13
Install of ducted type indoor unit
Notes:
1. When you choose to equip the receiving board (this component is optional) on the units it is
requried that set the 2nd position of S7 DIP switch to OFF position, meanwhile if need to plug the
communication cable from receiving board into 9 core terminal CN20 which locates on the mainboard,
and wired remote controller is disabled.
2. When you choosed to equip wired remote controller to the units, it needs to set the 2nd position of
S7 DIP switch to the ON position, and connect 4 core communication cable to CN19 terminal on the
mainboard; the address code on wired remote controller and indoor mainboard address code MUST
BE THE SAME, after doing this, the receiving header is disabled.
3. The driving method of the blower on OV-R224P/Na-M and OV-R280P/Na-M is Belt driving, there is
only 1 fan speed, if need to adjust the E.S.P, it is required that the adjustment of the pulley is within
safe range (please consultant technical professionals)
5 bits functional DIP switch mainboard
S7 function DIP
S1Address DIP