91 / 120
2018-02-13
Climatix HERU® 400-2400
Miscellaneous
HERU® CX I/O configuration
Controller 1
Physical positioning for controller POL683x
IO
Function
IO type
Connection
Comments
Digital outputs
DO1 Outside air damper
Digital
T6 (Q13,Q14) ST1/ST2
DO2 Pump Heating, Electric heating
command (stage-1)
Digital
T6 (Q23,Q24) CP1, EHC
DO3 Pump cooling, HCP start heating Digital
T6 (Q33,Q34) CP2, DX-CHP
DO4 Common alarm A+B, alarm A
Digital
T6 (Q43,Q44)
DO5 Alarm B
Digital
T7 (Q53,Q54)
DO6 AUX operating mode indication
Digital
T7 (Q63,Q64)
Analog outputs
AO1 Supply air signal 0-10 V DC
0...10 V DC
T3 (Y1,M)
Supply-EC
AO2 Extract air signal 0-10 V DC
0...10 V DC
T3 (Y2,M)
Extract-EC
Binary inputs
DI1
Alarm Fans (Common alarm
Extract)
Digital
T4 (D1,M)
Supply-
EC+Extract-EC
DI2
Alarm HRW recovery
Digital
T4 (D2,M)
EMS
DI3
External control input 1 (Timer
input), presence detector
Digital
T4 (D3,M)
TM1, GN1
DI4
External control input 2, Alarm
filter, Quick stop
Digital
T4 (D4,M)
TM2, GP3/GP4
DI5
Alarm fire/smoke
Digital
T4 (D5,M)
Universal inputs
X1
Supply air temperature
NI1KLG
T2 (X1,M)
GT1
X2
Extract air temperature, room
temperature
NI1KLG
T2 (X2,M)
GT2, GTR
Universal inputs/outputs
X3
Outside temperature
NI1KLG
T2 (X3,M)
GT3
X4
Frost protection sensor, Alarm
electric heater/Overheating
NI1KLG
T2 (X4,M)
GT8, GT9 (GT9-
A/GT9-M)
X5
Exhaust air temperature, min
limit recovery
NI1KLG
T2 (X5,M)
GT42
X6
Recovery signal
AO
0…
10 V DC
T2 (X6,M)
EMS
X7
Heating valve signal, electric
heater signal
AO
0…
10 V DC
T2 (X7,M)
SV1
X8
Cooling valve signal, cooling unit
signal, signal HCP
AO
0…
10 V DC
T2 (X8,M)
SV2, KM1, HCP
Expansion module 1
Physical positioning expansion module POL955 with address 1
IO
Function
IO type
Connection
Comments
Digital outputs
DO11
Cooling unit 1-stage, DX stage-1
Digital
T3 (Q13,Q14) KM1, DX-1
DO12
DX stage-2
Digital
T3 (Q23,Q24) DX-2
DO13
Indication supply air stage 2
Digital
T3 (Q33,Q34) Supply air
Stage-2 Ind
DO14
Indication supply air stage 3
Digital
T4 (Q43,Q44) Supply air
Stage-3 Ind
Analog outputs
AO11
Back-up
0...10 V DC
T5 (Y1,M)
AO12
Back-up
0...10 V DC
T5 (Y2,M)
Universal inputs/outputs
X11
Supply air pressure (GP1)
AI
0…
10 V DC
T1 (X1,M)
GP1
Summary of Contents for HERU 400-2400 S
Page 1: ...U S E R M A N U A L E N H E R U 4 0 0 2 4 0 0 T S HERU T HERU S...
Page 2: ......
Page 14: ...14 120 Climatix HERU 400 2400 2018 02 13 Scope of assembly installation instructions...
Page 45: ...45 120 2018 02 13 Climatix HERU 400 2400 External components basic unit...
Page 97: ...97 120 2018 02 13 Climatix HERU 400 2400 Miscellaneous Menu structure Menu overview...
Page 98: ...98 120 Climatix HERU 400 2400 2018 02 13 Miscellaneous Start page Main index Unit...
Page 104: ...104 120 Climatix HERU 400 2400 2018 02 13 SERVICE HERU...
Page 111: ...111 120 2018 02 13 Climatix HERU 400 2400 SERVICE HERU...
Page 118: ...118 120 2017 11 03 Climatix HERU 400 2400 Troubleshooting...
Page 119: ......
Page 120: ......