OUTPUT
Rated voltage (V)
220V (standard), 230V/240V configurable
Waveform Sinusoidal
Frequency, UPS operation
50Hz +/- 0.2%
Distortion factor,
linear load
< 2% THD, R load
Distortion factor,
non-linear load
< 5% THD, RCD load
Crest factor
3:1
Power factor
typ. 0.7 (0.65 – 1.0)
Overload behaviour
Normal mode, inverter
overload <105%
Has no effect
Normal mode, inverter
overload 105 - 125%
5 minutes, then bypass mode
Normal mode, inverter
overload >125%
1 minute, then bypass mode
Battery mode, inverter
overload <105%
Has no effect
Battery mode, inverter
overload 105 - 125%
30 seconds, then standby mode
Battery mode, inverter
overload >125%
250ms, then standby mode
Efficiency, normal mode
>88%
Efficiency, battery mode
>83%
Output socket
4x
IEC320 C13
4x
IEC320 C13
2x
IEC320 C13
+ terminal
BATTERY
Type
CSB GP 1272
F2
CSB GP1272
F2
CSB HR
1234W F2
12V/7.2Ah
12V/7.2Ah
12V/9Ah
Quantity 3
6
6
Service life
3-5 years in accordance with EUROBAT
Charging time
5 hours to reach 90% capacity
Charging current (A)
1
Battery test
Automatic, manual, remote