6-4
H
Control Characteristics
Control method
Sine-wave PWM method (automatic torque boost)
Frequency control
range
1.5 to 400 Hz
Frequency accuracy
(temperature
fluctuation)
Digital command:
±
0.01% (–10
°
C to 50
°
C)
Analog command:
±
1% (25
±
10
°
C)
Frequency setting
resolution
Digital command:
0.1 Hz (less than 100 Hz), 1 Hz (100 Hz or more)
Analog command:
0.06 Hz (60 Hz)
Frequency output
resolution
0.1 Hz (operation resolution)
Overload resistance
1 minute or less when 150% of rated output current is received
Frequency setting
signal
0 to 10 VDC (20 k
Ω
) or 4 to 20 mA (250
Ω
)
Note This setting can be switched using the internal DIP switch.
Acceleration/Decelerati
on time
0.0 to 999 seconds (acceleration and deceleration times are
set separately)
Braking torque
(continuous
regenerative braking)
Approximately 20%
Note 125% to 220% when braking resistor is externally
installed.
Voltage/Frequency
characteristics
Simple V/f pattern setting
Specifications
Chapter 6
Summary of Contents for SYSDRIVE 3G3EV SERIES
Page 1: ...USER S MANUAL SYSDRIVE 3G3EV Standard Models Compact Low noise Inverter Cat No I011 E1 3...
Page 5: ...Chapter 1 Getting Started 1 1 Items to be Checked when Unpacking 1 2 Precautions 1...
Page 9: ...Chapter 2 Overview 2 1 Features 2 2 Component Names 2...
Page 14: ...Chapter 3 Design 3 1 Installation 3 2 Wiring 3...
Page 72: ...Chapter 6 Specifications 6 1 Specifications of Main Unit 6...