54
Supplementary Explanations of Functions
Appendix B
Switching to the High or Low Value when Input Disconnection
Occurs during Process Value Scaling with Negative Gain
If an input becomes disconnected during process value scaling with negative gain, either the maximum (high)
or minimum (low) process value can be set.
If the process value’s
High/low value after sensor error
setting is set to high, the maximum process value will be
set when the input is disconnected.
If the process value’s
High/low value after sensor error
setting is set to low, the minimum process value will be
set when the input is disconnected.
4200 (105%)
4000 (100%)
3000 (75%)
0 (0%)
−
200 (
−
5%)
3.2 mA
4 mA
20 mA
20.8 mA
Input signal
Process value (stored data)
Process value scaling with negative gain
When process value is greater than 3,000,
output turns ON.
When input signal is less than 8 mA, output turns ON.
4200 (105%)
4000 (100%)
0 (0%)
−
200 (
−
5%)
3.2 mA
4 mA
20 mA
20.8 mA
Input signal
Process value (stored data)
Process value scaling with negative gain
If the high value is set, the maximum
value of 4200 will be specified when an
input is disconnected.
If the low value is set, the minimum value
of
−
200 will be specified when an input is
disconnected.