External components basic unit
Damper motors
There are two different types of actuators for damper control.
-
Spring return
(2-point)
-
On/Off
(3-point)
The On/Off actuator is only designed to be combined with electric air heater EHC.
If the air heater is a water heater, the system must be equipped with a spring-return
(2-point) actuator. If not, the coil and/or the fluid piping system can freeze. Natural
draught can occur in the ventilation ducts at the same time as frost protection
regulation with related circulation pumps is put out of operation due to power failure.
Connection of spring
-
return motor
54
Damper control
Outside/s upply
air
Red
Black
ST1
55
56
Damper control
Extract air
ST2
51
52
53
Red
Black
2-pos ition 24V AC
2-pos ition 24V
AC
If the damper motor turns the wrong way when HERU® CX is started, flip the damper
actuator.
993061001 Damper motor spring 24 VAC
Connection On/Off motor
54
Damper control
outside/Supply
air
Orange
Black
ST1
Violet
55
56
Damper control
Extract air
ST2
51
52
53
3-läges 24V AC
3-pos ition 24V AC
G0
Orange
Black
Violet
G0
If the damper motor is turned the wrong way when HERU® CX is started, switch
Violet/Orange.
ST1, ST2
Important!
Connection
Part no.:
Connection
Summary of Contents for HERU 400-2400 S
Page 1: ...U S E R M A N U A L E N H E R U 4 0 0 2 4 0 0 T S HERU T HERU S...
Page 2: ......
Page 14: ...14 120 Climatix HERU 400 2400 2018 02 13 Scope of assembly installation instructions...
Page 45: ...45 120 2018 02 13 Climatix HERU 400 2400 External components basic unit...
Page 97: ...97 120 2018 02 13 Climatix HERU 400 2400 Miscellaneous Menu structure Menu overview...
Page 98: ...98 120 Climatix HERU 400 2400 2018 02 13 Miscellaneous Start page Main index Unit...
Page 104: ...104 120 Climatix HERU 400 2400 2018 02 13 SERVICE HERU...
Page 111: ...111 120 2018 02 13 Climatix HERU 400 2400 SERVICE HERU...
Page 118: ...118 120 2017 11 03 Climatix HERU 400 2400 Troubleshooting...
Page 119: ......
Page 120: ......