Errors Detected by the Universal Input Unit
Section 5-2
Processing and Results in the Continuously Refreshed Area
Processing and Results in the Initial Settings Area
Processing
Result
LED indicators on Unit
Data range error address
stored in DM Area
While the power is ON, an
out-of-range setting is set in
the continuously refreshed
area.
The Unit will continue operat-
ing with the original continu-
ously refreshed area data.
ERC indicator is lit.
RUN indicator remains lit.
The lowest DM address
where the out-of-range error
occurred is stored, in four
digits hexadecimal, as the
offset value from m (i.e., the
number of added words).
↓
Leave the power ON and
change the setting to a valid
value.
The Unit will operate with the
edited settings in the contin-
uously refreshed area.
ERC indicator is lit.
RUN indicator remains lit.
If there is no other error,
0000 hex is stored. (If there
is another error, the offset
value for that DM address is
stored.)
When the PLC is turned ON
or the Unit is restarted with
an error still in effect.
The Unit will not start up.
ERC indicator is lit.
RUN indicator is not lit.
The lowest DM address
where the out-of-range error
occurred is stored, in four
digits hexadecimal, as the
offset value from m (i.e., the
number of added words).
↓
When the setting is made
within the allowable range,
and the PLC is turned ON or
the Unit is restarted
The Unit starts up normally.
ERC indicator is not lit.
RUN indicator is lit.
If there is no other error,
0000 hex is stored. (If there
is another error, the offset
value for that DM address is
stored.)
Processing
Result
LED indicators on Unit
Data range error address
stored in DM Area
While the power is ON, an
out-of-range setting is set in
the initial settings area.
The Unit will continue operat-
ing with the original the initial
settings area data.
ERC indicator is lit.
RUN indicator remains lit.
If there is no error in the set-
tings, the value remains
0000 hex. (If there is an
error, the offset value for that
DM address is stored.)
↓
When the PLC is turned ON
or when the Unit is restarted
The Unit will not start up.
ERC indicator is lit.
RUN indicator is not lit.
The lowest DM address
where the out-of-range error
occurred is stored, in four
digits hexadecimal, as the
offset value from m (i.e., the
number of added words).
↓
When the setting is made
within the allowable range,
and the PLC is turned ON or
the Unit is restarted
The Unit starts up normally.
ERC indicator is not lit.
RUN indicator is lit.
If there is no other error,
0000 hex is stored. (If there
is another error, the offset
value for that DM address is
stored.)