3-18
D
Wires to be Used
Always use twisted-pair shielded wires to prevent malfunctions due to noise.
Wire type
Wire size
Wire to be used
Single wire
0.5 to 1.25 mm
2
Polyethylene-insulated cable for
Stranded wire
0.5 to 1.25 mm
2
instrumentation (with shield)
D
Wiring Method
•
The wiring procedure is the same as for sequence input/output terminals, described
previously.
•
Always separate the cables from the main circuit cables and other power cables.
•
Connect the shield to the ground terminal of the Inverter. Do not connect to the control-
ler.
•
Insulate the shield with tape to prevent it from coming into contact with other signal
lines and devices.
H
Tightening Torque of Control Circuit Terminals
Tighten the control circuit terminals to the torque of 0.5 N
S
m which is the same torque
as for the M3 screws.
Note 1. Applying a torque of greater than 0.5 N
S
m may damage the terminal block.
Note 2. If the tightening torque is insufficient, wires may be disconnected.