32
The Performance Parameters List of Ducted Type Indoor Units
Model
Item
OV-R224P/Na-M
OV-R280P/Na-M
Cooling capacity
W
22400
28000
Heating capacity
W
25000
31000
Air volume
m
3
/h
4000
4800
Noise(H/L)
dB(A)
54
57
Motor input power
W
2000
2000
External Static Pressure
Pa
120
120
Phase number-Voltage-Frequency
380V 3N
~
50Hz
380V 3N
~
50Hz
The type of anti-electric shock
protection
I
Width
mm
1500
1500
Depth
mm
1000
1000
Outline
dimensions
Height
mm
500
500
The aperture of condensing
draiHge pipe
inch
1
"
Net weight
Kg
Please refer to the nameplate
Length
mm
1194
Dimensions of air
outlet
Width
mm
292
Length
mm
1194
Dimensions of
air return
Width
mm
342
Diameter of gas pipe
inch
φ
3/4
"
φ
7/8
"
Diameter of liquid pipe
inch
φ
3/8
"
φ
3/8
"
Note:
1. The performance parameters are tested under the rated working condition;
3. Please refer to the actual parameters on the nameplate.
4. The cooling capacity was tested in the condition of outdoor temp.35
(dry bulb)/24
(wet bulb), indoor temp.27
(dry bulb)/19
(wet bulb)
5. The heating capacity was tested in the condition of outdoor temp.7
(dry bulb)/6
(wet bulb), indoor temp.20
(dry
bulb), it is not include the heating capacity of auxiliary electric heat.
6. The value of noise is the value which was tested in the anechoic chamber, the measuring point is 1.4m under the unit,
the actual running the temp. will be higher due to the influence of environment.