4-10
H
List of Constants
Constant
no.
Dedicated
indicator
Description
Setting range
Factory setting
n01
Constant write-inhibit selec-
tion/constant initialization
0, 1, 8, 9
1
n02
Operation mode selection
0 to 5
0
n03
Interruption mode selection
0, 1
0
n04
Forward/reverse rotation
selection
For, rEv
For
n06
Multi-function input selec-
tion
0 to 4
1
n09
Multi-function output selec-
tion
0, 1, 2
1
n11
Frequency reference 1
0.0 to 400
6.0 (Hz)
n12
Frequency reference 2
0.0 to 400
0.0 (Hz)
n20
Acceleration time
0.0 to 999
10.0 (seconds)
n21
Deceleration time
0.0 to 999
10.0 (seconds)
n24
Maximum frequency
50.0 to 400
60.0 (Hz)
n25
Maximum voltage
1 to 255
(see note 1)
200 (V)
(see note 1)
n26
Maximum voltage frequency 1.6 to 400
60.0 (Hz)
n31
Electronic thermal reference
current
0.0 to see note 2
See note 2
n33
Stall prevention during de-
celeration
0, 1
0
n36
Operation after recovery
from power interruption
0, 1, 2
0
n37
Carrier frequency
1, 2, 3, 4
(see note 3)
4
(see note 4)
n39
Frequency reference gain
0.10 to 2.55
1.00
n40
Frequency reference bias
–99 to 99
0 (%)
n61
Stop Key selection
0, 1
0
n64
Operator’s frequency set-
ting method
0, 1
0
n68
Error history
(Display only)
Note 1. The upper limit of the setting range and the factory setting for the 400-VAC class
are double the above values.
Note 2. The setting range and factory setting for n31 (electronic thermal reference cur-
rent) depend on the Inverter model. For details, refer to page 4-19.
Normally, set the rated motor amperage in n31.
Preparing for Operation
Chapter 4
Summary of Contents for SYSDRIVE 3G3EV SERIES
Page 1: ...USER S MANUAL SYSDRIVE 3G3EV Standard Models Compact Low noise Inverter Cat No I011 E1 3...
Page 5: ...Chapter 1 Getting Started 1 1 Items to be Checked when Unpacking 1 2 Precautions 1...
Page 9: ...Chapter 2 Overview 2 1 Features 2 2 Component Names 2...
Page 14: ...Chapter 3 Design 3 1 Installation 3 2 Wiring 3...
Page 72: ...Chapter 6 Specifications 6 1 Specifications of Main Unit 6...