8
Install of ducted type indoor unit
5). Install the Electrical Box.
In order to ease the maintaining work, we recommend to get of the electrical box part of the indoor unit to refix
it at the air outlet part. Please see following Fig 4.
Fig. 4 Schematic for the Electrical Box part
6). Adjust the tightness of the belt of the fan unit
The rotation of the fan is achieved by the transmission of the belt. The velocity and stability of the fan is associated with
the tightness of the belt and the tightness should be adjusted after a period of time. For a new belt, the tightness should be
adjusted for at least twice within 24 hours. After one week running, the tightness of the belt should be adjusted again, we
should routinely check it every 1-2 months; also ensure the test results complying with Table 2. The adjustment of the
tightness of the belt is shown in Fig. 5. Loosen screws fixing motor on the base, move motor along the direction of arrow
as shown in the picture, then fix the screw again.
The tightness level of belt is tested by tensiometer as shown in Fig. 6, when
△
reaches the deviation
length(Deviation=The total length beit/64) ,read the value on the meter, the value should be in the category
specified in Table 2.
Table.2 Tension range of the belt
Tension (N)
Section area of the belt
Diameter of the small belt (mm)
Min
Max
SPA
Φ80
7.5
10.9
Φ80
7.2
8.3
Φ71
5.8
6.6
SPZ
Φ67
7.8
9.0