41
Expansion Setting Area
Section 4-3
DM words m+39 and m+40 enable the Expansion Setting Area and set it
to CIO 0005.
If the process value of input 1 exceeds the high limit alarm value, CPU
Unit bit CIO 2000.01 is turned ON (1). If the CJ1 PLC’s ladder program
is being executed in RUN mode or MONITOR mode, the input condi-
tion of CIO 2000.01 (2) will be reflected in CIO 4.01 (3) and sent to Out-
put Unit OC221 (4) where the alarm will be output.
If DM words D20039 and D20040 set CIO 0005 as the Expansion Set-
ting Area (5), CIO 5.01 is turned ON directly from the AD04U Input Unit
(6) and the alarm is output externally from Output Unit OC201 (7).
This is how the Expansion Setting Area settings can be used to set
alarm outputs without using the ladder program.
Universal Input Unit
CJ1 CPU Unit
Input 1
CJ1W-OC221
16 outputs
CIO 0004
Unit number
set to 0.
AD04U
CIO 2000
CIO 2009
D20000
D20039
D20040
D20099
Data areas
OC221
OC201
CJ1W-OC201
8 outputs
CIO 0005
Ladder program processing
2000.01
4.01
CIO 0
CIO 4
CIO 5
External alarm
circuit
External alarm
circuit
(1)
(6)
(5)
(2)
(3)
(4)
(7)
Set from Expansion Setting Area.
to
to
to
to
to
Expansion Setting Area
set to CIO 0005.