Seite 64 von 128
Pin
Description
1 Battery
flat
(open collector)
2
UPS TxD (typ. RS-232 level)
3
UPS RxD (typ. RS-232 level)
4 Remote
inverter
OFF 5-12V DC, 10-24mA
(in battery mode)
5 GND
6 -
7 Battery
flat
(open emitter)
8
Battery mode (open emitter)
9
Battery mode (open collector)
Table 7: Interface pin assignment (DB9-socket)
Notes:
1.) Pins 1 & 7: floating output. Open if battery voltage normal.
Closed if battery voltage low.
2.) Pins 4 & 5: floating input. If an auxiliary voltage (5-12V
DC) is applied for at least 20 seconds when in battery
mode, the UPS will shut down. These pins do not perform
any other function.
3.) Pins 8 & 9: floating output. Open during normal operation,
closed during battery operation.
7.2.3 Slot for optional interface cards
XANTO RT is equipped with a slot for optional interface cards.
This ensures compatibility with the following ONLINE USV-
Systeme AG products:
Order no.
Description
DW5SNMP30 Network
management card, professional
DW7SNMP30
Network management card, basic
PHXUSB USB-adaptor
Table 8: Overview of interface accessories