CAUTION:
The XANTO RT 2000 and XANTO RT 3000 do
not contain internal batteries. To ensure proper
operation, the UPS must be connected to a Bat-
terypack.
8.2 Rack installation
If installing the UPS inside a rack, you must use a standard
19“ rack with a depth of at least 400mm. To ensure optimum
weight distribution, please use our optional mounting rails
(order no. “Rack-Kit”) or alternatively use mounting rails spe-
cific to the cabinet manufacturer.
1.) Use the mounting angle included in the scope of supply.
2.) Remove the M4x8 screws from both side panels of the
UPS (4 on each side).
3.) Attach the mounting angle using the screws you have just
removed.
4.) Mount the UPS in the rack and secure it.
8.3 Software installation
To install the DataWatch shutdown, management and monitor-
ing software, please follow the separate instructions included
on the CD.