4-12
Example of 3-wire Sequence Mode
Stop
switch
(contact b)
Run
switch
(contact a)
Run command (starts Inverter when “closed”)
Stop command (stops Inverter when “opened”)
Forward/Reverse rotation command (rotates
motor in forward direction when “opened”;
rotates motor in reverse direction when “closed”)
Common
Example of Operation
Forward rotation
Motor operation
Reverse rotation
Run command
Stop command
Forward/Reverse
rotation command
n02
Operation Mode Selection
Setting range
0 to 5
Factory setting 0
This constant is used to specify whether the Inverter is to be operated with a Digital
Operator or external signals.
Value
Run command
Frequency reference
DIP switch setting
0
Digital Operator
Digital Operator (n11)
OFF
1
Control terminal
Digital Operator (n11)
OFF
2
Digital Operator
Control terminal (voltage input)
OFF
3
Control terminal
Control terminal (voltage input)
OFF
4
Digital Operator
Control terminal (amperage input) ON
5
Control terminal
Control terminal (amperage input) ON
Note 1. The above setting operation can be performed when constant no. 02 is se-
lected. This operation is also possible when the dedicated indicator (“MODE”)
is lit.
Preparing for Operation
Chapter 4
Summary of Contents for SYSDRIVE 3G3EV SERIES
Page 1: ...USER S MANUAL SYSDRIVE 3G3EV Standard Models Compact Low noise Inverter Cat No I011 E1 3...
Page 5: ...Chapter 1 Getting Started 1 1 Items to be Checked when Unpacking 1 2 Precautions 1...
Page 9: ...Chapter 2 Overview 2 1 Features 2 2 Component Names 2...
Page 14: ...Chapter 3 Design 3 1 Installation 3 2 Wiring 3...
Page 72: ...Chapter 6 Specifications 6 1 Specifications of Main Unit 6...