Climatix HERU® 400-2400
2018-02-13
Miscellaneous
Functions
Operation indication in the control unit
On/alarm
“Voltage
on”
will glow steadily.
Flashes when the control unit has been tripped.
Operation
Illuminates when the motor will rotate, i.e. when the input signal
exceeds the threshold value.
Rotation
Flashes every time the magnet passes the magnet sensor, regardless
of the setting of the DIP switch
“Rotation
monitor”.
Also flashes if the input signal is lower than the threshold value.
12.1.3.1
Troubleshooting, alarm
Observation
indication
Cause/action
Check that the DIP
switches are correctly
set
DIP switch
“On”
to the left.
No LED
illuminated
Check that 230 VAC ±10% is on the mains terminal. If the
mains voltage is correct, replace the control unit.
Rotation alarm
•
Belt broken
•
Belt dislodged
•
Belt stuck
•
Magnet sensor or magnet not intact
Overvoltage
The feed voltage is above 265 V. Ensure correct voltage to
the unit.
Undervoltage
The feed voltage is below 190 V. Ensure correct voltage to
the unit.
Over/under
temperature
The temperature in the control unit is above +85
°
C or below
-30
°
C.
Summary of Contents for HERU 400-2400 S
Page 1: ...U S E R M A N U A L E N H E R U 4 0 0 2 4 0 0 T S HERU T HERU S...
Page 2: ......
Page 14: ...14 120 Climatix HERU 400 2400 2018 02 13 Scope of assembly installation instructions...
Page 45: ...45 120 2018 02 13 Climatix HERU 400 2400 External components basic unit...
Page 97: ...97 120 2018 02 13 Climatix HERU 400 2400 Miscellaneous Menu structure Menu overview...
Page 98: ...98 120 Climatix HERU 400 2400 2018 02 13 Miscellaneous Start page Main index Unit...
Page 104: ...104 120 Climatix HERU 400 2400 2018 02 13 SERVICE HERU...
Page 111: ...111 120 2018 02 13 Climatix HERU 400 2400 SERVICE HERU...
Page 118: ...118 120 2017 11 03 Climatix HERU 400 2400 Troubleshooting...
Page 119: ......
Page 120: ......