Installation and operating manual for WATERFRIEND -Chlorine MRD-3 Page 27
Setting the upper ORP alarm
There is a setting facility for the required alarm limit value in the menu.
Procedure:
Press the
key
1. Select ORP settings
2. Select upper alarm
The current value is shown on the left side of the display.
To adjust this value, the following two options are available:
a) PLUS / MINUS keys
•
By pressing the arrow keys
or
, the value can be
modified stepwise.
•
Press
to store the new setting.
b) Keyboard
The value can also be set directly by using the keyboard on the
right side of the display:
•
enter the desired value
•
Press
to store the new setting.
Factory setting: 800 mV
Range: 700 to 999 mV
Setting the ORP power on delay
This setting should only be adjusted by a professional, and is only accessible in Expert Mode.
The controller only starts up after a delay period once the power supply has been provided and once
external enable has been switched on (e.g. filter control unit). This power-on delay is necessary because a
period specific to the overall system elapses once the filter pumps have been switched on before the
completely mixed water reaches the sensors. This mixing process is mainly dependent on the pool size, the
dimensions of the filter pump, the pipe length and the filter itself.
The delay period can, if required, be adapted to the actual pool size.
Procedure:
Press the
key
1. Select ORP settings
2. Select Start delay
The current value is shown on the left side of the display.
To adjust this value, the following two options are available:
a) PLUS / MINUS keys
•
By pressing the arrow keys
or
, the value can be
modified stepwise.
•
Press
to store the new setting.
b) Keyboard
The value can also be set directly by using the keyboard on the
right side of the display:
•
enter the desired value
•
Press
to store the new setting.
Factory setting: 60 minutes
Range: 1 to 120 minutes