 0 T S HERU T HERU S...
Page 2: ......
Page 14: ...14 120 Climatix HERU 400 2400 2018 02 13 Scope of assembly installation instructions...
Page 45: ...45 120 2018 02 13 Climatix HERU 400 2400 External components basic unit...
Page 97: ...97 120 2018 02 13 Climatix HERU 400 2400 Miscellaneous Menu structure Menu overview...
Page 98: ...98 120 Climatix HERU 400 2400 2018 02 13 Miscellaneous Start page Main index Unit...
Page 104: ...104 120 Climatix HERU 400 2400 2018 02 13 SERVICE HERU...
Page 111: ...111 120 2018 02 13 Climatix HERU 400 2400 SERVICE HERU...
Page 118: ...118 120 2017 11 03 Climatix HERU 400 2400 Troubleshooting...
Page 119: ......
Page 120: ......