![background image](http://html1.mh-extra.com/html/omron/wago-i-o-system/wago-i-o-system_connection-manual_1633448008.webp)
5
.
Applicable
Devices and Device Configuration
5
5.2. Device Configuration
The hardware components to reproduce the connection procedure of this document are as
follows:
Manufacturer
Name
Model
Version
OMRON
CPU Unit
(Built-in EtherCAT port)
NJ501-1500
Ver.1.07
OMRON
Power Supply Unit
NJ-PA3001
OMRON
Sysmac Studio
SYSMAC-SE2[][][]
Ver.1.08
-
Personal computer
(OS: Windows 7)
-
-
USB cable
(USB 2.0 type B connector)
-
OMRON
Ethernet cable (with industrial
Ethernet connector)
XS5W-T421-[]M[]-K
WAGO
WAGO-I/O-SYSTEM Fieldbus
Coupler with ID Address Selection
Switch
750-354/000-001
Rev.
0x00010002
WAGO
Power supply module
750-602
WAGO
2-channel digital output module
750-501
WAGO
4-channel digital input module
750-407
WAGO
End module
750-600
WAGO
ESI file
WAGO_750_354.xml
-
24 VDC power supply
-
Precautions for Correct Use
Prepare the ESI file shown in this section beforehand. The ESI file can be downloaded from
the WAGO website.
(WAGO
https://eshop.wago.com/JPBC/0_5StartPage.jsp?supplierAID=750-354%2F000-001&catalog
ID=WAGO01&zone=7)
Contact WAGO if the file is not available.
USB cable
NJ501-1500
(Built-in EtherCAT port)
750-354/000-001+
750-602+750-501+
750-407+750-600
Personal computer
(Sysmac Studio installed,
OS: Windows 7)
Ethernet cable
24 VDC
power supply
24 VDC
power supply
Summary of Contents for WAGO-I/O-SYSTEM