Battery
LED indicator for battery fault,
Battery
LED
flashes every 2 seconds. The cause could be
a faulty contact or a battery that is no longer
adequate due to ageing. Check contacts! If
this check does not rectify the problem, install
new battery. On this topic see section 10.3.
Overload
LED indicator for indicating overloading of the
UPS system.
Table 8: Indications
10.5.2 Acoustic warnings
No. Acoustic
warning
Cause
Solution
1
1 x every 4
seconds
UPS in the
battery
mode
.
Check input voltage,
input fuse and
circuit breaker.
Battery low.
Replace battery.
2
1 x every second
Output overloaded.
Check the "UPS utilisa-
tion"
indicator. Re-
duce load if necessary.
General fault.
Please contact dealer.
3 Continuous
Battery low.
Charge or replace bat-
tery.
Table 9: Acoustic warnings
10.6 Trouble shooting
If the UPS system does not operate correctly, please attempt
to solve the problem using the table below.
No. Problem
Cause
Solution
Button not pressed
for long enough
Keep
pressed until
acoustic signal stops (3
sec.).
1
Does not switch
on after pressing
.
Mains cable not
connected cor-
rectly.
Check the cable connec-
tion, particularly the
seating of the connec-
tors.
Summary of Contents for ZINTO A 1000
Page 1: ...www online ups com Manual ZINTO A Series A 800 A 1000 A 1500 A 2000 A 3000 ...
Page 3: ...2 181 Manual ZintoA_final_ger_engl_it_20081017 doc 05 11 2008 Dipl Ing S Spitzley ...
Page 63: ...62 181 Manual ZintoA_final_ger_engl_it_20081017 doc 05 11 2008 Dipl Ing S Spitzley ...
Page 65: ...64 181 Manual ZintoA_final_ger_engl_it_20081017 doc 05 11 2008 Dipl Ing S Spitzley ...
Page 123: ...122 181 Manual ZintoA_final_ger_engl_it_20081017 doc 05 11 2008 Dipl Ing S Spitzley ...