Climatix HERU® 400-2400
2018-02-13
Modbus pressure sensor for pressure regulation
Assembly
To obtain the desired IP rating, the differential pressure sensor must be mounted
vertically (connection fittings downward). The connection fittings must also be located
higher than the measuring tube at the air duct.
When the connection fittings are pointed upward, or if these are lower than the
measuring tube, condensation water can collect in the sensor and cause damage.
Pressure regulation, addressing of pressure sensor
When using Modbus signal for pressure sensors, the pressure range does not need to
be adjusted. Modbus handles this via the data signal. The measuring range is only used
when the 0-10 V signal is used.
Description I/O designation
Type of function
Pressure sensor
unit
I/O-
type
Pxxx
x40x
xxx1
Supply air
pressure, GP1
QBM68.2525
P401
Pressure
MB address 40
1=P1
Extract air
pressure, GP2
QBM68.2525
P402
Pressure
MB address 40
2=P2
Important!
1
2
3
4
5
6
7
8
O
N
1
2
3
4
O
N
A
B
Summary of Contents for HERU 400-2400 S
Page 1: ...U S E R M A N U A L E N H E R U 4 0 0 2 4 0 0 T S HERU T HERU S...
Page 2: ......
Page 14: ...14 120 Climatix HERU 400 2400 2018 02 13 Scope of assembly installation instructions...
Page 45: ...45 120 2018 02 13 Climatix HERU 400 2400 External components basic unit...
Page 97: ...97 120 2018 02 13 Climatix HERU 400 2400 Miscellaneous Menu structure Menu overview...
Page 98: ...98 120 Climatix HERU 400 2400 2018 02 13 Miscellaneous Start page Main index Unit...
Page 104: ...104 120 Climatix HERU 400 2400 2018 02 13 SERVICE HERU...
Page 111: ...111 120 2018 02 13 Climatix HERU 400 2400 SERVICE HERU...
Page 118: ...118 120 2017 11 03 Climatix HERU 400 2400 Troubleshooting...
Page 119: ......
Page 120: ......