Seite 76 von 128
10.4 Operational test
Please test general operation of the UPS whenever you carry
out maintenance work.
UPS operating state:
Whenever the primary power supply is active, the UPS should
operate in
normal mode
. In the event of a primary power sup-
ply failure, the UPS is forced to operate in
battery mode
. No
fault message should be output in either case.
Switchover:
Simulate a power failure by tripping the building wiring fuse.
The UPS should be able to switch between
normal mode
and
battery mode
(see Section 9.1) without any problems.
After simulating the power failure, reconnect the mains to the
UPS. The UPS should then switch back from
battery mode
to
normal mode
.
LEDs:
While the UPS is in the above operating states, check whether
the LEDs are providing a correct indication of the relevant
operating modes.
Summary of Contents for XANTO RT1000
Page 1: ...www online ups com Manual XANTO RT Series RT 1000 RT 2000 RT 3000 ...
Page 3: ...Seite 2 von 128 ...
Page 45: ...Seite 44 von 128 ...
Page 85: ...Seite 84 von 128 ...
Page 87: ...Seite 86 von 128 ...
Page 129: ...Seite 128 von 128 ...